Tripp Lite PowerVerter APSX3024SW, Sine Wave Inverters Инструкция по применению

  • Привет! Я прочитал руководство пользователя по инверторам/зарядным устройствам Tripp Lite APSX 3024SW и APSX 6048VRNET. Я знаю, как настроить их параметры, подключить к батарее и сети, а также устранить типичные неполадки. Задавайте ваши вопросы – я готов помочь!
  • Как выбрать подходящий тип и емкость батареи?
    Что делать, если индикаторы батареи мигают?
    Как настроить параметры работы инвертора/зарядного устройства?
    Как подключить инвертор/зарядное устройство к батарее и сети?
1
Owner’s Manual
APSX Pure Sine Wave
DC-to-AC Inverter/Chargers
Models: APSX3024SW, APSX6048VRNET
Introduction 2
Important Safety Instructions 2
Feature Identification 3
Operation 4
Configuration 5
Battery Selection 8
Battery Connection 9
AC Input/Output Connection 10
AC Generator Input 10
Service/Maintenance 11
Troubleshooting 11
Warranty 12
Español 13
Français 25
 37
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2019 Tripp Lite. All rights reserved. Isobar
®
is a registered trademark of Tripp Lite.
2
Important Safety Instructions
Introduction
SAVE THESE INSTRUCTIONS!
This manual contains important instructions and warnings that should be followed during the installation, operation and storage of all
Tripp Lite Inverter/Chargers.
Location Warnings
Install your Inverter/Charger in a location or compartment that minimizes exposure to heat, dust, direct sunlight and moisture.
Although your Inverter/Charger is moisture resistant, it is NOT waterproof. Flooding the unit with water will cause it to short circuit and
could cause personal injury due to electric shock. Never immerse the unit, and avoid any area where standing water might accumulate.
Mounting should be in the driest location available.
Leave a minimum of 50 mm clearance at front and back of the Inverter/Charger for proper ventilation. The heavier the load of connected
equipment, the more heat will be generated by the unit.
Do not install the Inverter/Charger directly near magnetic storage media, as this may result in data corruption.
Do not install near flammable materials, fuel or chemicals.
Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the
unit’s internal cooling, eventually causing product damage not covered under warranty.
Mount your Inverter/Charger BEFORE DC battery and AC power connection. Failure to follow these instructions may lead to personal injury
and/or damage to the Inverter/Charger and connected systems.
Battery Connection Warnings
The battery should be connected before operating the Inverter/Charger.
Multiple battery systems must be comprised of batteries of identical voltage, age, amp-hour capacity and type.
Because explosive hydrogen gas can accumulate near batteries if they are not kept well ventilated, your batteries should not be installed
in a “dead air” compartment. Ideally, any compartment would have some ventilation to outside air.
Sparks may result during final battery connection. Always observe proper polarity as batteries are connected.
Do not allow objects to contact the two DC input terminals. Do not short or bridge these terminals together. Serious personal injury or
property damage could result.
Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of
the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Connect your Inverter/Charger only to a properly grounded AC power source. Do not connect the unit to itself; this will damage the device
and void your warranty.
The main grounding lug should be connected to earth ground with a minimum 3.15 mm diameter 8 AWG wire.
Operation Warnings
Your Inverter/Charger does not require routine maintenance. Do not open the device for any reason. There are no user serviceable parts
inside.
Potentially lethal voltages exist within the Inverter/Charger as long as the battery supply and/or AC input are connected. During any
service work, the battery supply and AC input connection should therefore be disconnected.
Do not connect or disconnect batteries while the Inverter/Charger is operating in either inverting or charging mode. Operating Mode
Switch should be in the OFF position. Dangerous arcing may result.
Congratulations! You’ve purchased the most advanced, feature-rich Inverter/Charger designed as an alternative energy source during
utility power failures. Tripp Lite APS Inverter/Chargers keep your equipment constantly up and productive through all utility power problems
(blackouts, brownouts and high voltages) by automatically inverting DC power from user-supplied batteries into AC power. Built-in Isobar®
surge suppression provides an additional level of equipment protection. When utility power is present, APS Inverter/Chargers automatically
pass through power to your equipment while simultaneously recharging your connected battery bank. APS Inverter/Chargers are the quiet
alternative to gas generators during emergency backup applications—with no fumes, fuel or noise to deal with! You get AC electricity
anywhere and anytime you need it.
3
Feature Identification
1
Configuration DIP Switches: Optimize Inverter/Charger
operation depending on your application. See Configuration
section for setting instructions.
2
Operating Mode Rocker Switch: Controls Inverter/Charger
operation. The “AUTO/REMOTE” setting ensures your equipment
receives constant, uninterrupted AC power. It also enables the
Inverter/Charger to be remotely monitored and controlled with
an optional remote module (Tripp Lite model APSRM4, sold
separately). The “CHARGE ONLY” setting allows your batteries
to return to full charge faster by turning the inverter off, which
halts battery discharging. The “OFF” position de-energizes the
unit (including its AC output). See Operation section for setting
instructions.
3
Operation Indicator Lights: Intuitive “traffic light” signals
show whether the Inverter/Charger is operating from AC line
power or DC battery power. It also warns you if the connected
equipment load is too high. See Operation section for
instructions on reading indicator lights.
4
Battery Indicator Lights: Intuitive “traffic light” signals show
approximate charge level of your battery. See Operation
section for instructions on reading indicator lights.
5
DC Power Terminals: Connect to your battery terminals. See
Battery Connection section for connection instructions.
6
Hardwire AC Input/Output Terminal Strip (Access Panel):
Securely connects the Inverter/Charger to facility electrical
system. See Input/Output Connection section for connection
instructions.
7
Knockouts for AC Input/Output Conduits
8
Remote Control Module Connector: Allows remote
monitoring and control with an optional module (Tripp Lite
model APSRM4, sold separately). See remote module
owner’s manual for connection instructions.
9
Battery Charge Conserver (Load Sense) Control:
Conserves battery power by setting the low-load level at which
the Inverter/Charger’s inverter automatically shuts off. See
Configuration section for setting instructions.
10
Main Ground Lug: Properly grounds the Inverter/Charger to
earth ground. See Battery Connection section for connection
instructions.
11
Thermostatically Controlled Cooling Fans: Quiet, efficient
fans regulate internal temperature and prolong equipment
service life. Fans run at variable speed, depending on
temperature and load.
12
Remote Generator Start Connector: Automatically cycles
generator based on battery voltage. Use with user-supplied
cable. See Configuration section for more information.
13
Remote Battery Temperature Sensing Connector: Prolongs
battery life by adjusting charge based on battery temperature.
Contact Tripp Lite for optional temperature sensing cable
accessory. See Configuration section for more information.
14
RS-232 Serial Communication Connector
(APSX6048VRNET only): Can be used to attach an
external SNMP/Web management module (Tripp Lite model
SNMPWEBSOLOHV) to remotely monitor your inverter/charger.
15
12V DC Power Connector (APSX6048VRNET only):
Independently powers SNMP/Web management module
(Tripp Lite model SNMPWEBSOLOHV) without the use of an
AC outlet.
11213
6
7 11
14
2
5
9
10
4 8 3
On Side,
Not Shown.
15
4
Operation
Switch Modes
After configuring, mounting and connecting your Inverter/Charger,
you are able to operate it by switching between the following
operating modes as appropriate to your situation:
AUTO/REMOTE: Switch to this mode when you need
constant, uninterrupted AC power for connected
appliances and equipment. The Inverter/Charger will
continue to supply AC power to connected equipment
and to charge your connected batteries while utility-
or generator-supplied AC power is present. Since the
inverter is ON (but in Standby) in this mode, it will automatically
switch to your battery system to supply AC power to connected
equipment in the absence of a utility/generator source or in over/
under voltage situations. “AUTO/REMOTE” also enables an optional
remote control module (Tripp Lite model APSRM4, sold separately)
to function when connected to the unit.
CHARGE ONLY: Switch to this mode when you are not
using connected appliances and equipment in order
to conserve battery power by disabling the inverter.
The Inverter/Charger will continue to pass through AC
power to connected equipment and charge connected
batteries while utility- or generator-supplied AC power
is present. However, since the inverter is OFF in this mode, it WILL
NOT supply AC power to connected equipment in the absence of a
utility/generator source or in over/under voltage situations.
OFF: Switch to this mode to shut down the Inverter/
Charger completely, preventing the inverter from
drawing power from the batteries, and preventing utility
AC from passing through to connected equipment or
charging the batteries. Use this switch to automatically
reset the unit if it shuts down due to overload or
overheating. First remove the excessive load or allow the unit to
sufficiently cool (applicable to your situation). Switch to “OFF”, then
back to “AUTO/REMOTE” or “CHARGE ONLY” as desired. If unit fails
to reset, remove more load or allow unit to cool further and retry.
Note: The optional remote control module (APSRM4) will only reset
overloads.
Indicator Lights
Your Inverter/Charger (as well as an optional Tripp Lite Remote
Control Module, sold separately) is equipped with a simple, intuitive,
user-friendly set of indicator lights. These easily remembered “traffic
light” signals will allow you, shortly after first use, to tell at a glance
the charge condition of your batteries, as well as ascertain operating
details and fault conditions.
LINE Green Indicator: If the operating mode
switch is set to “AUTO/REMOTE,” this light will
ILLUMINATE CONTINUOUSLY when your connected
equipment is receiving continuous AC power
supplied from a utility/generator source.
If the operating mode switch is set to “CHARGE ONLY,” this light will
FLASH to alert you that the unit’s inverter is OFF and will NOT supply
AC power in the absence of a utility/generator source or in over/
under voltage situations.
INV (Inverting) Yellow Indicator: This light will
ILLUMINATE CONTINUOUSLY whenever connected
equipment is receiving battery-supplied, inverted AC
power (in the absence of a utility/generator source
or in over/under voltage situations). This light will be
off when AC power is supplying the load. This light
will FLASH to alert you if the load is less than the Battery Charge
Conserver (Load Sense) setting.
LOAD Red Indicator: This red light will ILLUMINATE
CONTINUOUSLY whenever the inverter is functioning
and the power demanded by connected appliances
and equipment exceeds 100% of load capacity. The
light will FLASH to alert you when the inverter shuts
down due to a severe overload or overheating. If
this happens, turn the operating mode switch “OFF”; remove the
overload and let the unit cool. You may then turn the operating
mode switch to either “AUTO/REMOTE” or “CHARGE ONLY” after
it has adequately cooled. This light will be off when AC power is
supplying the load.
BATTERY Indicator Lights: These three lights will illuminate in
several sequences to show the approximate charge level of your
connected battery bank and alert you to two fault conditions:
Approximate Battery Charge Level*
Indicator Illuminated Battery Capacity
(Charging/Discharging)
1
Green 91%–Full
2
Green & Yellow 81%–90%
3
Yellow 61%–80%
4
Yellow & Red 41%–60%
5
Red 21%–40%
6
All three lights off 1%–20%
7
Flashing red 0% (Inverter shutdown)
* Charge levels listed are approximate. Actual
conditions vary depending on battery condition
and load.
Fault Condition
Indicator Illuminated Fault Condition
1
All three lights Excessive discharge
flash slowly* (Inverter shutdown)
2
All three lights Overcharge (Charger
flash quickly** shutdown)
*Approximately ½ second on, ½ second off. See Troubleshooting section.
** Approximately ¼ second on, ¼ second off. May also indicate a battery
charger fault exists. See Troubleshooting section.
Resetting Your Inverter/Charger
to Restore AC Power
Your Inverter/Charger may cease supplying AC power or DC charging
power in order to protect itself from overload or to protect your
electrical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to “OFF” and
remove some of the connected electrical load (ie: turn off some of
the AC devices drawing power which may have caused the overload
of the unit). Wait one minute, then switch operating mode switch
back to either “AUTO/REMOTE” or “CHARGE ONLY.”
6
3
5
2
4
7
1
21
5
Configuration
Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located
on the front panel of your unit, see diagram) to optimize Inverter/
Charger operation depending on your application. Warning: Make
sure the unit is turned OFF before changing DIP Switch
settings.
1
Not Used
2
Select Line Connect Relay Transfer Time - OPTIONAL
Transfer Time Switch Position
1/2 Cycle Transfer Time Up
1 Cycle Transfer Time Down (factory setting)
3
Select Frequency - REQUIRED
Frequency Switch Position
60 Hz Up
50 Hz Down (factory setting)
4
Select Line Voltage - REQUIRED
(APSX6048VRNET model only)
Voltage
Switch Position
208 VAC Up
230 VAC Down (factory setting)
5
Select Battery Charger Amp Setting
CAUTION: When switching to the High Charge Amp setting,
the user must ensure that the amp-hour capacity of
their battery system exceeds the amperage of the High
Charge Amp setting or the batteries may be damaged or
degraded.
6
Select Equalize Battery Charge - OPTIONAL
Switch this DIP switch to the down position for 3 seconds
to begin the process of equalizing the charge state of your
battery’s cells by time-limited overcharge of all cells. This
can extend the useful life of certain types of batteries;
consult with your battery’s manufacturer to determine if
your batteries could benefit from this process. The charge
equalization process is automatic; once started, it can
only be stopped by removing the input power.
Note: The Inverter/Charger’s default transfer time setting is
1 cycle, which provides optimal protection for standard loads
in areas with frequent outages. If you will use the Inverter/
Charger to support computers or other sensitive electronic
equipment loads, set the transfer time to ½ cycle (switch
#2 UP) to ensure uninterrupted operation when the Inverter/
Charger transfers to battery power.
Battery Charger Switch Position
Low Charge Amps (23A) Up (factory setting)
High Charge Amps (90A) Down
Setting Procedure
Move to “Equalize” (DOWN) postition for 3
seconds.
Move to “Reset” (UP) postition and leave
it there. This is the factory default setting.
CAUTION: Do not leave DIP switch #6 in
the down position after beginning process.
Battery charge equalization should only
be performed in strict accordance with the
battery manufacturer’s instructions and
specifications.
Battery Charge Switch Position
Reset Up (factory setting)
Equalize Down (3 seconds)
7
8
Select AC Input Current Sharing—OPTIONAL
(APSX3024SW model only; APSX6048VRNET model operates in “Most Limiting” mode only)
Your Inverter/Charger features a high-output battery charger that can draw a significant amount of AC power from your utility source or
generator when charging at its maximum rate. If your unit is supplying its full AC power rating to its connected heavy electrical loads at the
same time as this high charging occurs, the AC input circuit breaker could trip, resulting in the complete shut off of pass-through utility power.
6
Configuration
230V Operation (APSX3024SW)
9
10
Select Low VAC Input Voltage Point for Switching
to Battery - OPTIONAL*
Voltage 9, 10 Switch Position
180 VAC Up, Up
170 VAC Up, Down
160 VAC Down, Up
150 VAC Down, Down (factory setting)
11
Select High AC Input Voltage Point for Switching to
Battery - OPTIONAL*
Voltage Switch Position
270 VAC Up
260 VAC Down (factory setting)
208V Operation (APSX6048VRNET model with Switch #4 in “Up” position)
9
10
Select Low VAC Input Voltage Point for Switching
to Battery - OPTIONAL*
Voltage 9, 10 Switch Position
175 VAC Up, Up
165 VAC Up, Down
175 VAC Down, Up
165 VAC Down, Down (factory setting)
11
Select High AC Input Voltage Point for Switching to
Battery - OPTIONAL*
Voltage Switch Position
245 VAC Up
235 VAC Down (factory setting)
230V Operation (APSX6048VRNET model with Switch #4 in “Down” position)
9
10
Select Low VAC Input Voltage Point for Switching
to Battery
Voltage 9, 10 Switch Position
180 VAC Up, Up
170 VAC Up, Down
180 VAC Down, Up
170 VAC Down, Down (factory setting)
11
Select High AC Input Voltage Point for Switching to
Battery - OPTIONAL*
Voltage Switch Position
270 VAC Up
260 VAC Down (factory setting)
* Most of your connected appliances and equipment will perform adequately when your Inverter/Charger’s High AC Input Voltage Point and its Low AC
Voltage Input Point is left in the factory setting. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that
would have little effect on equipment operation, you may wish to adjust these settings. By increasing the High AC Voltage Point and/or decreasing the Low
AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.
To reduce the chance of tripping this breaker, all Inverter/Chargers are pre-set to automatically limit the input current as described in “Most
Limiting” below. If your unit is equipped with DIP switches 7 and 8, they may be used to select other AC input current sharing settings.
Verify that AC input wiring is rated for the higher current that results when using the other settings.
Select Battery Charger-Limiting Points
“Most Limiting” (#7 & #8 Up): Charger-
limiting takes effect the moment any AC load
is applied; charger output falls gradually from
full output at no AC load passing through to
no output at full load (factory setting).
“Less Limiting” (#7 Up & #8 Down):
Charger-limiting begins when the Inverter/
Charger’s load reaches 33% of the Inverter/
Charger’s load rating. Charger output falls
gradually from full output at 33% of the
Inverter/Charger’s load rating to about 33% of full output at full load.
“Least Limiting” (#7 Down & #8 Up):
Charger-limiting begins when the Inverter/
Charger’s load reaches 66% of the Inverter/
Charger’s load rating. Charger output falls
gradually from full output at 66% of the
Inverter/Charger’s load rating to about 66% of full output at full load.
“No Limiting” (#7 & #8 Down): No charger-
limiting occurs at any load size.
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
7
Configuration
12
Select Battery Type - REQUIRED
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect, or your batteries may be degraded or
damaged over an extended period of time. See “Battery Selection” for more information.
Battery Type Switch Position
AGM/Gel Cell (Sealed) Battery Up
Wet Cell (Vented) Battery Down (factory setting)
Set Battery Charge Conserver (Load Sense) Control—OPTIONAL
In order to save battery power, the unit’s inverter automatically shuts off in the absence of any power demand from
connected equipment or appliances (the electrical load). When the Inverter/Charger detects a load, it automatically turns its
inverter function on. Users may choose the minimum load the Inverter/Charger will detect by adjusting the Battery Charge
Conserver Control (see diagram). Using a flathead screwdriver, turn the control clockwise to lower the minimum load that
will be detected, causing the inverter to turn on for smaller loads. When the control is turned fully clockwise, the inverter will
operate even when there is no load. Turn the control counterclockwise to increase the minimum load that will be detected,
causing the inverter to stay off until the new minimum load is reached.
Note: The factory setting for the control is fully clockwise. However, based on the threshold load to which you’d like the inverter to respond, you should
adjust the control counterclockwise to reduce its sensitivity until the inverter is active only when connected equipment or appliances are actually in use.
Connect Remote Control—OPTIONAL
The unit features an 8-conductor telephone style jack on the front panel for use with an optional remote control module (Tripp Lite model
APSRM4, sold separately). The remote module allows the Inverter/Charger to be mounted in a compartment or cabinet out of sight, while
operated conveniently from a remote location. See instructions packed with the remote control module.
Connect Battery Temperature Sensing Cable—OPTIONAL
(Contact Tripp Lite for optional temperature sensing cable accessory.)
The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature.
Connect the sensor cable (the cable has an RJ style connector on one end and a sensor on the other) to the RJ style jack located on the
front panel of the Inverter/Charger labeled “RMT BATT TEMP.” With user-supplied electrical or duct tape, affix the sensor to the side of the
battery below the electrolyte level. Make sure that nothing, not even tape, comes between the sensor and the side of the battery. To guard
against false readings due to ambient temperature, place the sensor between batteries, if possible, and away from sources of extreme heat
or cold. If the sensor cable is not used, the Inverter/Charger will charge according to its default value (25º C).
Connect Automatic Generator Starter—OPTIONAL
Connect the RJ type modular jack on the front panel labeled “RMT GEN START” to separate
generator ON/OFF switching mechanism with user-supplied cable (see Pin Configuration Diagram).
Once attached, the interface will allow the Inverter/Charger to automatically switch a separate
generator on when connected battery voltage levels are low and switch it off when battery voltage
levels are high.
Note: The operations below apply only to the APSX6048VRNET.
Connect External SNMP/Web Management Module—OPTIONAL
(Contact Tripp Lite for optional external SNMP/Web management module accessory.)
The SNMP/Web management module (Tripp Lite model SNMPWEBSOLOHV) allows the user to remotely monitor and control the
inverter/charger. Using the standard serial cable provided with the SNMPWEBSOLOHV, connect one end to the Accessory port on the
SNMPWEBSOLOHV labeled “UPS/APS” and the other end to the DB9 serial port located on the front panel of the Inverter/Charger.
Connect 12V DC Power Connector—OPTIONAL
The DC Power Connector enables the SNMPWEBSOLOHV to be powered directly from the Inverter/Charger, eliminating the need for an AC
outlet. Connect one end of the cable (included with the SNMPWEBSOLOHV) to the port on the SNMPWEBSOLOHV labeled “DC Power” and
connect the other end directly to the Inverter/Charger.
8
Battery Selection
Select Battery Type
Select “Deep Cycle” batteries to enjoy optimum performance from your Inverter/Charger. Batteries of either Wet-Cell (vented) or Gel-Cell /
Absorbed Glass Mat (sealed) construction are ideal. 6-volt “golf cart,” Marine Deep-Cycle or 8D Deep-Cycle batteries are also acceptable.
You must set the Inverter/Charger’s Battery Type DIP Switch (see Configuration section for more information) to match the type of batteries
you connect or your batteries may be degraded or damaged over an extended period of time.
Match Battery Amp-Hour Capacity to Your Application
Select a battery or system of batteries that will provide your Inverter/Charger with proper DC voltage and an adequate amp-hour capacity to
power your application. Even though Tripp Lite Inverter/Chargers are highly efficient at DC-to-AC inversion, their rated output capacities are
limited by the total amp-hour capacity of connected batteries plus the output of an alternator when one is used.
• STEP 1) Determine Total Wattage Required
Add the wattage ratings of all equipment you will connect to your
Inverter/Charger. Wattage ratings are usually listed in equipment
manuals or on nameplates. If your equipment is rated in amps,
multiply that number times AC utility voltage to estimate watts.
(Example: a drill requires 2.8 amps. 2.8 amps × 230 volts =
640 watts.)
Note: Your Inverter/Charger will operate at higher efficiencies at about
75% - 80% of nameplate rating.
• STEP 2) Determine DC Battery Amps Required
Divide the total wattage required (from step 1, above) by the
nominal battery voltage to determine the DC amps required.
• STEP 3) Estimate Battery Amp-Hours Required
Multiply the DC amps required (from step 2, above) by the
number of hours you estimate you will operate your equipment
exclusively from battery power before you have to recharge your
batteries with utility- or generator-supplied AC power. Compensate
for inefficiency by multiplying this number by 1.2. This will give
you a rough estimate of how many amp-hours of battery power
(from one or several batteries) you should connect to your
Inverter/Charger.
Note: Battery amp-hour ratings are usually given for a 20-hour discharge
rate. Actual amp-hour capacities are less when batteries are discharged
at faster rates. For example, batteries discharged in 55 minutes provide
only 50% of their listed amp-hour ratings, while batteries discharged in
9 minutes provide as little as 30% of their amp-hour ratings.
• STEP 4) Estimate Battery Recharge Required,
Given Your Application
You must allow your batteries to recharge long enough to replace
the charge lost during inverter operation or else you will eventually
run down your batteries. To estimate the minimum amount of
time you need to recharge your batteries given your application,
divide your required battery amp-hours (from step 3, above)
by your Inverter/Charger’s rated charging amps (23A or 90A,
depending on Switch #5 setting).
Example
Tools
13mm (1/2”) Drill Circular Saw
640W + 800W = 1440W
Appliances and Electronics
Desktop
Signal Computer
Relay with Large
Refrigerator Table Fan Tower LCD Monitor
540W + 150W + 500W + 250W = 1440W
1440 watts ÷ 48V = 30 DC Amps
30 DC Amps × 5 Hrs. Runtime
× 1.2 Inefficiency Rating = 180 Amp-Hours
180 Amp-Hours ÷ 23 Amps
Inverter/Charger Rating = 7.8 Hours Recharge
9
Battery Connection
Connect your Inverter/Charger to your batteries using the following procedures:
• Connect DC Wiring: Though your Inverter/Charger is a high-efficiency converter of electricity, its rated
output capacity is limited by the length and gauge of the cabling running from the battery to the unit. Use
the shortest length and largest diameter cabling (maximum 9.3 mm diameter (2/0 AWG)) to fit your Inverter/
Charger’s DC Input terminals. Shorter and heavier gauge cabling reduces DC voltage drop and allows for
maximum transfer of current. Your Inverter/Charger is capable of delivering peak wattage at up to 200% of
its rated continuous wattage output for brief periods of time. Heavier gauge cabling should be used when
continuously operating heavy draw equipment under these conditions. Tighten your Inverter/Charger and
battery terminals to approximately 3.5 Newton-meters of torque to create an efficient connection and to
prevent excessive heating at this connection. Insufficient tightening of the terminals could void your warranty.
See table below for recommended cable sizing chart.
• Connect Fuse: Tripp Lite recommends that you connect your battery to your Inverter/Charger’s DC terminals with wiring that includes
a fuse and fuse block within 450 mm of the battery. The fuse’s rating must equal or exceed the Minimum DC Fuse Rating shown on the
Inverter/Charger’s nameplate. See diagrams below for proper fuse placement. The battery wire with the fuse should not be grounded.
• Battery Grounding: The Inverter/Charger will operate properly with the battery negative terminal or the battery positive terminal
connected to earth ground. It will also operate properly without an earth ground connection to either battery terminal. Any battery ground
connection should be made directly from the battery terminal to earth ground.
Maximum Recommended DC Cable Length
Wire Diameter (Gauge)
8.3 mm (0 AWG) 9.3 mm (2/0 AWG)
VDC Output Power Maximum Distance from Battery to Unit
24V 3000W 13 m (42 ft) 16 m (52 ft)
48V 6000W Do not use 32 m (105 ft)
WARNING!
• Follow all applicable electrical codes and requirements for battery grounding.
• Never attempt to operate your Inverter/Charger by connecting it directly to output from an alternator rather
than a battery or battery bank.
• Observe proper polarity with all DC connections.
Series Connection
In a series connection, your Inverter/Charger’s Nominal DC Input Voltage must match the number of batteries multiplied by their voltage.
For example, a 48V DC Inverter/Charger requires either four 12V batteries connected in series (48 = 4 × 12) or eight 6V batteries
connected in series (48 = 8 × 6).
Contact Tripp Lite technical support for assistance with additional parallel, series or series/parallel connections.
Figure below illustrates a 48V Inverter/Charger with a negative grounded battery system using 12V batteries.
Figure below illustrates a 48V Inverter/Charger with a positive grounded battery system using 12V batteries.
1
Earth Ground
2
Battery
3
UL-Listed Fuse
& Fuse Block
(mounted within
450 mm of the
battery)
4
Large Diameter
Cabling, Maximum
9.3 mm diameter
(2/0 AWG) to Fit
Terminals
DC Connectors
Multiple Battery Connection (Series)
Multiple Battery Connection (Series)
1
2
2
2
2
2
2
2 4
43
3
2
1
10
AC Input/Output Connection
AC Generator Input
To avoid overloading your Inverter/Charger, be sure to match the power requirements of the equipment you plan to run at any one time (add
their total watts) with the output wattage capacity of your Inverter/Charger model. When figuring the power requirements of your equipment,
do not confuse “continuous” wattage with “peak” wattage ratings. Most electric motors require extra power at start-up (“peak” wattage)
than required to run continuously after start-up, sometimes over 100% more. Some motors, such as in refrigerators and pumps, start and
stop intermittently according to demand, requiring “peak” wattage at multiple, unpredictable times during operation.
• Cabinet Grounding
Using a 3.15 mm diameter (8 AWG) wire or larger, directly connect the Main Ground Lug to earth ground. See the Feature Identification
section to locate the Main Ground Lug on your specific Inverter/Charger model.
• OverPower™ and DoubleBoost™ Features
Tripp Lite Inverter/Chargers deliver up to 150% of their nameplate-rated wattage for 1-60 minutes (OverPower) and up to 200% for 10
seconds (DoubleBoost) under ideal battery and temperature conditions*, providing ample reserve power to support tools and equipment.
* For best results, utilize OverPower for as short a duration as possible, ensure that battery bank and cabling are able to provide full nominal DC voltage
under load, and allow the inverter/charger to cool completely before and after OverPower utilization.
Warning! Consult a qualified electrician and follow all applicable electrical codes and requirements for
hardwire connection. Disconnect both DC input and AC utility supply before attempting hardwiring. Over-
current protection should be provided in accordance with local and/or national electrical codes. Refer to
nameplate on unit for input and output current ratings. Use wire with a minimum temperature rating of 90º C.
A readily visible and adequate disconnect device must be provided. Failure to properly ground your Inverter/
Charger to earth ground may result in a lethal electrical shock hazard.
Remove the screws and cover plate over the hardwire terminal strip. Remove the knockout covers closest to the desired electrical source
and to your equipment. Attach 13 mm (0.5 inch) diameter conduits (user-supplied) to the knockouts and thread wires through. Connect
the conduits to each other with the ground bond connection supplied.
Ground*
• Connect the incoming and outgoing ground wires to the ground
terminals
1
.
• Connect the Main Ground Lug
2
to earth ground.
AC Input
• Connect the incoming hot wire to the input hot terminal
3
.
• Connect the incoming neutral wire to the input neutral terminal
4
.
AC Output
• Connect the outgoing hot wire to the output hot terminal
5
.
• Connect the outgoing neutral wire to the output neutral terminal
6
.
Replace cover plate and tighten screws.
* If the incoming conduit only contains two wires (hot and neutral), the incoming
conduit must be bonded to the main ground lug on the unit. In any case, the
incoming conduit must be bonded to earth ground, and the incoming conduit must
be bonded to the outgoing conduit.
The inverter/charger is designed to provide heavy-duty power to both the AC output load and the DC battery charging load at the same time.
The amount of additional input power required is determined by the setting of the AC Input Current Sharing DIP switches (switches 7 and
8 - see the Configuration section for switch settings). The recommended minimum VA rating for AC generator input is shown in the table
below.
Minimum Recommended AC Generator VA Rating
AC Input Current
Sharing APSX3024SW APSX6048VRNET
Most Limiting 3750VA 7500VA
Less Limiting 4900VA N/A
Least Limiting 6000VA N/A
No Limiting 7200VA N/A
Note: If the applied AC load is significantly less than that of the
Inverter/Charger’s AC output rating, a smaller size generator may
be used by setting the battery charger DIP Switch to the low DC
current setting. The minimum recommended VA rating for the AC
generator would then be the VA needed for the Charger (1100 VA
for APSX3024SW or 2000 VA for APSX6048VRNET) plus the VA
required for the load.
2
3
5
4
6
1
11
Service
Maintenance
Troubleshooting
Your Tripp Lite product is covered by the warranty described in this manual. A variety of Extended Warranty and On-Site Service Programs
are also available from Tripp Lite. For more information on service, visit www.tripplite.com/support. Before returning your product for service,
follow these steps:
1. Review the installation and operation procedures in this manual to insure that the service problem does not originate from a misreading
of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Product Returns link. From here you can request a Returned
Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit’s model and serial
numbers, along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to you.
Any damages (direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized
Tripp Lite service center are not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must
have transportation charges prepaid. Mark the RMA number on the outside of the package. If the product is within its warranty period,
enclose a copy of your sales receipt. Return the product for service using an insured carrier to the address given to you when you
request the RMA.
Your Inverter/Charger requires no maintenance and contains no user-serviceable or replaceable parts, but should be kept dry at all times.
Periodically check, clean and tighten all cable connections as necessary, both at the unit and at the battery.
Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service before returning
your unit for service.
SYMPTOM PROBLEMS CORRECTIONS
No AC Output (All
Indicator Lights Are OFF)
Unit is not properly connected to utility power. Connect unit to utility power.
Operating Mode Switch is set to “OFF” and AC
input is present.
Set Operating Mode Switch to “AUTO/REMOTE” or “CHARGE ONLY.”
This is normal when the Operating Mode Switch
is set to “CHARGE ONLY” and AC input is absent.
No correction is required. AC output will return when AC input returns.
Set Operating Mode Switch to “AUTO/REMOTE” if you require AC output.
Unit has shut down due to battery overcharge
(preventing battery damage). The problem may
be with connected auxiliary chargers, if any, or
with the unit’s charger.
Disconnect any auxiliary chargers. Reset by moving Operating Mode Switch
to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” or “CHARGE ONLY.”
If unit remains in shutdown mode after several attempts to reset, contact
Tripp Lite Customer Service for assistance.
Unit has shut down due to excessive battery
discharge.
Use an auxiliary charger* to raise battery voltage. Check external battery
connections and fuse. Unit automatically resets when condition is cleared.
Unit has shut down due to overload. Reduce load. Reset by moving Operating Mode Switch to “OFF.” Wait 1
minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.”
Battery Not Recharging
(AC Input Present)
Connected batteries are dead. Check and replace old batteries.
Battery fuse* is blown. Check and replace fuse.*
Battery cabling* is loose. Check and tighten or replace cabling.*
Unit has shut down due to battery overcharge
(preventing battery damage). The problem may
be with connected auxiliary chargers, if any, or
with the unit’s charger.
Disconnect any auxiliary chargers. Reset by moving Operating Mode Switch
to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” or “CHARGE ONLY.”
If unit remains in shutdown mode after several attempts to reset, contact
Tripp Lite Customer Service for assistance.
All Three Battery Indicator
Lights Are Slowly Flashing
(½ Second Flashes)
Battery is excessively discharged. Use an auxiliary charger* to raise battery voltage. Check external battery
connections and fuse. Unit automatically resets when condition is cleared.
All Three Battery Indicator
Lights Are Rapidly Flashing
(¼ Second Flashes)
Battery is overcharged. Unit will shut down to
prevent battery damage. The problem may be
with connected auxiliary chargers, if any, or with
the unit’s charger.
Disconnect any auxiliary chargers. Reset by moving Operating Mode Switch
to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” or “CHARGE ONLY.”
If unit remains in shutdown mode after several attempts to reset, contact
Tripp Lite Customer Service for assistance.
Red “LOW” Battery
Indicator Light is Flashing
Battery voltage is low. Unit will automatically
shut down after 10 seconds to protect battery
from damage.
Make sure that AC power is present in order to recharge batteries. Reset
by moving Operating Mode Switch to “OFF” then to “AUTO/REMOTE” or
“CHARGE ONLY.”
False reading due to undersized or insufficiently
connected DC cabling.
Use sufficient size DC cable sufficiently connected to the Inverter/Charger.
Red “LOAD” Operation
Indicator Light Flashing
Inverter is overloaded. Unit will automatically
shut down after 5 seconds.
Reduce load. Reset by moving Operating Mode Switch to “OFF.”
Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.”
*User-supplied.
12
Warranty
2-Year Limited Warranty
TRIPP LITE warrants its products to be free from defects in materials and workmanship for a period of two (2) years from the date of initial purchase. TRIPP LITE’s obligation
under this warranty is limited to repairing or replacing (at its sole option) any such defective products. To obtain service under this warranty, you must obtain a Returned Material
Authorization (RMA) number from TRIPP LITE or an authorized TRIPP LITE service center. Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with
transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply
to equipment, which has been damaged by accident, negligence or misapplication or has been altered or modified in any way.
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE.
Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE
OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, TRIPP LITE is not liable for any costs, such as lost profits or revenue, loss of equipment,
loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment
from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found
on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series
number. The series number should not be confused with the marketing name or model number of the product.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Note on Labeling
Two symbols are used on the APS labels.
V~: AC Voltage
: DC Voltage
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
13
Manual del Propietario
Inversores / Cargadores
APSX de CD a CA de
Onda Sinusoidal Pura
Modelos: APSX3024SW, APSX6048VRNET
Introducción 14
Instrucciones de Seguridad Importantes 14
Identificación de las Características 15
Operación 16
Configuración 17
Selección de la Batería 20
Conexión de la Batería 21
Conexión de entrada/salida de CA 22
Entrada de Generador de CA 22
Servicio/Mantenimiento 23
Solución de Problemas 23
Garantía 24
English 1
Français 25
 37
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2019 Tripp Lite.Todos los derechos reservados. Isobar
®
es una marca registrada de Tripp Lite.
14
Instrucciones de Seguridad Importantes
¡GUARDE ESTAS INSTRUCCIONES!
Este manual contiene instrucciones y advertencias importantes que deben seguirse durante la instalación, el funcionamiento y el
almacenamiento de todos los Inversores/Cargadores de Tripp Lite.
Advertencias de ubicación
Instale su Inversor/Cargador en una ubicación o compartimiento que minimice la exposición al calor, polvo, luz solar directa y humedad.
Aunque su Inversor/Cargador es resistente a la humedad NO es a prueba de agua.El inundar la unidad con agua causará un corto
circuito y podría causar lesiones personales debidas a descarga eléctrica.Nunca sumerja la unidad y evite cualquier área en donde se
pueda acumular agua estancada.La instalación se debe hacer en el sitio más seco posible.
Deje un mínimo de 50 mm de holgura al frente y en la parte posterior del Inversor/Cargador para una ventilación adecuada.Mientras más
alta sea la carga conectada, mayor calor generará la unidad.
No coloque el Inversor/Cargador cerca de medios de almacenamiento magnéticos, podría causar corrupción de datos.
No instale cerca de materiales, combustible o químicos inflamables.
No Instale la unidad con el panel frontal o trasero orientado hacia abajo (en cualquier ángulo).Si la instala de esta manera
inhibirá gravemente la capacidad de enfriamiento interno de la unidad, lo que eventualmente provocará daños en el producto
no cubiertos por la garantía.
Instale su Inversor Cargador ANTES de la conexión de la batería de CD y la alimentación de CA.La omisión al seguir estas instrucciones
puede conducir a lesiones personales y/o daño al Inversor/Cargador y los sistemas conectados.
Advertencias sobre la Conexión de la Batería
La batería debe conectarse antes de operar el Inversor/Cargador.
Los sistemas de baterías múltiples deben componerse de baterías de voltaje, edad, capacidad en amp-hora y tipo idénticos.
Si las baterías no se mantienen bien ventiladas, puede acumularse hidrógeno explosivo cerca de las mismas, las baterías no deben
instalarse en compartimientos sin ventilación.De manera ideal, cualquier compartimiento debe tener alguna ventilación al aire exterior.
Durante la conexión final de las baterías pueden producirse chispas.Observe siempre la polaridad correcta al conectar las baterías.
No permita que algún objeto haga contacto entre las dos terminales de entrada de CD.No ponga en corto o puentee estas terminales
entre sí.Puede causarse una lesión personal severa o daño a la propiedad.
Advertencias sobre la Conexión de Equipos
No se recomienda usar este equipo en aplicaciones de mantenimiento artificial de vida, donde se puede esperar razonablemente que
su falla cause la falla del equipo de mantenimiento de vida o que afecte de manera importante su seguridad o eficiencia.No use este
equipo en presencia de mezclas anestésicas inflamables con aire, oxígeno u óxido nitroso.
Conecte su Inversor/Cargador directamente a una fuente de energía CA adecuadamente conectado a tierra.No enchufe la unidad a sí
misma, dañará el dispositivo y anulará la garantía.
La oreja de conexión a tierra principal debe conectarse a tierra con un cable de 3.15 mm de diámetro (8 AWG) mínimo.
Advertencias de Operación
Su Inversor/Cargador no requiere rutina de mantenimiento.No abra el dispositivo bajo ninguna circunstancia.No tiene partes internas que
el usuario pueda reparar.
Dentro del Inversor/Cargador existen voltajes potencialmente letales mientras estén conectados el suministro de las baterías y/o la
alimentación CA.Por lo tanto deben desconectarse la alimentación de batería y la alimentación de CA durante cualquier trabajo de
mantenimiento.
No conecte o desconecte las baterías mientras el Inversor/Cargador esté operando en modo de inversor o cargador.El Interruptor del
Modo de Operación debe estar en la posición OFF.Puede ocasionarse un arco peligroso.
Introducción
¡Felicitaciones! Usted compró el Inversor/Cargador más avanzado y lleno de funciones diseñado como fuente de energía alternativa durante
fallas de la energía de la red pública. Los Inversores/Cargadores APS de Tripp Lite mantienen su equipo constantemente encendido
y productivo a través de todos los problemas de energía de la red (apagones, reducciones de tensión y sobretensiones) invirtiendo
automáticamente la energía CD de las baterías, proporcionadas por el usuario, a energía CA. La supresión de sobretensiones integrada
proporciona un nivel adicional de protección al equipo. Cuando se cuenta con energía suministrada por la red pública, los inversores/
cargadores APS automáticamente pasan energía a su equipo mientras, al mismo tiempo, recargan el banco de baterías conectado.
Los inversores/cargadores APS son la alternativa silenciosa para los generadores de combustible durante aplicaciones de respaldo de
emergencia ¡Sin tener que soportar humo, combustible ni ruido! Usted obtiene electricidad CA en el lugar y la hora que la necesite.
15
Identificación de las Características
1
Interruptores DIP de Configuración: Optimice la operación
del Inversor/Cargador dependiendo de su aplicación.Para
instrucciones vea la sección de Configuración.
2
Interruptor (Selector) de Modo de Operación: Controla
la operación del Inversor/Cargador.La posición de “AUTO/
REMOTE” asegura que su equipo reciba energía CA constante
sin interrupción.También activa el Inversor/Cargador para ser
monitoreado en forma remota con un módulo remoto opcional
(modelo APSRM4 de Tripp Lite, se vende por separado).La
posición de “CHARGE ONLY” permite que sus baterías regresen
a carga completa más rápido apagando el inversor, lo que
suspende la descarga de la batería.La posición “OFF” desactiva
la unidad (incluyendo su salida de CA).Para instrucciones vea
la sección de Operación.
3
Luces del Indicador de Operación: Las señales intuitivas
“tipo semáforo” muestran cuando el Inversor/Cargador está
operando desde la alimentación de CA o la energía CD de la
batería.También le advierten si la carga del equipo conectado
es demasiado alta.Para instrucciones sobre la lectura de las
luces indicadoras, vea la sección de Operación.
4
Luces del Indicador de Batería: Las señales intuitivas
“tipo semaforo” muestran el nivel de carga aproximado de
su batería.Para instrucciones sobre la lectura de las luces
indicadoras, vea la sección de Operación.
5
Terminales de Energía de CD: Conecte las terminales de su
batería.Para las instrucciones de conexión, vea la sección de
Conexión de Bateria.
6
Tira de Terminales de Cableado de Entrada/Salida de
CA (Panel de Acceso): Conecta con seguridad el Inversor/
Cargador al sistema de suministro eléctrico de la instalación.
Para las instrucciones de conexión, vea la sección de
Conexión de Entrada/Salida de CA.
7
Accesps para Conductos de Entrada/Salida de CA
8
Conector del Módulo de Control Remoto Permite el
monitoreo y control remoto con un módulo opcional (modelo
APSRM4 de Tripp Lite, se vende por separado.Consulte
el manual del propietario del módulo remoto para ver las
instrucciones de conexión.
9
Control del Conservador de Carga de la Batería (Detección de
Carga): Conserva la energía de la batería seleccionando el nivel de
carga baja al que el Inversor/Cargador se apaga automáticamente.
Para instrucciones vea la sección de Configuración.
10
Pestaña de Conexión Principal a Tierra: Conecta
correctamente a tierra el Inversor/Cargador.Para las instrucciones
de conexión, vea la sección de Conexión de Bateria.
11
Ventiladores de Enfriamiento Controlados por Termostato:
Ventiladores silenciosos y eficientes regulan la temperatura
interna y prolongan la vida útil del equipo.Los ventiladores
funcionan a una velocidad variable, dependiendo de la
temperatura y carga.
12
Conector de Arranque Remoto del Generador: Enciende y
apaga automáticamente el generador basado en el voltaje de
la batería. Use con cable suministrado por el usuario. Para más
información, consulte la sección de Configuración.
13
Conexión de Detección Remota de Temperatura de la
Batería: Prolonga la vida de la batería ajustando la carga
basado en la temperatura de la batería.Póngase en contacto
con Tripp Lite para obtener el cable opcional de detección
de temperatura.Consulte la sección de Configuration para
obtener más información.
14
Conector de Comunicación Serial RS-232 (APSX6048VRNET
únicamente): Puede usarse para conectar un módulo externo
de administración (modelo SNMPWEBSOLOHV de Tripp Lite) para
monitorear en forma remota su Inversor/Cargador.
15
Conector de Alimentación de CC (APSX6048VRNET
únicamente): Alimenta independientemente al módulo de
administración de red/SNMP (Modelo SNMPWEBSOLOHV de
Tripp Lite) sin el uso de un tomacorrientes de CA.
11213
6
7 11
14
2
5
9
10
4 8 3
En el Costado
No se Muestra
15
16
Operación
Modos del Interruptor
Después de configurar, instalar y conectar su Inversor/Cargador,
usted puede operarlo conmutando entre los siguientes modos de
funcionamiento según convenga a su situación:
AUTO/REMOTE: Cambie a este modo cuando
necesite energía CA constante y sin interrupción
para aplicaciones y equipo conectado.El Inversor/
Cargador continuará suministrando energía CA al
equipo conectado y cargando sus baterías conectadas
mientras esté presente energía CA de la red o de
generador.Ya que el inversor está encendido (pero en espera) en
este modo, conmutará automáticamente a su sistema de batería
para alimentar CA al equipo conectado en ausencia de una fuente
de energía de la redpública/generador o en situaciones de alto/
bajovoltaje.“AUTO/REMOTE” activa también un módulo opcional
de control remoto (modelo APSRM4 de Tripp Lite, se vende por
separado) para funcionar cuando está conectado a la unidad.
CHARGE ONLY: Cambie a este modo cuando no
esté usando dispositivos y equipo conectados a fin
de conservar energía de la batería desactivando el
inversor.El Inversor/Cargador continuará pasando
energía de CA al equipo conectado y cargando sus
baterías conectadas mientras esté presente energía
CA de la red pública o de generador. Sin embargo, ya que el
inversor está apagado, en este modo, no alimentará energía CA al
equipo conectado en ausencia de una fuente deenergía de la red
pública/generador o en situaciones de alto/bajovoltaje.
OFF: Cambie a este modo para apagar completamente
el Inversor/ Cargador, evitando que el inversor
descargue energía de las baterías y evitando el paso
de energía CA al equipo conectado o la carga de
las baterías.Use este interruptor para reestablecer
automáticamente la unidad si se apaga debido a
sobrecarga o sobrecalentamiento.Retire primero la carga excesiva
o permita que la unidad se enfríe lo suficiente (aplicable a su
situación).Cambie a “OFF”, entonces regrese a “AUTO/REMOTE” o
“CHARGE ONLY” según desee. Si la unidad no se reestablece, retire
más carga o deje que la unidad se enfríe más y reintente.
Nota: El módulo opcional de control remoto (APSRM4) sólo reestablecerá
sobrecargas
Luces Indicadoras
Su Inversor/Cargador (así como un Módulo opcional de control
remoto de Tripp Lite, se vende por separado) está equipado con un
juegogrupo de luces indicadores sencillo, intuitivo y amigable.Estas
señales “tipo semáforo” fáciles de recordar le permitirán conocer de
un vistazo la condición de carga de sus baterías, así como averiguar
detalles y condiciones de falla.
LINE (alimentación)Indicador Verde: Si el
selector de modo de operación está en “AUTO/
REMOTE”, esta luz ENCENDERÁ CONTINUAMENTE
cuando su equipo conectado esté recibiendo
energía CA continua suministrada desde la red del
servicio público o un generador.
Si el selector del modo de operación está en to “CHARGE ONLY”,
esta luz DESTELLARÁ para advertirle que el inversor de la unidad
está apagado y NO suministrará energía CA en ausencia de una
fuente de energía de la red del servicio público o generador o en
condiciones de alto o bajo voltaje.
INV (Inversión)Indicador Verde: Esta luz
ENCENDERÁ CONTINUAMENTE cuando el equipo
conectado esté recibiendo energía CA invertida
suministrada por la batería (en ausencia de una
fuente de energía de la red pública o generador o en
situaciones de alto o bajo voltaje). Esta luz estará
apagada cuando la energía CA esté alimentando la carga. Esta luz
DESTELLARÁ para advertirle si la carga es inferior a la calibración del
Conservador de Carga de la Batería (Detector de Carga).
LOAD (Carga) Indicador Rojo: Esta luz roja
ENCENDERÁ CONTINUAMENTE cuando el inversor
esté funcionando y la energía demandada por las
aplicaciones y equipos instalados exceda el 100%
de la capacidad de carga.La luz DESTELLARÁ para
advertirle cuando el inversor se apague debido a una
sobrecarga o sobrecalentamiento severo.Si esto ocurre, coloque el
selector de modo en “OFF”; reduzca la sobrecarga y deje que la unidad
se enfríe.Usted puede cambiar el selector de modo a “AUTO/REMOTE”
o“CHARGE ONLY” después de haberse enfriado adecuadamente. Esta
luz estará apagada cuando la energía CA esté alimentando la carga.
Luces Indicadoras de BATTERY (Batería): Estas tres luces
encenderán en diversas secuencias para mostrar el nivel de carga
aproximado de su banco de baterías conectado y le avisará de dos
condiciones de falla:
Nivel de Carga Aproximado de la Batería*
Indicador Encendido Capacidad de Batería
(Cargando/Descargando)
1
Verde 91%–Llena
2
Verde y Amarillo 81%–90%
3
Amarillo 61%–80%
4
Amarillo y Rojo 41%–60%
5
Rojo 21%–40%
6
Las tres luces
apagadas 1%–20%
7
Rojo destellando 0% (Inversor apagado)
* Los niveles de carga listados son aproximados. Las
condiciones reales varían de acuerdo con la condición y carga de la batería.
Condición de Falla
Indicador Encendido Condición de Falla
1
Las tres luces Descarga excesiva
destellan lento* (Inversor apagado)
2
Las tres luces Sobrecarga
destellan rápido** (Cargador apagado)
*Aproximadamente 1/2 segundo encendido, 1/2 segundo apagado.Consulte
la sección de Solución de Problemas.**Aproximadamente 1/4 segundo
encendido, 1/4 segundo apagado.Puede indicar también que existe una
falla del cargadior.Consulte la sección de Solución de Problemas.
Reestablecimiento de su Inversor/Cargador
para Reestablecer la Energía CA
Su Inversor/Cargador puede cesar de alimentar energía de CA
o carga de CD a fin de protegerse de sobrecargas o proteger su
sistema eléctrico.Para reestablecer el funcionamiento normal:
Reestablecimiento de Sobrecarga: Cambie el selector de modo
a “OFF” y retire algo de la carga conectada (p.e.:apague algunos de
los dispositivos de CA que descargan energía lo que puede haber
causado la sobrecarga de la unidad).Espere un minuto, entonces
cambie el selector de modo nuevamente a “AUTO/REMOTE” o
“CHARGE ONLY.”
Posición =
(Posición Φ)
6
3
5
2
4
7
1
21
17
Configuración
Calibración de los Interruptores DIP de
Configuración
Usando una herramienta pequeña, ajuste los interruptores DIP
de configuración (localizados en el panel frontal de su unidad,
ver diagrama) para optimizar la operación del Inversor/Cargador
dependiendo de su aplicación. Advertencia:Asegúrese de que la
unidad esté apagada antes de cambiar la configuración de los
interruptores DIP.
1
Sin Uso
2
Selecciona Tiempo de Transferencia de Relevador para
Conectar a Línea - OPCIONAL
Tiempo de transferencia Posición del Interruptor
Tiempo de transferencia de 1/2 ciclo. Arriba
Tiempo de transferencia de 1 ciclo. Abajo (ajuste de fábrica)
3
Selecciona Frecuencia - REQUERIDO
Frecuencia Posición del Interruptor
60 Hz Arriba
50 Hz Abajo (ajuste de fábrica)
4
Selecciona Tensión de Línea – REQUERIDO
(Sólo modelo APSX6048VRNET)
Tensión Posición del Interruptor
208 VCA Arriba
230 VCA Abajo (ajuste de fábrica)
5
Selecciona el ajuste de Amperaje del Cargador de Batería
PRECAUCIÓN: Al cambiar a un ajuste de Amperaje de
Carga Alto [High Charge Amp], el usuario debe asegurar
que la capacidad en amp hora de su sistema de batería
exceda la corriente del ajuste High Charge Amp o las
baterías pueden dañarse o degradarse.
6
Select Equalize Battery Charge - OPTIONAL
Cambie Este interruptor DIP a la posición de abajo por 3
segundos para iniciar el proceso de ecualizado del estado
de carga de las celdas de su batería sobrecargando por
tiempo limitado todas las celdas.Esto puede extender
la vida útil de algunos tipos de baterías; consulte al
fabricante de sus baterías para determinar si éstas pueden
beneficiarse de este proceso.El proceso de ecualizado de
carga es automático; una vez iniciado, puede detenerse
solamente retirando la energía de alimentación.
Nota: El tiempo de transferencia predeterminada del Inversor
Cargador es de un ciclo, lo que proporciona protección óptima
para cargas estándar en áreas con apagones frecuentes.
Si utiliza el Inversor/Cargador para respaldar computadoras
u otras cargas de equipo electrónico sensible, coloque el
tiempo de transferencia en 1/2 ciclo (selector #2 arriba) para
asegurar operación ininterrumpida al cambiar el Inversor/
Cargador a energía de batería.
Cargador de Batería Posición del Interruptor
Amperaje de Carga Arriba (ajuste
bajo (23A) de fábrica)
Amperaje de Carga Abajo
Alto (90A)
Procedimiento de Ajuste
Mueva a la posición “Equalize” (ABAJO) por 3
segundos.
Mueva a la posición “Reset” (ARRIBA) y
déjelo así.Esta es la posición predeterminada.
PRECAUCIÓN:No deje el interruptor DIP #6
en la posición abajo después de iniciado el
proceso.La ecualización de carga de la batería
debe realizarse sólo con apego estricto a las
instrucciones y especificaciones del fabricante
de la batería.
Carga de la Batería Posición de Interruptor
Reset Arriba (ajuste de fábrica)
Equalize Abajo (3 segundos)
7
8
Selecciona Repartir Corriente de Entrada CA– OPCIONAL
(Sólo el modelo APSX3024SW; el modelo APSX6048VRNET opera sólo en modo “Most Limiting” [Más Limitado])
Su Inversor/Cargador cuenta con un cargador de batería de alta salida que puede usar una cantidad significativa de energía CA de su
instalación o generador al cargar a su tasa máxima.Si su unidad está alimentando a su tasa máxima de energía CA a sus cargas eléctricas
pesadas conectadas al mismo tiempo que se presenta esta carga alta, el interruptor automático de alimentación puede dispararse,
causando el apagado completo del paso de la corriente de alimentación.
Interruptores Dip de Conguració
(Para las instrucciones vea el manual
o la parte superior de la unidad)
Más rápida
Más lenta
Amperaje de carga bajo
Amperaje de carga alto
Restablecer
Ecualizar
18
Configuración
Operación a 230V (APSX3024SW)
9
10
Selecciona el Punto de Voltaje Bajo de la
Alimentación en VCA para Cambiar a Batería – OPCIONAL*
Voltaje Posición del Interruptor 9, 10
180 VCA Arriba, Arriba
170 VCA Arriba, Abajo
160 VCA Abajo, Arriba
150 VCA Abajo, Abajo (ajustede fábrica)
11
Selecciona el Punto del VoltajeAlto de la Alimentación en
VCA para Cambiar a Batería – OPCIONAL*
Voltaje Posición del Interruptor
270 VAC Arriba
260 VAC Abajo (ajuste de fábrica)
Operación a 208V (modelo APSX6048VRNET con Interruptor #4 en la posición“Arriba”)
9
10
Seleccione el Punto de Voltaje Bajo VAC para
Cambiar aBatería - OPCIONAL*
Voltaje Posición del Interruptor 9, 10
175 VCA Arriba, Arriba
165 VCA Arriba, Abajo
175 VCA Abajo, Arriba
165 VCA Abajo, Abajo (ajustede fábrica)
11
Selecciona el Punto de Voltaje Bajo de Alimentación en
VCA para Cambiar a Batería – OPCIONAL*
Voltaje Posición del Interruptor
245 VCA Arriba
235 VCA Abajo (ajuste de fábrica)
Operación a 230V (modelo APSX6048VRNET con Interruptor #4 en posición “Abajo”)
9
10
Selecciona el Punto de Voltaje Bajo de Alimentación
en VCA para Cambiar a Batería
Voltaje Posición del Interruptor 9, 10
180 VCA Arriba, Arriba
170 VCA Arriba, Abajo
180 VCA Abajo, Arriba
170 VCA Abajo, Abajo (ajuste de fábrica)
11
Selecciona el Punto Alto de Tensión de Alimentación en
VCA para Cambiar a Batería – OPCIONAL*
Voltaje Posición de Interruptor
270 VCA Arriba
260 VCA Abajo (ajuste de fábrica)
* La mayoría de sus aplicaciones y equipos conectados funcionarán adecuadamente cuando su Inversor/Cargador esté en el Punto Alto de Tensión de CA de
Alimentación se deja en la calibración de fábrica.Como sea.Si la unidad conmuta frecuentemente a energía de batería debido a oscilaciones momentáneas de tensión
alta/baja de alimentación que pueden tener poco efecto en la operación del equipo, usted puede desear cambiar estas calibraciones.Aumentando el Punto de Tensión
Alta de CA y/o reduciendo el Punto de Tensión Baja de CA, usted reducirá el número de veces que su unidad conmuta a batería debido a las oscilaciones de tensión.
Para reducir el riesgo de disparar este interruptor automático, todos los Inversores/Cargadores se pre-ajustan para limitar automáticamente
la corriente de entrada como se describe en “Más Limitado” más abajo.Si su unidad está equipada con los interruptores DIP 7 y 8, deben
usarse para seleccionar otras calibraciones de repartir corriente de alimentación CA.Verifique que el cableado de alimentación CA sea de un
calibre adecuadopara la corriente más alta que resulte al usar los otros ajustes.
Selecciona Cargador de Batería – Puntos de Límite
“Más Limitado” (#7 y #8 Arriba): La
limitación del cargador tiene efecto al
momento que se aplica la carga CA; la salida
del cargador desciende gradualmente desde
salida total cuando no hay carga CA pasando
a sin salida a carga plena (ajuste de fábrica).
“Menos Limitado” (#7 Arriba y #8
Abajo): limitación del cargador inicia cuando
el Inversor/Cargador alcanza el 33% de
su especificación de carga.La salida del
cargador desciende gradualmente desde
salida completa al 33% de la especificación de carga del Inversor/
Cargador a alrededor del 33% de la salida total a plena carga.
“Minimamente Limitada” (#7 Abajo y
#8 Arriba): La limitación del cargador inicia
cuando el Inversor/Cargador alcanza el 66%
de su especificación de carga. La salida del
cargador desciende gradualmente desde
salida completa al 66% de la especificación de carga del Inversor/
Cargador a alrededor del 66% de la salida total a plena carga.
“No Limitado” (#7 y #8 Abajo): La no
limitación del cargador ocurre a cualquier tasa
de carga.
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
19
Configuración
12
Selecciona Tipo de Batería - REQUERIDO
PRECAUCIÓN:La calibración del interruptor DIP de Tipo de Batería debe coincidir con el tipo de baterías que conecte o sus baterías se
degradarán o dañarán después de un período de tiempo.Consulte “Selección de Batería” para obtener más información.
Tipo de Batería Posición de Interruptor
Batería AGM/Celda de Gel (Sellada) Arriba
Batería de Celda Húmeda (Ventilada) Abajo (ajuste de fábrica)
Configuración de Control del Conservador de Carga de la Batería (Detección de Carga) – OPCIONAL
A fin de ahorrar energía de la batería, el inversor de la unidad se apaga automáticamente en ausencia de demanda de
energía de aplicaciones o equipo conectados (la carga eléctrica).Cuando el Inversor/Cargador detecta una carga, enciende
automáticamente su función de inversor.Los usuarios pueden elegir la carga mínima que el inversor/Cargador detectará
ajustando el Control del Conservador de Carga de la Batería (ver diagrama).Usando una herramienta pequeña, girar el
control en sentido de las manecillas del reloj a la carga mínima que se detectará, hará que el inversor encienda para cargas
más pequeñas.Cuando el control se gire completamente en sentido de las manecillas del reloj, el inversor operará aún si no
hay carga.Girar el control en sentido opuesto a las manecillas del reloj para aumentar la carga mínima que se detectará,
causará que el inversor permanezca apagado hasta que se alcance una nueva carga mínima.
Nota: El ajuste de fábrica para el control es completamente en sentido de las manecillas del reloj.Como sea, basado enel umbral de la carga a la que
desea que responda el inversor, deberá ajustar el control en sentido opuesto a las manecillas del reloj para reducir su sensibilidad hasta que el inversor se
active sólo cuando las aplicaciones y equipo conectados estén realmente en uso.
Conexión del Control Remoto – OPCIONAL
La unidad cuenta con un conector tipo telefónico de 8 conductores en el panel frontal para usarlo con un módulo opcional de control
remoto (modelo APSRM4 de Tripp Lite, se vende por separado).El módulo remoto permite que el Inversor/Cargador se instale en un
compartimiento o gabinete oculto mientras funciona convenientemente desde una posición remota.Vea las instrucciones empacadas con
el módulo de control remoto.
Conexión del Cable de Detección de Temperatura de la Batería – OPCIONAL
(Póngase en contacto con Tripp Lite para obtener el cable opcional de detección de temperatura).
La función de detección de temperatura de la batería prolonga la vida de la misma ajustando el nivel de voltaje de carga flotante basado
en la temperatura de la batería. Conecte el cable sensor (el cable tiene un conector estilo RJ en un extremo y un sensor en el otro)
al conector estilo RJ ubicado en el panel frontal del Inversor/Cargador etiquetado “RMT BATT TEMP.” Con cinta eléctrica o para ductos
proporcionada por el usuario, sujete el sensor al costado de la batería por debajo del nivel del electrolito. Asegúrese de que nada, ni
siquiera cinta, quede entre el sensor y el costado de la batería. Para evitar lecturas falsas debidas a temperatura ambiente, de ser posible,
coloque el sensor entre baterías y alejado de fuentes de calor o frío extremo.Si no se utiliza el cable del sensor, el Inversor/Cargador
cargará de acuerdo con su valor por defecto (25º C).
Conexión de Arrancador Automático del Generador — OPCIONAL
Conecte el conector modular tipo RJ en el panel frontal etiquetado “RMT GEN START” para
encender/apagar el mecanismo de encendido del generador con el cable suministrado por el usuario
(ver Diagrama de Configuración de Terminales). Una vez instalada, la interfaz permitirá que el
Inversor/Cargador encienda automáticamente un generador separado cuando los niveles de voltaje
de la batereía estén bajos y lo apague cuando los niveles de voltaje de la batería estén altos.
Nota: Las operaciones siguientes se aplican únicamente al APSX6048VRNET.
Conecte el Módulo de Administración SNMP/Web Externo —OPCIONAL
(Para el accesorio módulo de administración SNMP/Web externo opcional, póngase en contacto con Tripp Lite).
El módulo de administración SNMP/Web (Tripp Lite modelo SNMPWEBSOLOHV) permite al usuario monitorear y controlar en forma remota
al inversor/cargador. Usando el cable serial estándar, suministrado, con el SNMPWEBSOLOHV, conecte un extremo al puerto de accesorios
etiquetado “UPS/APS” en el SNMPWEBSOLOHV y el otro extremo al puerto serial DB9 localizado en el panel frontal del Inversor/Cargador.
Conecte el Conector de Energía de 12V CD —OPCIONAL
El conector de energía de CD permite energizar al SNMPWEBSOLOHV directamente desde el Inversor/Cargador, eliminando la necesidad
de un tomacorrientes de CA. Conecte un extremo del cable (incluido con el SNMPWEBSOLOHV) al puerto etiquetado “DC Power” en el
SNMPWEBSOLOHV y conecte el otro extremo directamente en el Inversor/Cargador.
AGM/Celda
de Gel
Celda
Húmeda
20
Selección de la Batería
Selección del Tipo de Batería
Seleccione baterías de “Ciclo Profundo” para disfrutar un rendimiento óptimo de su Inversor/Cargador.Son ideales baterías de construcción
de celda húmeda (ventiladas) o de celdas de gel/AGM (selladas).También son aceptables baterías de 6 volts para carros de golf, de ciclo
profundo marinas o de ciclo profundo 8D.Debe colocar el interruptor DIP de Tipo de Batería del Inversor/Cargador (para más información,
consulte la sección de Configuración) para coincidir con el tipo de baterías que conecte o sus baterías se degradarán o dañarán después
de un período de tiempo.
Haga Coincidir la Capacidad en Amp-Hora de la Batería con su Aplicación
Seleccione una batería o sistema de baterías que alimente a su Inversor/Cargador con el voltajeCD adecuado y la capacidad amp-
hora apropiada para alimentar su aplicación.Aunque los Inversores/Cargadores son altamente eficientes en la inversión de DC a CA
,sus capacidades nominales de salida están limitadas por la capacidad amp-hora total de las baterías conectadas más la salida de un
alternador cuando se use alguno..
• Paso 1) Determine la Potencia Total Requerida
Sume las especificaciones de potencia del equipo que conectará
a su Inversor/Cargador.La especificación de potencia en Watts
está anotada normalmente en los manuales del equipo o en
las placas de identificación.Si su equipo está especificado
en amperes, multiplique por el voltaje CA para estimar watts.
(Ejemplo:un taladro requiere 2.8 amperes.2.8 amps × 230 volts
= 640 watts.)
Nota: Su Inversor/Cargador funcionará a mayores eficiencias alrededor
del 75% - 80% de la especificación de placa.
• PASO 2) Determine los Amperes CD de Batería Requeridos
Divida la potencia total requerida (del paso 1, arriba) entre el
voltaje nominal de la batería para determinar los amperes CD
requeridos.
• PASO 3) Estime los Amp-Hora de la Batería Requeridos
Multiplique los amperes CD requeridos (del paso 2, arriba) por
el número de horas que estima operar su equipo exclusivamente
desde la batería antes de tener que recargarla con energía de
CA de la red o generador. Compense la eficiencia multiplicando
este número por 1.2. Esto le dará un estimado aproximado de
cuantos amp-hora de energía de la batería (de una o varias
baterías) debe conectar a su Inversor/Cargador.
Nota: Las especificaciones de amp-hora de la batería están dados
normalmente para una tasa de descarga de 20 horas.Las capacidades
reales en amp-hora son inferiores cuando las baterías se descargan a
tasas más rápidas.Por ejemplo, baterías descargadas en 55 minutos
proporcionan sólo 50% de su especificación en amp-hora, mientras que
baterías descargadas en 9 minutos proporcionan únicamente 30% de su
especificación en amp-hora.
• PASO 4) Recarga Requerida Estimada para la Batería,
Dada su Aplicación
Debe permitir que sus baterías se recarguen lo suficiente para
reponer la carga perdida durante la operación del inversor o
eventualmente agotará sus baterías.Para estimar el tiempo
mínimo necesario para recargar sus baterías en función de su
aplicación, divida los amp-hora de su batería (del paso 3, arriba)
entre los amperes de de carga especificados de su Inversor/
Cargador (23A ó 90A, dependiendo de la posición del interruptor
#5).
Ejemplo
Herramientas
Taladro de (1/2”) 13mm Sierra Circular
640W + 800W = 1440W
Aparatos y Equipos Electrónicos
Computadora
de Escritorio
Ventilador Torre con Monitor
Refrigerador de Mesa Retransmisora LCD Grande
540W + 150W + 500W + 250W = 1440W
1440 watts ÷ 48V = 30 Amps CD
30 Amps CD × 5 Hrs. De Respaldo
× 1.2 Tasa de Ineficiencia = 180 Amp-Hora
180Amp-Hora ÷ 23 Amperes Especificados
del Inversor/Cargador = 7.8 Horas de Recarga
/