7. Technical data
7.1 Electrical data
7.2 Temperatures
7.3 Miscellaneous
Conversion of SI units into US units, see page 13.
8. Service
If the sensor is defective, replace the sensor.
9. Disposal
This product or parts of it must be disposed of in an environmentally sound
way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service
workshop.
Voltage supply to the sensor:
PELV (protective extra low voltage)
(EN 60335-1)
12 - 30 VDC
Load: 24 V: max. 500 ohm
16 V: max. 200 ohm
12 V: max. 100 ohm
Output signal, 3-wire: 4 - 20 mA
Enclosure class: IP 55 (according to EN 60529)
Temperature at sensor: –10 °C to +70 °C
temporarily (max. 10 min.) up to 80 °C
Ambient temperature: –10 °C to +70 °C
Storage temperature: –40 °C to +80 °C
Cable length: 0.9 m
Cable length for DPI kit 2: 5 m
Max. air humidity: 95 %
Pressure range DPI: 0.... 0.6, 1.0, 1.6, 2.5, 4.0, 6.0, 10 bar
Pressure range DPI kit 2: 0.... 1.2, 2.5, 4.0, 6.0, 10 bar