Mitsubishi Electric AL-ASI-BD/AL2-ASI-BD Инструкция по применению

Тип
Инструкция по применению
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Dimensioni esterne
Dimensiones externas
AL-ASI-BD
ITL
ESP
ASI
-
2 6 . 5 ( 1 . 0 4 " )
5 3 . 5 ( 2 . 1 1 " )
9 0 ( 3 . 5 4 " )
ASI
+
ASI
-
ASI
+
2 4 . 5 ( 0 . 9 6 " )
5 3 . 1 ( 2 . 0 9 " )
9 0 ( 3 . 5 4 " )
ASI
-
ASI
+
ASI
-
ASI
+
mm(inch)
AL2-ASI-BD
Figure 1
Figure 2
ASI
-
1
2
ASI
+
4
3
ASI
-
ASI
+
AC 100-240V
POWER
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
1 2
3
4
5
6
7
8
9
10
11
12
IN
L
N
~
ASI
+
ASI
-
OK
ESC
~
ASI
-
ASI
+
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
LN
~
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
OK
ESC
ASI
+
ASI
-
ASI
+
ASI
-
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
A
B
A
Il presente manuale contiene il testo, i diagrammi e le spiegazioni che
guideranno il lettore nell’esecuzione dell’installazione e nel corretto
impiego del modulo interfaccia AL-ASI-BD e AL2-ASI-BD AS. Il
manuale deve essere letto prima di eseguire l’installazione o di utilizzare
l’unità. Per ulteriori informazioni consultare il manuale hardware
α o α2,
e i manuali di programmazione dei microcontrollori della serie
α / α2.
Avvertenza
La cassetta di memoria può essere sostituita unicamente da person-
ale specializzato a conoscenza delle specifiche elettriche locali e
nazionali.
Per installare o rimuovere la cassetta di memoria occorre dapprima
disinserire l’alimentazione principale.
Sostituire il coperchio dopo aver rimosso la cassetta di memoria.
Mitsubishi Electric non si assume in alcun caso la responsabilità di
danni derivanti dall'installazione o dall'impiego del prodotto.
1. INTRODUZIONE
Il modulo AL-ASI-BD e AL2-ASI-BD (in seguito AL-ASI-BD) é un modulo utilizzato insieme
alle seguenti serie di controllori
α (α e α2) per la comunicazione e trasmissione di dati
mediante la rete AS-I (rete di Interfaccia Attuatore-Sensore).
La scheda AL-ASI-BD si collega all'unità principale del controllore serie
α formando una
stazione secondaria per una rete di tipo AS-I (4 ingressi + 4 uscite). Per realizzare una rete
AS-I si possono collegare sino ad un massimo di 31 slave. L'alimentazione necessaria
viene fornita attraverso il bus dall'alimentatore dell'interfaccia AS-I. Il segnale di
comunicazione viene sovrapposto a quello di alimentazione sul bus AS-I.
2. SPECIFICHE TECNICHE
Per le specifiche generali rimandiamo al manuale delle serie hardware α (α o α2).
Tabella 1. Associazione Modulo-Microcontrollore
Modello di Interfaccia Modello di Microcontrollore
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Tabella 2. Specifiche di comunicazione dell'hardware
Posizione Descrizione
Numero di I/O 4 ingressi (E01-E04) + 4 uscite (A01-A04)
Tempo di refresh I/O 5ms
Distanza rete max. 100 m
Tensione di alimentazione
esterna
30,5 V c.c. (alimentatore tramite interfaccia
AS-I)
Consumo di corrente esterna 40 mA o inferiore
Conforme alle norme AS-I, CE
Tabella 3. Specifiche di comunicazione del software
Posizione Descrizone
Numero di stazioni
Impostato dalla stazione primaria
(impostazione di fabbrica 0)
Codice di I/O 7
Codice di I/D F
Bit dati D0-D3
ingresso uscita 01 - 04 (E01 - E04, A01 -
A04)
Bit parametri
P0
Da monitor di comunicazione (impostata
per default)
*1
P1,P2,P3 Non utilizzato
ITL
*1 Funzione per resettare il segnale di ingresso quando la comunicazione
dell'interfaccia AS è disattivata per 70 ms ed oltre.
3. CABLAGGIO E INSTALLAZIONE
Per il cablaggio dell’interfaccia AS-I, consultare la figura 1.
Utilizzare il cavo piatto (giallo) dell'interfaccia AS-I per collegare la scheda AL-ASI-
BD alla rete.
Per l'installazione della AL-ASI-BD, consultare la figura 2:
Prima di rimuovere il coperchio, disinserire tutti i terminali
dall'alimentazione.
1) Rimuovere la vite ‘A’ e conservarla.
2) Rimuovere con cautela la mascherina della porta di espansione montata in
fabbrica.
3) Tagliare la sezione ‘B’ dell'unità base del controllore della serie α.
4) Collocare la scheda AL-ASI-BD sull'unità base.
5) Serrare la vite ‘A’ a una coppia di serraggio di 0,4 N·m.
Quando si collega il cavo dell'interfaccia AS-I al modulo, serrare le viti del pin di
comunicazione con una coppia pari a 0,5 - 0,6 N·m.
4. IMPOSTAZIONE DELL'INDIRIZZO
SECONDARIO E DIAGNOSI
Un indirizzo secondario può essere impostato in due modi, ovvero tramite la scheda
primaria dell'interfaccia AS-I oppure con un dispositivo di programmazione. Quando
viene aggiunta una nuova stazione al bus di interfaccia AS-I, la scheda primaria
assegnerà l'indirizzo libero più basso.
Gli indirizzi secondari sono compresi in un range tra 1 e 31 e possono essere
assegnati soltanto ad una scheda con indirizzo iniziale 0 (zero). Prima della
spedizione, le nuove schede vengono preimpostate su 0. Se una scheda è stata
precedentemente assegnata ad un indirizzo diverso da 0, prima di poterla
aggiungere alla rete dovrà essere impostata sullo zero.
Alla rete si possono aggiungere molti moduli uno alla volta; tutti, eccetto uno, devono
essere impostati come moduli passivi (imposta N1=1). Una volta accesa la rete, i
moduli possono essere attivati singolarmente (impostare N1=0) dove il master di rete
assegnerà il numero di stazione.
Le stazioni devono essere aggiunte alla rete una per volta. In questo caso, la rete
deve essere disinserita prima di effettuare qualsiasi aggiunta. Per maggiori dettagli
su come modificare il numero di stazioni da una scheda primaria di interfaccia AS-I,
consultare il manuale delle schede primarie di interfaccia AS-I.
Controlli di errore applicabili:
1) Se si verifica un errore di comunicazione (M6):
- controllare i collegamenti con la scheda primaria di interfaccia AS-I e che il
numero della stazione secondaria sia corretto.
2) Se si verifica un errore di alimentazione comunicazione (M7):
- controllare il collegamento del cavo del bus di interfaccia AS-I su ogni unità
connessa, l'alimentatore dell'interfaccia AS-I ed il relativo funzionamento.
Bit sistema
M6
"ON" se si verifica un errore di
comunicazione sull'interfaccia AS
-I
M7
"ON" se si verifica un errore di
comunicazione per mancanza di corrente
all'interfaccia AS
-I
Bit control N1
ON: scollegare dalla rete l´interfaccia
AS-I
OFF: collegare alla rete l´interfaccia AS-I
Tabella 4. Configurazione dei pin del connettore AL-ASI-BD
Numero Nome Impiego
1 & 3 ASI + Per cavo collegamento ASI +
2 & 4 ASI - Per cavo collegamento ASI -
Tabella 3. Specifiche di comunicazione del software
Posizione Descrizone
Este manual contiene textos, diagramas y explicaciones que
ayudarán al lector en la instrucción y operación correctas de los
módulos de interfaz AL-ASI-BD y AL2-ASI-BD AS. Este debiera
leerse y comprenderse atentamente antes de instalar o usar la
unidad. Para mayores informaciones diríjase a los Manuales de
Hardware α ó α2, y a los Manuales de Programación de las series
α ó α2.
Advertencia
Las únicas personas autorizadas a reemplazar el módulo AL-
ASI-BD son aquellos especialistas que dominan las normas
locales y nacionales de electrotecnia.
Desconecte la alimentación eléctrica antes de instalar o retirar
el módulo AL-ASI-BD.
Reemplace la cubierta después de retirar el módulo AL-ASI-
BD.
Mitsubishi Electric no se responsabiliza bajo ninguna circun-
stancia por cualquier daño ocurrido como consecuencia de la
instalación o la utilización inapropiadas de este equipo.
1. INTRODUCCIóN
El módulo de panel de la interfaz del sensor actuador AL-ASI-BD y AL2-ASI-BD (en
adelante referido como AL-ASI-BD) se utiliza en conjunto con el siguiente
controlador de las series a (a y a 2) para la comunicación del datos a través de una
red para la interfaz del sensor actuador (interfaz AS).
El AL-ASI-BD se conecta al cuerpo principal del controlador de serie α, formando
una estación esclava al servicio de una red (4 entradas, 4 salidas). Al crear esta red
de ampliación, es posible conectar 31 estaciones esclavas como máximo. La fuente
de energía eléctrica de la interfaz AS suministra la corriente necesaria para la
comunicación a través del bus de la red.
2. ESPECIFICACIONES
En el caso de especificaciones generales por favor referirse al Manual de Hardware
de la serie a (α ó α2).
Tabla 1. Controlador aplicable
Nombre del modelo de la
interfaz
Nombre del modelo del controlador
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Tabla 2. Especificaciones de la comunicación a nivel de
hardware
Concepto Descripción
Número de I/O 4 entradas (E01-E04) 4 salidas (A01-A04)
Tiempo de renovación I/O 5ms
Alcance de la red máx. 100m
Voltaje de alimentación
externa
30,5V CC (fuente de interfaz AS)
Consumo 40 mA o menos
Conforme a las normas ASi, CE
Tabla 3. Especificaciones de la comunicación a nivel de
software
Concepto Descripción
Número de estación
Configurada por la estación maestra (por
defecto es 0 de fábrica)
Código I/O 7
Código I/D F
Bit de datos D0-D3
Entrada Salida 01 - 04 (E01 - E04, A01 -
A04)
Bit de
configuración
P0
Monitor de comunicación (configurada por
defecto).
*1
P1,P2,P
3
No usado
ESP
*1 Función para resetear la señal de entrada cuando la comunicación de la interfaz
AS se interrumpe por 70 ms o más.
3. CONEXION E INSTALACIÓN
Para conocer la conexión de la interfaz AS consulte la figura 1.
Utilice un cable plano para interfaz AS (amarillo) para conectar el AL-ASI-BD a la red.
Para instalar el AL-ASI-BD consulte la figura 2;
Desconectar todos los terminales de la fuente de alimentación de
energía antes de retirar la cubierta.
1) Retire el tornillo ‘A’ y guárdelo.
2) Retire con cuidado la cubierta puertos de expansión montada de fábrica.
3) Separe la sección ‘B’ de la unidad base del controlador de la serie α.
4) Vuelva a colocar el AL-ASI-BD en la unidad base.
5) Apriete el tornillo ‘A’ a un torque de 0,4 N·m.
Al conectar el cable de interfaz AS al módulo, apriete los tornillos de los pines del
conector de comunicación con un torque de 0,5 - 0,6 N·m.
4. ASIGNACIÓN DE DIRECCIONES
AL ESCLAVO Y DIAGNÓSTICO
La dirección del esclavo de cada una de las direcciones esclavas pueden configurarse ya
sea con la unidad central o con un dispositivo de programación. Al agregarse una nueva
estación al bus de la interfaz AS, el módulo maestro asigna la dirección más baja
disponible.
Las direcciones de las estaciones esclavas varían de 1 a 31 y pueden asignarse
solamente a un módulo provisto de dirección inicial 0 (cero). Los módulos nuevos vienen
preajustados a 0 antes de su envío desde fábrica. Si a un módulo se le ha asignado antes
una dirección que no sea 0, tendrá que reinicializarse a 0 antes de poder agregarlo a la
red.
Las estaciones se agregan a la red a razón de una por vez. En esas circunstancias es
preciso desconectar la red antes de cada ampliación. Consulte el manual de módulos del
maestro de la interface AS para saber cómo cambiar los números de los módulos de la
unidad central.
Comprobaciones a realizar en caso de error
1) Si ocurre un error por defecto de comunicación (M6);
- verifique las conexiones al maestro de la interfaz AS y compruebe si el número
de la estación esclava es el correcto,
2) Si se produce un error de suministro de alimentación a la comunicación (M7);
- verifique la conexión del cable del bus de la interfaz AS en cada una de las
unidades afectadas, incluida la fuente de alimentación de la interfaz AS y su
funcionamiento.
Bit de sistema
M6
"ON" (conectado) cuando ocurre un error de
comunicación de la interfaz AS
M7
"ON" (conectado) cuando ocurre un error de
comunicación a causa de una falla de
energía de la interfaz AS
Bit de control N1
ON: Desconectado de la red de interfaz
AS.
OFF: Conecta a la red de interfaz AS.
Tabla 4. Asignación de pines del conector AL-ASI-BD
Número Nombre Empleo
1 y 3 ASI + Para conexión por cable ASI +
2 y 4 ASI - Para conexión por cable ASI -
Tabla 3. Especificaciones de la comunicación a nivel de
software
Concepto Descripción
JY992D81401G
Effective April 2015
Specifications are subject to
change with out notice.
Manual number : JY992D81401
Manual revision : G
Date : 04/2015
JY992D81402G
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
AL-ASI-BD, AL2-ASI-BD
Maskinvaruhandbok
Руководство по аппаратной части
JY992D81402G
Yttre mått
Внешние размеры
AL-ASI-BD
SWE
RUS
ASI
-
26.5
53.5
90
ASI
+
ASI
-
ASI
+
24.5
53.1
90
ASI
-
ASI
+
ASI
-
ASI
+
mm
AL2-ASI-BD
Figure 1
Figure 2
ASI
-
1
2
ASI
+
4
3
ASI
-
ASI
+
AC 100-240V
POWER
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
1 2
3
4
5
6
7
8
9
10
11
12
IN
L
N
~
ASI
+
ASI
-
OK
ESC
~
ASI
-
ASI
+
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
LN
~
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
OK
ESC
ASI
+
ASI
-
ASI
+
ASI
-
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
A
B
A
Den här handboken innehåller text, scheman och förklaringar, som
vägleder till korrekt programmering och användning av AS-
gränssnittsmodulerna AL-ASI-BD och AL2-ASI-BD. Läs igenom och
förstå handboken innan du försöker installera eller använda enheten.
Ytterligare information finns i handböckerna för
α-maskinvara eller α2-
maskinvara samt programmeringshandböcker för
α och α2-serien.
Viktigt
AL-ASI-BD och AL2-ASI-BD får endast bytas av personer med
utbildning i och kännedom om gällande lokala och nationella elstan-
darder.
Stäng av strömförsörjningen för att installera eller avlägsna AL-ASI-
BD eller AL2-ASI-BD.
Sätt tillbaka kåpan efter att ha avlägsnat AL-ASI-BD eller AL2-ASI-
BD.
Mitsubishi Electric är under inga omständigheter ersättningsskyldigt
eller ansvarigt för följdskador som kan uppstå till följd av installation
eller användning av utrustningen.
1. INLEDNING
AL-ASI-BD och AL2-ASI-BD gränssnittskortmodul för ställdonssensor (Actuator Sensor
Interface-modul, nedan kallad AL-ASI-BD) används tillsammans med följande styrenhet i
serierna
α (α och α2) för datakommunikation via ett AS-gränssnittsnätverk (Actuator
Sensor-nätverk).
AL-ASI-BD ansluts till huvudenheten på en styrenhet i serien, så att den utgör en
slavstation i ett AS-gränssnittsnätverk (4 ingångar, 4 utgångar). Högst 31 slavenheter kan
anslutas för att bilda ett AS-gränssnittsnätverk. Strömförsörjning för kommunikation sker
via AS-gränssnittsbussen, via AS-gränssnittets strömförsörjningsenhet.
Kommunikationssignalen överlagras över strömförsörjningen på AS-gränssnittsbussen.
2. SPECIFIKATIONER
Allmänna data finns i maskinvaruhandböckerna för serierna α (α och α 2).
Tabell 1. Styrenheter som kan användas
Gränssnittets modellnamn Styrenhetens modellnamn
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Tabell 2. Maskinvarudata, kommunikation
Post Innehåll
Antal I/O 4 ingångar (in. E01 - E04) 4 utgångar (ut. A01 - A04)
I/O-uppdateringstid Max. 5ms
Nätverksavstånd Max. 100m
Extern
spänningsförsörjning
Typiskt 30,5 V DC (strömförsörjning för AS - gränssnitt)
Strömförbrukning,
extern
strömförbrukning
40 mA eller mindre
Uppfyller AS-gränssnittscertifiering, CE
Tabell 3. Especificaciones de la comunicación a nivel de
software
Concepto Innehåll
Stationsnummer Anges från masterstation (fabriksinställning 0)
I/O-kod 7
ID-kod F F
Databit D0-D3 ingång/utgång 01 - 04 (E01 - E04, A01 - A04)
Parameterbit
P0
Kommunikationsövervakning
(standardinställd).
*1
P1,P2,P3 Används inte
SWE
*1 Funktion för att återställa insignal (E01 - E04) när kommunikationen med
AS-gränssnittet bryts under 70 ms eller mer.
3. KABELANSLUTNING OCH
INSTALLATION
Kabelanslutning för AS-gränssnitt visas i figur 1.
Använd AS-gränssnittets flatkabel (gul) för att ansluta AL-ASI-BD till nätverket.
För installation av AL-ASI-BD, se figur 2.
Koppla bort samtliga anslutningar från strömförsörjningen innan
skyddet avlägsnas.
1) Avlägsna och spara skruv A.
2) Avlägsna försiktigt det fabriksmonterade expansionsplatsskyddet.
3) Skär bort sektion B av α-styrenhetens huvudenhet.
4) Sätt tillbaka AL-ASI-BD på huvudenheten.
5) Dra åt skruv "A" med 0,4 N·m.
När du ansluter AS-gränssnittskabeln till modulen, skall du dra åt
kommunikationsanslutningens skruvar med 0,5 - 0,6 N·m.
4. SLAVADRESSINSTÄLLNING
OCH DIAGNOSTIK
Adressen till AL-ASI-BD måste ställas in från mastermodulen för AS-gränssnitt.
Inställningsområdet för slavadress är 1 till 31. Nya moduler är förinställda till 0 vid
leverans. Om en modul tidigare tilldelats någon annan adress än 0, måste den
återställas till 0 innan den kan läggas till i ett nytt AS-gränssnittsnätverk.
I handboken för mastermodulen för AS-gränssnitt finns mer information om hur du
ställer in stationsadress från AS-gränssnittsmastern.
Många moduler kan läggas till samtidigt till nätverket. Alla utom en av dem skall vara
satt till passivt läge (sätt N1 = 1). När nätverket spänningssatts kan modulerna
aktiveras var för sig (sätt N1 = 0), där masterstationen tilldelar en slavadress.
Tillämpliga felkontroller:
1) Om ett kommunikationsfel (M6) uppkommer:
- Kontrollera anslutningarna till AS-gränssnittsmastern, samt att
slavstationsnumret är korrekt.
2) Om strömförsörjningsfel för kommunikation (M7) uppkommer:
Kontrollera AS-gränssnittsbusskabelns anslutning vid berörda enheter.
Kontrollera även strömförsörjningen till och funktionen hos AS-gränsnittet.
Systembit
M6
PÅ när kommunikationsfel för AS-gränssnitt
uppkommer.
M7
PÅ när kommunikationsfel för AS-gränssnittets
strömförsörjning uppkommer.
Kontrollbit N1
ON: Koppla bort från AS-gränssnittsnätverk.
OFF: Anslut till AS-gränssnittsnätverk.
Tabla 4. AL-ASI-BD stifttilldelning
Beteckning Namn Användning
1 & 3 ASI + För AS-gränssnitt, + kabelanslutning
2 &4 ASI - För AS-gränssnitt, - kabelanslutning
Tabell 3. Especificaciones de la comunicación a nivel de
software
Concepto Innehåll
В данном руководстве содержатся описания, схемы и
пояснения, которые помогут пользователю надлежащим
образом установить модули AS-интерфейса AL-ASI-BD и AL2-
ASI-BD и обеспечить их нормальное функционирование.
Данное руководство следует прочесть и усвоить, прежде чем
приступать к каким- либо работам по установке или
эксплуатации данного устройства. Дальнейшую информацию
вы найдете в Руководстве по аппаратной части контроллера
серии α 2 или α и в Рук
оводстве по программированию
контроллера серии α2 или α
Внимание
К работам по замене модулей AL-ASI-BD и AL2-ASI-BD
допускаются только квалифицированные электрики,
прошедшие подготовку к электромонтажным работам в
соответствии с местными и государственными
стандартами.
Выключите электропитание, прежде чем устанавливать
или вынимать модули AL-ASI-BD или AL2-ASI-BD.
После отсоединения модуля AL-ASI-BD или AL2-ASI-BD
установите на место крышку.
Mitsubishi Electric ни при каких обстоятельствах не несет
юридической ответственности за какие-ли
бо п
овреждения,
которые могут оказаться следствием установки или
эксплуатации данного устройства.
1. ВВЕДЕНИЕ
Модули AS-интерфейса (интерфейса датчиков и исполнительных устройств)
AL-ASI-BD и AL2-ASI-BD (далее называемые «модули AL-ASI-BD»)
предназначены для использования с контроллерами серии α (α и α 2) для
передачи данных по сети AS-интерфейса.
Модуль AL-ASI-BD подключается к главному блоку контроллера серии α2 и
создает подчиненную станцию сети AS-интерфейса (4 точки входа, 4 точки
выхода). Максимальное количество подчиненных узлов, которое можно
подключить к сети AS-и
нтерфейса – 31. Электропитание для связи подается по
шине AS-интерфейса от источника питания AS-интерфейса. Сигнал связи
накладывается на напряжение питания.
2. ТЕХНИЧЕСКИЕ
ХАРАКТЕРИСТИКИ
Общие технические характеристики см. в Руководстве по аппаратной части
контроллера серии α2 или α.
Таблица1 Тип контроллера для интерфейса
Модель интерфейса Модель контроллера
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Таблица2 Технические характеристики аппаратных
средств связи
Характеристика Значение
Количество входов/
выходов
4 входа (E01-E04) и 4 выхода (A01-A04)
Время обновления
состояния входов/
выходов
Макс. 5 мс
Протяженность сети Макс. 100 м
Напряжение внешнего
источника питания
30,5 В постоянного тока (источник питания
AS-интерфейса)
Потребляемый ток от
внешнего источника
40 мА или менее
Соответствует Сертификации AS-интерфейса, CE
Таблица3 Технические характеристики программного
обеспечения связи
Характеристика Значение
Номер станции
Задается мастер-станцией (на заводе-
изготовителе по умолчанию установлен 0)
Код IO 7
Код ID F
Биты
данных
D0-D3 Ввод-вывод 01 - 04 (E01 - E04, A01 - A04)
RUS
*1 Функция сброса входного сигнала (E01 - E04) при прерывании связи AS-
интерфейса на 70 мс или более
3. МОНТАЖ ПРОВОДОВ И
УСТАНОВКА
См. схему соединений AS-интерфейса на рис. 1
Для подключения модуля AL-ASI-BD к сети используйте плоский желтый кабель AS-
интерфейса.
Перед установкой модуля AL-ASI-BD ознакомитесь с рис. 2.
Перед тем, как снимать крышку, отключите все контактные клеммы
от источника питания.
1) Отвинтите винт «А», обеспечьте его сохранность.
2) Осторожно снимите установленную на заводе крышку порта расширения.
3) Удалите секцию «В» с корпуса главного блока контроллера серии
α2.
4) Присоедините модуль AL-ASI-BD к главному модулю.
5) Затяните винт «А» с вращательным моментом 0,4 Нм
При подключении кабеля AS-интерфейса к модулю затяните винты разъема
соединения передачи данных с вращательным моментом 0,5 - 0,6 Нм.
Параметрич
-еские биты
P0
Монитор передачи информации (установлен
по умолчанию)
*1
P1,P2,P3 Не используется
Системные
биты
M6
«ON» (включен) — при возникновении
ошибки передачи данных AS-интерфейса
M7
«ON» (включен) — при возникновении
ошибки передачи данных в результате сбоя
в электропитании
Бит
управления
N1
ON: (включен) — соединение с сетью
AS-интерфейса
OFF: (выключен) — отключение от сети
AS-интерфейса
Таблица4. Назначение штырьков разъема модуля AL-ASI-
BD
Номер Наименование Применение
1 и 3ASI +
Для соединения с «+» кабелем AS-
интерфейса
2 и 4ASI -
Для соединения с «-» кабелем AS-
интерфейса
Таблица3 Технические характеристики программного
обеспечения связи
Характеристика Значение
4. УСТАНОВКА АДРЕСОВ
ПОДЧИНЕННЫХ УЗЛОВ И
ДИАГНОСТИКА
Адрес модуля AL-ASI-BD должен задаваться из модуля мастер-узла AS-интерфейса.
Диапазон адресов подчиненных узловот 1 до 31. В новых модулях на заводе-
изготовителе устанавливается адрес 0; если модулю ранее был присвоен адрес,
отличный от 0, он должен быть выставлен на 0 перед подключением к сети AS-
интерфейса.
Подробнее о том, как задавать адрес станции через мастер-узел AS-интерфейса,
см.
в руководстве по главному узлу AS-интерфейса.
Одновременно к сети можно подключать несколько модулей, при этом все, кроме
одного, должны быть переведены в пассивное состояние (необходимо установить
N1=1). После подачи питания на устройства сети, модули можно активировать по
отдельности (установить N1=0), при этом мастер- узел присвоит адреса
подчиненным узлам.
Проверки в случае возможных ошибок
1) При возникновении сбоя передачи данных (ошибка М6)
- Проверьте подключение к мастер-модулю AS-интерфейса, проверьте
правильность номера подчиненной станции.
2) При возникновении сбоя подачи питания (ошибка М7)
- Проверьте соединение кабеля шины AS-интерфейса с каждым блоком, на
котором замечена данная неисправность, а также подачу питания на AS-
интерфейс.
Manual number : JY992D81402
Manual revision : G
Date : 04/2015
JY992D81402G
Effective April 2015
Specifications are subject to
change with out notice.
JY992D81402G
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
AL-ASI-BD, AL2-ASI-BD
Maskinvaruhandbok
Руководство по аппаратной части
JY992D81402G
Yttre mått
Внешние размеры
AL-ASI-BD
SWE
RUS
ASI
-
26.5
53.5
90
ASI
+
ASI
-
ASI
+
24.5
53.1
90
ASI
-
ASI
+
ASI
-
ASI
+
mm
AL2-ASI-BD
Figure 1
Figure 2
ASI
-
1
2
ASI
+
4
3
ASI
-
ASI
+
AC 100-240V
POWER
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
1 2
3
4
5
6
7
8
9
10
11
12
IN
L
N
~
ASI
+
ASI
-
OK
ESC
~
ASI
-
ASI
+
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
LN
~
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
OK
ESC
ASI
+
ASI
-
ASI
+
ASI
-
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
A
B
A
Den här handboken innehåller text, scheman och förklaringar, som
vägleder till korrekt programmering och användning av AS-
gränssnittsmodulerna AL-ASI-BD och AL2-ASI-BD. Läs igenom och
förstå handboken innan du försöker installera eller använda enheten.
Ytterligare information finns i handböckerna för
α-maskinvara eller α2-
maskinvara samt programmeringshandböcker för
α och α2-serien.
Viktigt
AL-ASI-BD och AL2-ASI-BD får endast bytas av personer med
utbildning i och kännedom om gällande lokala och nationella elstan-
darder.
Stäng av strömförsörjningen för att installera eller avlägsna AL-ASI-
BD eller AL2-ASI-BD.
Sätt tillbaka kåpan efter att ha avlägsnat AL-ASI-BD eller AL2-ASI-
BD.
Mitsubishi Electric är under inga omständigheter ersättningsskyldigt
eller ansvarigt för följdskador som kan uppstå till följd av installation
eller användning av utrustningen.
1. INLEDNING
AL-ASI-BD och AL2-ASI-BD gränssnittskortmodul för ställdonssensor (Actuator Sensor
Interface-modul, nedan kallad AL-ASI-BD) används tillsammans med följande styrenhet i
serierna
α (α och α2) för datakommunikation via ett AS-gränssnittsnätverk (Actuator
Sensor-nätverk).
AL-ASI-BD ansluts till huvudenheten på en styrenhet i serien, så att den utgör en
slavstation i ett AS-gränssnittsnätverk (4 ingångar, 4 utgångar). Högst 31 slavenheter kan
anslutas för att bilda ett AS-gränssnittsnätverk. Strömförsörjning för kommunikation sker
via AS-gränssnittsbussen, via AS-gränssnittets strömförsörjningsenhet.
Kommunikationssignalen överlagras över strömförsörjningen på AS-gränssnittsbussen.
2. SPECIFIKATIONER
Allmänna data finns i maskinvaruhandböckerna för serierna α (α och α 2).
Tabell 1. Styrenheter som kan användas
Gränssnittets modellnamn Styrenhetens modellnamn
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Tabell 2. Maskinvarudata, kommunikation
Post Innehåll
Antal I/O 4 ingångar (in. E01 - E04) 4 utgångar (ut. A01 - A04)
I/O-uppdateringstid Max. 5ms
Nätverksavstånd Max. 100m
Extern
spänningsförsörjning
Typiskt 30,5 V DC (strömförsörjning för AS - gränssnitt)
Strömförbrukning,
extern
strömförbrukning
40 mA eller mindre
Uppfyller AS-gränssnittscertifiering, CE
Tabell 3. Especificaciones de la comunicación a nivel de
software
Concepto Innehåll
Stationsnummer Anges från masterstation (fabriksinställning 0)
I/O-kod 7
ID-kod F F
Databit D0-D3 ingång/utgång 01 - 04 (E01 - E04, A01 - A04)
Parameterbit
P0
Kommunikationsövervakning
(standardinställd).
*1
P1,P2,P3 Används inte
SWE
*1 Funktion för att återställa insignal (E01 - E04) när kommunikationen med
AS-gränssnittet bryts under 70 ms eller mer.
3. KABELANSLUTNING OCH
INSTALLATION
Kabelanslutning för AS-gränssnitt visas i figur 1.
Använd AS-gränssnittets flatkabel (gul) för att ansluta AL-ASI-BD till nätverket.
För installation av AL-ASI-BD, se figur 2.
Koppla bort samtliga anslutningar från strömförsörjningen innan
skyddet avlägsnas.
1) Avlägsna och spara skruv A.
2) Avlägsna försiktigt det fabriksmonterade expansionsplatsskyddet.
3) Skär bort sektion B av α-styrenhetens huvudenhet.
4) Sätt tillbaka AL-ASI-BD på huvudenheten.
5) Dra åt skruv "A" med 0,4 N·m.
När du ansluter AS-gränssnittskabeln till modulen, skall du dra åt
kommunikationsanslutningens skruvar med 0,5 - 0,6 N·m.
4. SLAVADRESSINSTÄLLNING
OCH DIAGNOSTIK
Adressen till AL-ASI-BD måste ställas in från mastermodulen för AS-gränssnitt.
Inställningsområdet för slavadress är 1 till 31. Nya moduler är förinställda till 0 vid
leverans. Om en modul tidigare tilldelats någon annan adress än 0, måste den
återställas till 0 innan den kan läggas till i ett nytt AS-gränssnittsnätverk.
I handboken för mastermodulen för AS-gränssnitt finns mer information om hur du
ställer in stationsadress från AS-gränssnittsmastern.
Många moduler kan läggas till samtidigt till nätverket. Alla utom en av dem skall vara
satt till passivt läge (sätt N1 = 1). När nätverket spänningssatts kan modulerna
aktiveras var för sig (sätt N1 = 0), där masterstationen tilldelar en slavadress.
Tillämpliga felkontroller:
1) Om ett kommunikationsfel (M6) uppkommer:
- Kontrollera anslutningarna till AS-gränssnittsmastern, samt att
slavstationsnumret är korrekt.
2) Om strömförsörjningsfel för kommunikation (M7) uppkommer:
Kontrollera AS-gränssnittsbusskabelns anslutning vid berörda enheter.
Kontrollera även strömförsörjningen till och funktionen hos AS-gränsnittet.
Systembit
M6
PÅ när kommunikationsfel för AS-gränssnitt
uppkommer.
M7
PÅ när kommunikationsfel för AS-gränssnittets
strömförsörjning uppkommer.
Kontrollbit N1
ON: Koppla bort från AS-gränssnittsnätverk.
OFF: Anslut till AS-gränssnittsnätverk.
Tabla 4. AL-ASI-BD stifttilldelning
Beteckning Namn Användning
1 & 3 ASI + För AS-gränssnitt, + kabelanslutning
2 &4 ASI - För AS-gränssnitt, - kabelanslutning
Tabell 3. Especificaciones de la comunicación a nivel de
software
Concepto Innehåll
В данном руководстве содержатся описания, схемы и
пояснения, которые помогут пользователю надлежащим
образом установить модули AS-интерфейса AL-ASI-BD и AL2-
ASI-BD и обеспечить их нормальное функционирование.
Данное руководство следует прочесть и усвоить, прежде чем
приступать к каким- либо работам по установке или
эксплуатации данного устройства. Дальнейшую информацию
вы найдете в Руководстве по аппаратной части контроллера
серии α 2 или α и в Рук
оводстве по программированию
контроллера серии α2 или α
Внимание
К работам по замене модулей AL-ASI-BD и AL2-ASI-BD
допускаются только квалифицированные электрики,
прошедшие подготовку к электромонтажным работам в
соответствии с местными и государственными
стандартами.
Выключите электропитание, прежде чем устанавливать
или вынимать модули AL-ASI-BD или AL2-ASI-BD.
После отсоединения модуля AL-ASI-BD или AL2-ASI-BD
установите на место крышку.
Mitsubishi Electric ни при каких обстоятельствах не несет
юридической ответственности за какие-ли
бо п
овреждения,
которые могут оказаться следствием установки или
эксплуатации данного устройства.
1. ВВЕДЕНИЕ
Модули AS-интерфейса (интерфейса датчиков и исполнительных устройств)
AL-ASI-BD и AL2-ASI-BD (далее называемые «модули AL-ASI-BD»)
предназначены для использования с контроллерами серии α (α и α 2) для
передачи данных по сети AS-интерфейса.
Модуль AL-ASI-BD подключается к главному блоку контроллера серии α2 и
создает подчиненную станцию сети AS-интерфейса (4 точки входа, 4 точки
выхода). Максимальное количество подчиненных узлов, которое можно
подключить к сети AS-и
нтерфейса – 31. Электропитание для связи подается по
шине AS-интерфейса от источника питания AS-интерфейса. Сигнал связи
накладывается на напряжение питания.
2. ТЕХНИЧЕСКИЕ
ХАРАКТЕРИСТИКИ
Общие технические характеристики см. в Руководстве по аппаратной части
контроллера серии α2 или α.
Таблица1 Тип контроллера для интерфейса
Модель интерфейса Модель контроллера
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Таблица2 Технические характеристики аппаратных
средств связи
Характеристика Значение
Количество входов/
выходов
4 входа (E01-E04) и 4 выхода (A01-A04)
Время обновления
состояния входов/
выходов
Макс. 5 мс
Протяженность сети Макс. 100 м
Напряжение внешнего
источника питания
30,5 В постоянного тока (источник питания
AS-интерфейса)
Потребляемый ток от
внешнего источника
40 мА или менее
Соответствует Сертификации AS-интерфейса, CE
Таблица3 Технические характеристики программного
обеспечения связи
Характеристика Значение
Номер станции
Задается мастер-станцией (на заводе-
изготовителе по умолчанию установлен 0)
Код IO 7
Код ID F
Биты
данных
D0-D3 Ввод-вывод 01 - 04 (E01 - E04, A01 - A04)
RUS
*1 Функция сброса входного сигнала (E01 - E04) при прерывании связи AS-
интерфейса на 70 мс или более
3. МОНТАЖ ПРОВОДОВ И
УСТАНОВКА
См. схему соединений AS-интерфейса на рис. 1
Для подключения модуля AL-ASI-BD к сети используйте плоский желтый кабель AS-
интерфейса.
Перед установкой модуля AL-ASI-BD ознакомитесь с рис. 2.
Перед тем, как снимать крышку, отключите все контактные клеммы
от источника питания.
1) Отвинтите винт «А», обеспечьте его сохранность.
2) Осторожно снимите установленную на заводе крышку порта расширения.
3) Удалите секцию «В» с корпуса главного блока контроллера серии
α2.
4) Присоедините модуль AL-ASI-BD к главному модулю.
5) Затяните винт «А» с вращательным моментом 0,4 Нм
При подключении кабеля AS-интерфейса к модулю затяните винты разъема
соединения передачи данных с вращательным моментом 0,5 - 0,6 Нм.
Параметрич
-еские биты
P0
Монитор передачи информации (установлен
по умолчанию)
*1
P1,P2,P3 Не используется
Системные
биты
M6
«ON» (включен) — при возникновении
ошибки передачи данных AS-интерфейса
M7
«ON» (включен) — при возникновении
ошибки передачи данных в результате сбоя
в электропитании
Бит
управления
N1
ON: (включен) — соединение с сетью
AS-интерфейса
OFF: (выключен) — отключение от сети
AS-интерфейса
Таблица4. Назначение штырьков разъема модуля AL-ASI-
BD
Номер Наименование Применение
1 и 3ASI +
Для соединения с «+» кабелем AS-
интерфейса
2 и 4ASI -
Для соединения с «-» кабелем AS-
интерфейса
Таблица3 Технические характеристики программного
обеспечения связи
Характеристика Значение
4. УСТАНОВКА АДРЕСОВ
ПОДЧИНЕННЫХ УЗЛОВ И
ДИАГНОСТИКА
Адрес модуля AL-ASI-BD должен задаваться из модуля мастер-узла AS-интерфейса.
Диапазон адресов подчиненных узловот 1 до 31. В новых модулях на заводе-
изготовителе устанавливается адрес 0; если модулю ранее был присвоен адрес,
отличный от 0, он должен быть выставлен на 0 перед подключением к сети AS-
интерфейса.
Подробнее о том, как задавать адрес станции через мастер-узел AS-интерфейса,
см.
в руководстве по главному узлу AS-интерфейса.
Одновременно к сети можно подключать несколько модулей, при этом все, кроме
одного, должны быть переведены в пассивное состояние (необходимо установить
N1=1). После подачи питания на устройства сети, модули можно активировать по
отдельности (установить N1=0), при этом мастер- узел присвоит адреса
подчиненным узлам.
Проверки в случае возможных ошибок
1) При возникновении сбоя передачи данных (ошибка М6)
- Проверьте подключение к мастер-модулю AS-интерфейса, проверьте
правильность номера подчиненной станции.
2) При возникновении сбоя подачи питания (ошибка М7)
- Проверьте соединение кабеля шины AS-интерфейса с каждым блоком, на
котором замечена данная неисправность, а также подачу питания на AS-
интерфейс.
Manual number : JY992D81402
Manual revision : G
Date : 04/2015
JY992D81402G
Effective April 2015
Specifications are subject to
change with out notice.
JY992D81402G
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
AL-ASI-BD, AL2-ASI-BD
Maskinvaruhandbok
Руководство по аппаратной части
JY992D81402G
Yttre mått
Внешние размеры
AL-ASI-BD
SWE
RUS
ASI
-
26.5
53.5
90
ASI
+
ASI
-
ASI
+
24.5
53.1
90
ASI
-
ASI
+
ASI
-
ASI
+
mm
AL2-ASI-BD
Figure 1
Figure 2
ASI
-
1
2
ASI
+
4
3
ASI
-
ASI
+
AC 100-240V
POWER
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
1 2
3
4
5
6
7
8
9
10
11
12
IN
L
N
~
ASI
+
ASI
-
OK
ESC
~
ASI
-
ASI
+
AC INPUT
AL-20MR-A
OK
ESC
RELAY OUTPUT
LN
~
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
OK
ESC
ASI
+
ASI
-
ASI
+
ASI
-
AC INPUT
AL-20MR-A
RELAY OUTPUT
LN
AC 100-240V
POWER
1 2
3
4
5
6
7
8
9
10
11
12
IN
OUT
1
OUT
2
OUT
5
OUT
3
OUT
4
OUT
6
OUT
8
OUT
7
A
B
A
Den här handboken innehåller text, scheman och förklaringar, som
vägleder till korrekt programmering och användning av AS-
gränssnittsmodulerna AL-ASI-BD och AL2-ASI-BD. Läs igenom och
förstå handboken innan du försöker installera eller använda enheten.
Ytterligare information finns i handböckerna för
α-maskinvara eller α2-
maskinvara samt programmeringshandböcker för
α och α2-serien.
Viktigt
AL-ASI-BD och AL2-ASI-BD får endast bytas av personer med
utbildning i och kännedom om gällande lokala och nationella elstan-
darder.
Stäng av strömförsörjningen för att installera eller avlägsna AL-ASI-
BD eller AL2-ASI-BD.
Sätt tillbaka kåpan efter att ha avlägsnat AL-ASI-BD eller AL2-ASI-
BD.
Mitsubishi Electric är under inga omständigheter ersättningsskyldigt
eller ansvarigt för följdskador som kan uppstå till följd av installation
eller användning av utrustningen.
1. INLEDNING
AL-ASI-BD och AL2-ASI-BD gränssnittskortmodul för ställdonssensor (Actuator Sensor
Interface-modul, nedan kallad AL-ASI-BD) används tillsammans med följande styrenhet i
serierna
α (α och α2) för datakommunikation via ett AS-gränssnittsnätverk (Actuator
Sensor-nätverk).
AL-ASI-BD ansluts till huvudenheten på en styrenhet i serien, så att den utgör en
slavstation i ett AS-gränssnittsnätverk (4 ingångar, 4 utgångar). Högst 31 slavenheter kan
anslutas för att bilda ett AS-gränssnittsnätverk. Strömförsörjning för kommunikation sker
via AS-gränssnittsbussen, via AS-gränssnittets strömförsörjningsenhet.
Kommunikationssignalen överlagras över strömförsörjningen på AS-gränssnittsbussen.
2. SPECIFIKATIONER
Allmänna data finns i maskinvaruhandböckerna för serierna α (α och α 2).
Tabell 1. Styrenheter som kan användas
Gränssnittets modellnamn Styrenhetens modellnamn
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Tabell 2. Maskinvarudata, kommunikation
Post Innehåll
Antal I/O 4 ingångar (in. E01 - E04) 4 utgångar (ut. A01 - A04)
I/O-uppdateringstid Max. 5ms
Nätverksavstånd Max. 100m
Extern
spänningsförsörjning
Typiskt 30,5 V DC (strömförsörjning för AS - gränssnitt)
Strömförbrukning,
extern
strömförbrukning
40 mA eller mindre
Uppfyller AS-gränssnittscertifiering, CE
Tabell 3. Especificaciones de la comunicación a nivel de
software
Concepto Innehåll
Stationsnummer Anges från masterstation (fabriksinställning 0)
I/O-kod 7
ID-kod F F
Databit D0-D3 ingång/utgång 01 - 04 (E01 - E04, A01 - A04)
Parameterbit
P0
Kommunikationsövervakning
(standardinställd).
*1
P1,P2,P3 Används inte
SWE
*1 Funktion för att återställa insignal (E01 - E04) när kommunikationen med
AS-gränssnittet bryts under 70 ms eller mer.
3. KABELANSLUTNING OCH
INSTALLATION
Kabelanslutning för AS-gränssnitt visas i figur 1.
Använd AS-gränssnittets flatkabel (gul) för att ansluta AL-ASI-BD till nätverket.
För installation av AL-ASI-BD, se figur 2.
Koppla bort samtliga anslutningar från strömförsörjningen innan
skyddet avlägsnas.
1) Avlägsna och spara skruv A.
2) Avlägsna försiktigt det fabriksmonterade expansionsplatsskyddet.
3) Skär bort sektion B av α-styrenhetens huvudenhet.
4) Sätt tillbaka AL-ASI-BD på huvudenheten.
5) Dra åt skruv "A" med 0,4 N·m.
När du ansluter AS-gränssnittskabeln till modulen, skall du dra åt
kommunikationsanslutningens skruvar med 0,5 - 0,6 N·m.
4. SLAVADRESSINSTÄLLNING
OCH DIAGNOSTIK
Adressen till AL-ASI-BD måste ställas in från mastermodulen för AS-gränssnitt.
Inställningsområdet för slavadress är 1 till 31. Nya moduler är förinställda till 0 vid
leverans. Om en modul tidigare tilldelats någon annan adress än 0, måste den
återställas till 0 innan den kan läggas till i ett nytt AS-gränssnittsnätverk.
I handboken för mastermodulen för AS-gränssnitt finns mer information om hur du
ställer in stationsadress från AS-gränssnittsmastern.
Många moduler kan läggas till samtidigt till nätverket. Alla utom en av dem skall vara
satt till passivt läge (sätt N1 = 1). När nätverket spänningssatts kan modulerna
aktiveras var för sig (sätt N1 = 0), där masterstationen tilldelar en slavadress.
Tillämpliga felkontroller:
1) Om ett kommunikationsfel (M6) uppkommer:
- Kontrollera anslutningarna till AS-gränssnittsmastern, samt att
slavstationsnumret är korrekt.
2) Om strömförsörjningsfel för kommunikation (M7) uppkommer:
Kontrollera AS-gränssnittsbusskabelns anslutning vid berörda enheter.
Kontrollera även strömförsörjningen till och funktionen hos AS-gränsnittet.
Systembit
M6
PÅ när kommunikationsfel för AS-gränssnitt
uppkommer.
M7
PÅ när kommunikationsfel för AS-gränssnittets
strömförsörjning uppkommer.
Kontrollbit N1
ON: Koppla bort från AS-gränssnittsnätverk.
OFF: Anslut till AS-gränssnittsnätverk.
Tabla 4. AL-ASI-BD stifttilldelning
Beteckning Namn Användning
1 & 3 ASI + För AS-gränssnitt, + kabelanslutning
2 &4 ASI - För AS-gränssnitt, - kabelanslutning
Tabell 3. Especificaciones de la comunicación a nivel de
software
Concepto Innehåll
В данном руководстве содержатся описания, схемы и
пояснения, которые помогут пользователю надлежащим
образом установить модули AS-интерфейса AL-ASI-BD и AL2-
ASI-BD и обеспечить их нормальное функционирование.
Данное руководство следует прочесть и усвоить, прежде чем
приступать к каким- либо работам по установке или
эксплуатации данного устройства. Дальнейшую информацию
вы найдете в Руководстве по аппаратной части контроллера
серии α 2 или α и в Рук
оводстве по программированию
контроллера серии α2 или α
Внимание
К работам по замене модулей AL-ASI-BD и AL2-ASI-BD
допускаются только квалифицированные электрики,
прошедшие подготовку к электромонтажным работам в
соответствии с местными и государственными
стандартами.
Выключите электропитание, прежде чем устанавливать
или вынимать модули AL-ASI-BD или AL2-ASI-BD.
После отсоединения модуля AL-ASI-BD или AL2-ASI-BD
установите на место крышку.
Mitsubishi Electric ни при каких обстоятельствах не несет
юридической ответственности за какие-ли
бо п
овреждения,
которые могут оказаться следствием установки или
эксплуатации данного устройства.
1. ВВЕДЕНИЕ
Модули AS-интерфейса (интерфейса датчиков и исполнительных устройств)
AL-ASI-BD и AL2-ASI-BD (далее называемые «модули AL-ASI-BD»)
предназначены для использования с контроллерами серии α (α и α 2) для
передачи данных по сети AS-интерфейса.
Модуль AL-ASI-BD подключается к главному блоку контроллера серии α2 и
создает подчиненную станцию сети AS-интерфейса (4 точки входа, 4 точки
выхода). Максимальное количество подчиненных узлов, которое можно
подключить к сети AS-и
нтерфейса – 31. Электропитание для связи подается по
шине AS-интерфейса от источника питания AS-интерфейса. Сигнал связи
накладывается на напряжение питания.
2. ТЕХНИЧЕСКИЕ
ХАРАКТЕРИСТИКИ
Общие технические характеристики см. в Руководстве по аппаратной части
контроллера серии α2 или α.
Таблица1 Тип контроллера для интерфейса
Модель интерфейса Модель контроллера
AL-ASI-BD AL-20MR-A, AL-20MR-D, AL-20MT-D
AL2-ASI-BD AL2-14MR-*, AL2-24MR-*
Таблица2 Технические характеристики аппаратных
средств связи
Характеристика Значение
Количество входов/
выходов
4 входа (E01-E04) и 4 выхода (A01-A04)
Время обновления
состояния входов/
выходов
Макс. 5 мс
Протяженность сети Макс. 100 м
Напряжение внешнего
источника питания
30,5 В постоянного тока (источник питания
AS-интерфейса)
Потребляемый ток от
внешнего источника
40 мА или менее
Соответствует Сертификации AS-интерфейса, CE
Таблица3 Технические характеристики программного
обеспечения связи
Характеристика Значение
Номер станции
Задается мастер-станцией (на заводе-
изготовителе по умолчанию установлен 0)
Код IO 7
Код ID F
Биты
данных
D0-D3 Ввод-вывод 01 - 04 (E01 - E04, A01 - A04)
RUS
*1 Функция сброса входного сигнала (E01 - E04) при прерывании связи AS-
интерфейса на 70 мс или более
3. МОНТАЖ ПРОВОДОВ И
УСТАНОВКА
См. схему соединений AS-интерфейса на рис. 1
Для подключения модуля AL-ASI-BD к сети используйте плоский желтый кабель AS-
интерфейса.
Перед установкой модуля AL-ASI-BD ознакомитесь с рис. 2.
Перед тем, как снимать крышку, отключите все контактные клеммы
от источника питания.
1) Отвинтите винт «А», обеспечьте его сохранность.
2) Осторожно снимите установленную на заводе крышку порта расширения.
3) Удалите секцию «В» с корпуса главного блока контроллера серии
α2.
4) Присоедините модуль AL-ASI-BD к главному модулю.
5) Затяните винт «А» с вращательным моментом 0,4 Нм
При подключении кабеля AS-интерфейса к модулю затяните винты разъема
соединения передачи данных с вращательным моментом 0,5 - 0,6 Нм.
Параметрич
-еские биты
P0
Монитор передачи информации (установлен
по умолчанию)
*1
P1,P2,P3 Не используется
Системные
биты
M6
«ON» (включен) — при возникновении
ошибки передачи данных AS-интерфейса
M7
«ON» (включен) — при возникновении
ошибки передачи данных в результате сбоя
в электропитании
Бит
управления
N1
ON: (включен) — соединение с сетью
AS-интерфейса
OFF: (выключен) — отключение от сети
AS-интерфейса
Таблица4. Назначение штырьков разъема модуля AL-ASI-
BD
Номер Наименование Применение
1 и 3ASI +
Для соединения с «+» кабелем AS-
интерфейса
2 и 4ASI -
Для соединения с «-» кабелем AS-
интерфейса
Таблица3 Технические характеристики программного
обеспечения связи
Характеристика Значение
4. УСТАНОВКА АДРЕСОВ
ПОДЧИНЕННЫХ УЗЛОВ И
ДИАГНОСТИКА
Адрес модуля AL-ASI-BD должен задаваться из модуля мастер-узла AS-интерфейса.
Диапазон адресов подчиненных узловот 1 до 31. В новых модулях на заводе-
изготовителе устанавливается адрес 0; если модулю ранее был присвоен адрес,
отличный от 0, он должен быть выставлен на 0 перед подключением к сети AS-
интерфейса.
Подробнее о том, как задавать адрес станции через мастер-узел AS-интерфейса,
см.
в руководстве по главному узлу AS-интерфейса.
Одновременно к сети можно подключать несколько модулей, при этом все, кроме
одного, должны быть переведены в пассивное состояние (необходимо установить
N1=1). После подачи питания на устройства сети, модули можно активировать по
отдельности (установить N1=0), при этом мастер- узел присвоит адреса
подчиненным узлам.
Проверки в случае возможных ошибок
1) При возникновении сбоя передачи данных (ошибка М6)
- Проверьте подключение к мастер-модулю AS-интерфейса, проверьте
правильность номера подчиненной станции.
2) При возникновении сбоя подачи питания (ошибка М7)
- Проверьте соединение кабеля шины AS-интерфейса с каждым блоком, на
котором замечена данная неисправность, а также подачу питания на AS-
интерфейс.
Manual number : JY992D81402
Manual revision : G
Date : 04/2015
JY992D81402G
Effective April 2015
Specifications are subject to
change with out notice.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9

Mitsubishi Electric AL-ASI-BD/AL2-ASI-BD Инструкция по применению

Тип
Инструкция по применению

Задайте вопрос, и я найду ответ в документе

Поиск информации в документе стал проще с помощью ИИ