www.sentera.eu
MIW-AH2C1-6-RU-000 - 01 / 07 / 2019 11 - 12
обратно к содержанию
ТАБЛИЦЫ РЕГИСТРОВ MODBUS
Input registers
Data type Description Data Values
1Actual Temperature Level signed int Actual temperature. 200 = 20.0°C
2Current Output Duty Cycle signed int Current output in % 0-100 100 = 100%
3Selected Setpoint signed int Current setpoint in °C 50-300 300 = 30.0°C, 5—30°C
4–9 Reserved. Return 0.
10 Setpoint Source Selected
(Ext.SP / Int.SP) unsigned int Shows which setpoint is used - external by analogue input or internal
by trimmer or Modbus register 0,1 0 - External; 1 - Internal
11 Working Mode (Slave/Master) unsigned int Shows how the controller is working: as a Master providing analogue
output for a Slave device or as a Slave when the output in % repeats
the analogue input 0,1 0 - Slave; 1 - Master
12 Day / Night Mode unsigned int Shows which setpoint is active: selected by NO switch 0,1 0 - Day; 1 - Night
13 Remote Off Contact unsigned int Shows if the device is in remote off: selected by NC switch 0,1 0 - On, 1 = Standby.
14 Control Board Problem Shows if there is problem with the communication with the control
board 0,1 0 - OK,1 - Problem.
15–18 Reserved. Return 0.
Holding registers
Data type Description Data Values
1Device Slave Address unsigned int Device address. 1—247, default:1
2Baud rate unsigned int Modbus communication baud rate. 1—4, default: 2 1 = 9600, 2 = 19200, 3 = 38400,
4 = 57600
3Parity mode unsigned int Parity check mode. 0—2, default:1 0=8N1, 1=8E1, 2=8O1
4Device Type unsigned int Device Type: Read Only 6000, 6001 6000 = AH2C1-6, 6001 = AH2C1-
6-500,
5HW Version unsigned int Hardware Version. Read only XX.XX 0x0110 = HW version 1.10
6SW version unsigned int Software Version. Read only XX.XX 0x0120 = SW version 1.20
7Operating mode unsigned int Enables the Modbus control and disables the jumpers and trimmers. 0-1 0 = Standalone mode, 1 = Modbus
mode.
8Output Override unsigned int Enables the direct control over the outputs. Always settable. Active
only if holding register 7 is set to 1. 0-1 0 = Disabled, 1 = Enabled, default:
0.
9–10 Reserved. Return 0.
11 Day Setpoint Selection unsigned int Day setpoint 50—300, Default
250 300 = 30.0°C, 5—30°C
12 Night Setpoint Selection unsigned int Day setpoint 50—300, Default
180 300 = 30.0°C, 5—30°C
13 Working Mode unsigned int Slave or master in Modbus mode 0—1 Default 1; 0 - Slave, 1 - Master,
14 Setpoint Source Selection unsigned int External or Internal (Modbus) setpoint 0—1 Default 1; 0 = External setpoint, 1 = Internal
setpoint
15 Triac Control PWM Output
Period unsigned int PWM period time 1—60 default 30. 60 = 60sec.
16 Calibration at 10°C unsigned int Register containing the calibration value for 10°C. Write 1 to
perform calibration. 0—1023; Default
210
17 Calibration at 30°C unsigned int Register containing the calibration value for 30°C. Write 1 to
perform calibration. 0—1023, Default
490
18 Disable Remote Off. unsigned int Disables/enables the Remote Off Contact (CC) 0, 1, default:1. 0 - Disabled, 1 - Enabled.
19–20 Reserved. Return 0.
21 Override Output Value signed int Override output value in %(only active if registers 7 and 8 are
set) 0—100; default 0. 100 = 100%
22–30 Reserved. Return 0.
Для получения дополнительной информации о протоколе обмена данных Modbus, посетите: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
Параметры устройства могут быть настроены при помощи программы
3SModbus. Вы можете скачать ее с веб-сайта Sentera. В карте Modbus есть два
типа регистров:
РЕГИСТРЫ ВВОДА (см. Таблица Входные регистры ниже )
Входные регистры только для чтения. Вся информация доступна при помощи
функции «Чтение входных регистров». Таблица входные регистры показывают
возвращаемый тип данных и способ их интерпретации.
Регистры хранение (см. Таблицу регистров хранения ниже)
Регистры хранения можно читать и записывать. Для этого доступные команды:
«Чтение регистров хранения», «Запись отдельного регистра» и «Запись
нескольких регистров». Регистры, которые не используются, доступны только
для чтения, и поэтому запись в этих регистрах не возвращает исключения
ошибки Modbus и не вносит никаких изменений.
AH2C1-6 РЕГУЛЯТОР ДЛЯ УПРАВЛЕНИЯ
ЭЛЕКТРОНАГРЕВАТЕЛЕМ