Tripp Lite BP480V370, BP480V370NB Инструкция по применению

Тип
Инструкция по применению
1
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved.
Owner’s Manual
Extended-Run Battery Cabinet
Models: BP480V370, BP480V370NB
Not suitable for mobile applications.
2
Table of Contents
1. Introduction
1. Introduction 2
Features 2
2. Important Safety Instructions 3
Installation and Location Warnings 3
Connection Warnings 3
Battery Warnings 4
3. Battery Cabinet Installation 4
3.1 Preparation 4
3.2 Transportation 5
3.3 Mechanical Check 5
3.4 Internal Wiring (Typical) 5
3.5 Preliminary Electrical Check 5
(After Battery Installation)
3.6 Battery Cabinet Placement 5
3.7 Electrical Connection 6
3.8 Final Electrical Check 6
4. Operation and Charging 7
4.1 Determine Charging Voltages 7
4.2 Initial Charge 7
4.3 Operational Check 7
5. Maintenance 7
5.1 Maintenance Schedule 7
5.1.1 Quarterly Check 7
6. Mechanical Data 8
6.1 Physical Measurements 8
6.2 Battery Requirements 9
7. Installation 10
7.1 Battery Pre-Installation 10
7.2 Cable Jumpers and Internal Wiring 11
7.2.1 Included Cable Jumpers Specifications 11
7.2.2 Battery Cabinet Internal Wiring 12
7.2.3 Battery Cabinet Parallel Installation 13
7.3 Battery Installation 14
7.4 Installation Specifications 23
7.4.1 Installation and Floor Loading Information 23
7.4.2 Recommended Torque 23
8. Storage and Service 23
9. Warranty and Product Registration 24
Español 25
Русский 49
Tripp Lite’s Extended-Run Battery Cabinets connect to SmartOnline® UPS Systems to provide long-lasting battery backup for data centers,
telecommunications, networks, industrial facilities, security, emergency systems and other mission-critical applications that require high
capacity, high availability and extended runtime.
Features
• Battery cabinets are available in two options: BP480V370 and BP480V370NB. The BP480V370 model includes jumpers, terminals,
breaker, and 40 x of CSB GPL 121000 batteries in a separate pallet for a complete installation. The BP480V370NB model is a similar kit
but without batteries, allowing users the flexibility to purchase batteries for the cabinet separately.
Battery cabinets are available in voltages of 480V DC and capacities option of 100Ah @ C20 to 1.67VPC.
Battery cabinets contain multiple 12V DC batteries connected in series for higher voltages. Up to 3 battery cabinets may be connected in
parallel for increased runtime.
Each battery cabinet contains 6 shelves with 5, 6, or 7 individual batteries (maximum) per shelf.
Hinged lockable door facilitates access to batteries for periodic maintenance.
A minimum of 130 mm clearance is located above the individual batteries for access to terminals.
Battery cabinet is constructed of heavy gauge steel.
Baked powder coat finish provides chip and corrosion resistance.
Battery cabinet ships bolted to pallet with a double layer of protective stretch wrap and integrated corner and top protection.
Appropriate ventilation and convection cooling of individual batteries is provided via spacing between batteries. Front and rear vents allow
the free flow of warmer air out of the battery cabinet.
A molded case circuit breaker is provided for overcurrent protection.
User-supplied power output cables can be fed into the battery cabinet via built-in conduit knockouts on top of the cabinet.
For improved safety, higher power density and minimized maintenance, the cabinet systems use Valve-Regulated Lead-Acid (VRLA)
recombinant batteries. The electrolyte in these batteries is immobilized in either an absorbent mat separator or a gelling medium,
eliminating the spilling hazards and maintenance requirements of free liquid electrolyte. There is no need to add water or measure specific
gravity.
Because the batteries are recombinant cells that employ an oxygen recombination cycle, minimal gasses are emitted during normal float
charging. Each cell contains an individual valve, which releases the gas products from overcharge and prevents pressure build-up within
the cell.
3
2. Important Safety Instructions
SAVE THESE INSTRUCTIONS
All sections of this manual contain instructions and warnings that must be followed during the installation and operation of the
battery cabinet described in this manual. Read ALL instructions thoroughly before attempting to move, install or connect your
battery cabinet.
Failure to heed these warnings may affect your warranty and cause serious property damage and/or personal injury.
DANGER! LETHAL HIGH VOLTAGE HAZARD!
All wiring should be performed by a qualified electrician in accordance with the warnings in this manual and all
applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property damage.
Installation and Location Warnings
Install the battery cabinet in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and gasses,
conductive contaminants, dust and direct sunlight.
Install the battery cabinet in a level, structurally sound location.
The battery cabinet is extremely heavy. Exercise caution when moving or lifting the unit.
Operate the battery cabinet at indoor temperatures between 0° C and 40° C only. For best results, maintain an ambient indoor
temperature of 25° C.
Allow adequate space around the front and rear of the battery cabinet for proper ventilation. Do not block, cover or insert objects into the
battery cabinet’s external ventilation openings.
Do not place any object on the battery cabinet, especially containers of liquid.
Do not attempt to stack the battery cabinet. Attempting to stack the battery cabinet may cause permanent damage and create a potential
for serious personal injury.
Do not attempt to unpack or move the battery cabinet without assistance. Use appropriate handling equipment rated to bear the weight
and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under load. Spread forks to
maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.)
For emergency use, install a fire extinguisher rated for energized electrical equipment fires (Class C rating or exact equivalent, with a non-
conductive extinguishing agent) near the battery cabinet.
Connection Warnings
The battery cabinet contains hazardous high voltages that have the potential to cause personal injury or death from electric shock.
The battery cabinet has its own energy source. The output terminals may be live, even when the battery cabinet is not connected to a UPS
system.
The battery cabinet must be suitably grounded according to all applicable electrical wiring regulations.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the
life support equipment or to significantly affect its safety or effectiveness is not recommended.
De-energize all input and output power sources before installing cables or making electrical connections.
Use flexible cable of sufficient length to permit battery cabinet servicing.
Use ferrule caps to cover termination cables and prevent frayed ends from shorting on terminal blocks. Use cabling rated VW-1, FT-1 or
better. Use cable sleeves and connector clamps.
Confirm all cables are marked correctly according to their purpose, polarity and diameter.
Observe proper polarity by following the positive and negative markings on the unit. Failure to observe proper polarity may damage the
batteries and create a serious risk of personal injury and property damage.
Wiring and assembly should be performed by trained, qualified electricians only. Refer to the UPS unit’s Owner’s Manual for wire sizing.
4
2. Important Safety Instructions
Battery Warnings
The battery cabinet does not require routine maintenance by the user. There are no user-serviceable parts inside. Only qualified,
knowledgeable service personnel familiar with all required precautions should open the access panels for any reason. Keep unauthorized
personnel away from batteries.
The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries. Do not attempt to add water to these batteries or
sample the electrolyte specific gravity.
VRLA batteries can contain an explosive mixture of hydrogen gas. DO NOT SMOKE when near batteries. DO NOT cause flames or sparks
near batteries. Discharge static electricity from body before touching batteries. DO NOT open or mutilate batteries—released electrolyte is
harmful to the skin and eyes and may be toxic. DO NOT dispose of batteries in a fire—they may explode.
Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be
performed only by qualified service personnel observing proper precautions. Use tools with insulated handles. Remove watches, rings or
other metal objects. Wear rubber gloves and boots. Do not short or bridge the battery terminals with any object. Do not lay tools or metal
parts on top of batteries.
Replace batteries with equivalent batteries (same number and type) available from Tripp Lite.
The batteries are recyclable. Refer to local codes for disposal requirements. Do not dispose of batteries except through approved channels
in accordance with all applicable local, state and national regulations.
Do not connect or disconnect batteries when the UPS system is operating from the battery supply or when the unit is not in bypass mode.
Disconnect the charging source prior to connection or disconnecting battery terminals.
If the charging source remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The
charging source should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months.
Failure to recharge the batteries periodically may cause permanent battery damage.
Allow batteries to charge uninterrupted for 24 hours after installation.
Do not attempt to service the integrated battery charger (included with “C” models only). Contact Tripp Lite if service is
required.
Note on Labeling
These symbols may appear on the product label:
V~: AC Voltage
V : DC Voltage
: Ground
+: Battery Positive
–: Battery Negative
Refer to the product label for model numbers, voltage ratings and other important information.
3. Battery Cabinet Installation
Read Section 2 – Important Safety Instructions Before Installation
3.1 Preparation
At your site, prepare to off-load the battery cabinet from the delivery truck and transport it to the final installation location. Consider both
the packaged weight and dimensions.
Make sure the floor can support the load of the specific battery cabinet being installed. The battery cabinet must be installed in a
structurally sound area with a level floor that is able to bear the weight of the battery cabinet and other equipment that will be installed
nearby.
Draw a wiring schematic representing the cables connected between the battery cabinet’s output terminal blocks and any external
disconnect device, junction box and/or load/rectifier.
If you plan to store the battery cabinet for an extended period before or after installation, follow the instructions in Section 8. Storage
and Service.
5
3. Battery Cabinet Installation
3.2 Transportation
1. Inspect the shipping container(s) for visible damage (do not remove the stretch wrap around the unit until it has been transported to
the final installation location). Confirm that the model name and rating match the unit you ordered. If you determine the unit has been
damaged during shipping or if anything appears to be missing, contact Tripp Lite for assistance. Do not attempt to use the unit if it has
been damaged or mishandled.
2. Do not attempt to move or unpack the battery cabinet without assistance. Use appropriate handling equipment rated to bear the weight
and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under load. Spread forks to
maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.) Confirm load limits for freight elevators, handling
equipment and floors along the transport route are not exceed by the combined weight of the packaged battery cabinet, handling
equipment and personnel. Confirm that the packaged unit will pass through any doorways along the intended route.
3. The battery cabinet is secured with stretch wrap to protect it during shipping and movement within a facility. Remove the stretch wrap
from the battery cabinet when the unit is in the final installation location—not before.
3.3 Mechanical Check
While the assembled cabinet battery system is still on the shipping pallet, inspect all sides for impact or other damage.
1. Open the front door of the battery cabinet.
2. Confirm none of the individual batteries included on a separate pallet are damaged (applies to BP480V370 model only).
3. Confirm that none of the internal parts (terminal blocks, circuit breakers and other parts) have been damaged.
4. Note the individual battery model number. Refer to Section 6.2 for the battery’s terminal type and recommended torque.
5. Use insulated tools to tighten all battery terminal connections to the recommended torque.
6. Use insulated tools to tighten the cables from the positive and negative output terminals at the end batteries to the circuit breaker.
3.4 Internal Wiring (Typical)
Battery cabinets use multiple 12V DC batteries connected in series to provide nominal DC voltage of 480V DC (±240V DC).
Internal cabling is sized for specific application load currents. Do not use any other cable size other than the one provided in the battery
cabinet.
Each battery cabinet shelf includes a specific wiring diagram.
All circuit breakers are in the middle tier of the battery cabinet.
All load connection polarities will be marked by a POS (+) or NEG (-) label (or an “N” center label for ±240V DC strings).
All battery cabinets are provided with a branch circuit overcurrent protection device and may be wired directly to the load or UPS.
3.5 Preliminary Electrical Check (After Battery Installation)
1. Reset the circuit breaker to the “On” position and measure the battery cabinet output voltage at the output load connection points.
Measure voltage with a digital voltmeter.
2. The measured voltage should approximately match the voltage listed on the battery cabinet nameplate. The battery cabinet output
voltage will be equal to the number of individual batteries installed in series multiplied by the unit voltage. For example: 40 batteries x
12.84V DC = 513.6V DC output.
3. If the measured voltage is significantly different than anticipated, determine the cause (e.g. low charge, shorted cell, reversed battery,
faulty wiring) and correct the voltage disparity before proceeding.
4. Set the circuit breaker to the “off” position as a safety precaution during installation.
3.6 Battery Cabinet Placement
Place the battery cabinet in a cool location with free airflow and away from direct heat sources. The lifespan and performance of a battery
may be dramatically affected by elevated temperature, decreasing 50% for each 8.25° C above 25° C.
1. Prepare the surface where the cabinet will be placed. The surface must be clean, flat and able to support the battery cabinet and other
equipment installed nearby. See Section 7.4 for floor loading specifications.
2. Allow adequate clearance around the front and rear of the battery cabinet for ventilation and maintenance. The front door must be
accessible to allow easy access to internal batteries, internal fuses and other overcurrent protection devices. See Section 6.1 for
dimensions and battery cabinet measurements.
3. If the cabinet will be anchored to the floor, install appropriate anchor bolts in the mounting hole located at the bottom of the cabinet. Use
washers to create a level surface between the mounting areas around the anchor bolts.
4. Using extreme caution, remove the bolts securing the battery cabinet to the shipping pallet.
6
3. Battery Cabinet Installation
5. Forklift forks should be at maximum width within the cabinet clearance opening and fully inserted to prevent tipping. Lift cabinet from
bottom only. Be careful not to damage the sheet metal floor of the cabinet with the forks.
6. If the battery cabinet will be secured to the floor, carefully align and lower the battery cabinet down on the floor anchor bolts and secure
it in place.
7. If the cabinet will not be secured to the floor, lower it into the designated space and then level it using shims. Leveling does not affect
performance, but does align the battery cabinet with other equipment in the facility.
3.7 Electrical Connection
DANGER! LETHAL HIGH VOLTAGE HAZARD!
All wiring should be performed by a qualified electrician in accordance with the warnings in this manual and all
applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property damage.
The battery cabinet is connected to the load through a DC circuit breaker. This allows the battery to disconnect from the load and charger
for maintenance and/or repair.
The DC molded case circuit breakers are CE approved for branch circuit protection. If replacement is required, CE approved components
with the same voltage and current rating must be used.
The size of the load connection cables must consider maximum allowable voltage drop as well as the cables’ continuous ampere capacity
and anticipated ampere discharge rate of the individual battery cabinet. A maximum voltage drop of 1.5V DC in the load connection
cables is recommended. Refer to the UPS unit’s Owner’s Manual for recommended wire sizes.
Refer to all applicable local, state and national codes for appropriate cable size and ratings.
External circuit protection devices (fuses or circuit breakers) must consider the discharge rate of the battery, the wiring to be protected and
the DC short circuit current of the battery.
After performing the installation procedures in Section 7.:
1. Open the front door of the battery cabinet to access internal components. Use a digital voltmeter when voltage measurements are
required.
2. Determine if the battery has been inadvertently grounded by resetting the circuit breaker to the “On” position and measuring the voltage
between the battery cabinet grounding lug and the positive load connection point within the cabinet. This voltage should measure
0 (zero) VDC. If the measured voltage is not zero, determine the cause and correct before proceeding.
3. Return the internal circuit breaker to an open “Off” position as a safety precaution while connecting the output cables. Doing so prevents
damage in the event the cables are accidentally shorted.
4. The top of the battery cabinet includes knockouts for load connection cable entry. Punch out the appropriate knockout and connect the
conduit or cable bushing.
5. The output circuit breaker accommodates cables up to 300 mm
2
.
6. Connect an appropriate equipment grounding cable to the grounding lug located on the top of the battery cabinet.
7. Feed the positive and negative cables (and “N” center, if equipped) from the open external disconnect switch or the UPS battery field
wiring terminals through the conduit/cable bushing. Connect to the respective output terminals inside the battery cabinet.
3.8 Final Electrical Check
Before closing any connecting circuit breaker or disconnect switch, complete these verification steps:
1. Verify the battery cabinet output voltage is correct.
2. If battery cabinets will be operated in parallel, verify that the individual system output voltages match within 2V DC.
3. Verify the voltage measured between either output terminal and the battery cabinet ground is zero.
4. If any of the above verification steps show an irregularity, determine and correct the cause before proceeding.
5. Reset the circuit breaker to the “On” position.
7
4. Operation and Charging
4.1 Determine Charging Voltages
To determine the appropriate equalization (freshening) charge voltage and float charge voltage, multiply the number of batteries connected in
series in the battery cabinet by the recommended charging voltage per unit.
For example:
A +/- 240V DC cabinet containing 40 CSB GPL12100* batteries in series would use the following charging voltages:
Float Charge Voltage = 20 x (13.5 to 13.8V DC/unit average) = +/- 270 to 276V DC
4.2 Initial Charge
After the correct charging voltages have been calculated, follow these steps:
1. Adjust the charger/rectifier equalization and float voltage outputs to the appropriate level.
2. Place the charger/rectifier in equalization mode. Tripp Lite SmartOnline UPS units adjust the charging voltage level automatically based on
present battery voltage.
3. Close the disconnect switch/circuit breaker connection from the charger/rectifier to the battery cabinet(s) and start a 24-hour freshening
charge at the equalization charge.
4. After a few minutes on charge, monitor the voltage across several of the individual batteries to assure they are charging at the proper
value.
5. Following completion of the freshening charge, place the charger/rectifier in float charge mode. Tripp Lite SmartOnline UPS units adjust
the charging voltage level automatically based on the status of the battery voltage.
6. After the battery cabinet has been on float for an additional 1 to 24 hours, complete the operational check (see Section 4.3 below).
4.3 Operational Check
1. Measure and record the total system float voltage. Measure at the battery terminals.
2. Measure and record the system float current using a clamp-on ammeter.
3. Measure and record the float voltage of individual battery units.
4. Measure and record the temperature of several batteries. Measure battery temperature with a digital thermometer by placing the surface
thermocouple on the flat surface of the negative terminal—not the “L” connection surface. An infrared temperature monitor may also be
used.
5. Optional: Perform impedance and conductance tests on individual battery units. These tests require special equipment, but the data can
be useful in trending the system over time or identifying suspect units during later periodic checks. It may be necessary to disconnect the
battery system from the charger/load during these checks.
5. Maintenance
The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries, which are maintenance-free relative to the electrolyte.
You cannot add water to these batteries or sample the electrolyte specific gravity. It is necessary, however, to periodically check the charging
voltage, temperature and connections of the individual battery units.
5.1 Maintenance Schedule
5.1.1 Quarterly Check
Quarterly maintenance by qualified service personnel is recommended.
8
6. Mechanical Data
6.1 Physical Measurements
Dimensions (H x W x D): 2005 x 647 x 1100 mm
Empty Cabinet Weight: 487 lb. / 221 kg
TOP VIEW
FRONT VIEW
W D
H
SIDE VIEW REAR VIEW
9
6.2 Battery Requirements
Lead-Acid Cell Type and Quantity: 12V 100Ah x 40 Batteries
Lead-Acid Battery Maximum Size (H x W x D): 224 x 173 x 343 mm
Terminal Type: M6 Bolt
Terminal Torque (applies to CSB GPL 121000 model): 138.6 kgf•cm/13.58 N•m
6. Mechanical Data
W
D
H
TOP VIEW
FRONT VIEW SIDE VIEW REAR VIEW
CIRCUIT
BREAKER
D
W
H
10
7. Installation
7.1 Battery Pre-Installation
Battery cabinet:
The “F” marks the front side of the battery cabinet; the “R” marks the rear side of battery cabinet.
Battery shelf structure:
The cabinet includes 6 shelves total from L1 (bottom) to L6 (top).
F
R
L6
L5
L4
L3
L2
L1
Battery installation should only be performed by qualified service personnel.
11
7.2 Cable Jumpers and Internal Wiring
7.2.1 Included Cable Jumpers Specifications
1/0 AWG double wire
ITEM DESCRIPTION UNIT CABLE LENGTH (mm) QUANTITY CABLE NUMBER
A UL 1015#11/0AWG BLACK mm 250 28
1
A UL 1015#11/0AWG BLACK mm 300 6
2
A UL 1015#11/0AWG BLACK mm 550 3
3
A UL 1015#11/0AWG BLACK mm 850 1
4
A UL 1015#11/0AWG BLACK mm 550 1 N
A UL 1015#11/0AWG BLACK mm 800 1 N
A UL 1015#11/0AWG BLACK mm 1250 1 BAT+
A UL 1015#11/0AWG BLACK mm 1200 1 BAT-
B L/W PVC UL1015 TS #1/0 BLK PCS 84
Distance between battery shelves
645 mm
545 mm
61 mm
78 mm
2005 mm
78 mm
78 mm
78 mm
78 mm
7. Installation
L(mm)
B
B
A
12
7. Installation
7.2.2 Battery Cabinet Internal Wiring
Wiring to UPS
BAT
Breaker on
battery cabinet
(Rated for
400A,
600V DC)
L3
L6
L2
L1
L5
L4
F
R
13
7. Installation
7.2.3 Battery Cabinet Parallel Installation
L1
L2
L3
L4
L5
L6
Breaker on
battery cabinet
TO UPS
2
2
2
2
2
2
4
3
3
3
F
R
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1
1
1
1
1
1
1
1
1
L1
L2
L3
L4
L5
L6
Breaker on
battery cabinet
2
2
2
2
2
2
4
3
3
3
F
R
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1
1
1
1
1
1
1
1
1
-
N
+
-
N
+
TO UPS
R
L3
L3
L6 L6
L2
L2
L5 L5
L1
L1
L4
L4
F
R
F
Breaker
on battery
cabinet
Breaker
on battery
cabinet
BAT
14
7. Installation
7.3 Battery Installation
1. Pull out the latch from the front door hinge. Remove door.
2. Unscrew the M4 screws (12 pcs.) with a Phillips screwdriver and remove the side panels.
15
7. Installation
3. Unscrew the M6 screws (4 pcs.) from each battery tray. Remove all the battery trays from cabinet.
4. Battery installation in the battery cabinet will start from the bottom (L1) and end at the top (L6). See below right figure for internal wiring
“L1”. Reference the table and diagrams in Sections 7.1.1 and 7.2.2 for the appropriate wire jumper needed.
F
R
L1
BAT-
L2
16
5. Use the saved M6 screws to secure the battery tray for L2.
6. See the below right diagram for internal wiring “L2”. Reference the table and diagrams in Sections 7.1.1 and 7.2.2 for the appropriate
wire jumper needed.
7. Installation
F
R
L2
L3
L1
17
7. Installation
7. Use the saved M6 screws to secure the next battery tray for L3.
8. See the below right diagram for internal wiring “L3”. Reference the table and diagrams in Sections 7.1.1 and 7.2.2 for the appropriate
wire jumper needed.
L3
F
R
L2
N
18
7. Installation
9. Use the saved M6 screws to secure the next battery tray for L4.
10. See the below right diagram for internal wiring “L4”. Reference the table and diagrams in Sections 7.1.1 and 7.2.2 for the appropriate
wire jumper needed.
L4
F
R
L5
N
19
7. Installation
11. Use the saved M6 screws to secure the next battery tray for L5.
12. See the below right diagram for internal wiring “L5”. Reference the table and diagrams in Sections 7.1.1 and 7.2.2 for the appropriate
wire jumper needed.
F
R
L5
L4
L6
20
7. Installation
13. Use the saved M6 screws to secure the next battery tray for L6.
14. Remove the M4 screws (4 pcs.) from cabinet top cover and remove.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Tripp Lite BP480V370, BP480V370NB Инструкция по применению

Тип
Инструкция по применению

Задайте вопрос, и я найду ответ в документе

Поиск информации в документе стал проще с помощью ИИ

на других языках