McQuay 5SL07C Инструкция по установке

Категория
Сплит-системы кондиционирования
Тип
Инструкция по установке
WALL MOUNTED
SPLIT TYPE AIR CONDITIONER
(G Series)
INSTALLATION MANUAL
Group: WALL MOUNTED
Part Number: A08019020381
Date: JANUARY 2004
IM-WMG-0104-McQuay
© 2004 McQuay International
i
All dimensions are in mm / (in)
Indoor Unit (MWMG Series)
OUTLINE AND DIMENSIONS
INSTALLATION
PLATE
Dimension A B C D E F G H I J K L M N O
07 / 09G / GR 799 260 198 490 246 185 124 8 56 50 319 379 50 128 132
(31,5) (10,2) (7,8) (19,3) (9,7) (7,3) (4,9) (0,3) (2,2) (2,0) (12,6) (15,0) (2,0) (5,1) (5,2)
10 / 15G / GR 899 260 198 590 246 185 124 8 56 50 419 495 50 128 132
(35,4) (10,2) (7,8) (23,2) (9,7) (7,3) (4,9) (0,3) (2,2) (2,0) (16,5) (19,5) (2,0) (5,1) (5,2)
A
B
FRONT VIEW
TOP VIEW
C
SIDE VIEW
D
F
G
E
H
O
N
I
I
J
K
L
M
ii
Indoor Unit (MWMG Series)
All dimensions are in mm / (in)
Dimension
20 / 25G / GR
I
48
(1,9)
H
8
(0,3)
G
51
(2,0)
F
99
(3,9)
E
294
(11,6)
D
912
(35,9)
C
220
(8,6)
B
310
(12,2)
A
1060
(41,7)
O
160
(6,3)
N
138
(5,4)
M
160
(6,3)
L
403
(15,9)
K
354
(13,9)
J
43
(1,7)
FRONT VIEW
TOP VIEW
SIDE VIEW
INSTALLATION
PLATE
A
B
C
A
B
D
F
G
M
H
I
I
O
N
M
K
L
J
CENTER LINE
iii
Outdoor Unit (MLC Series)
All dimensions are in mm / (in)
3
(0,1)
B
EF
NC N
KLL
M
30
(1,2)
A
D
19
(0,7)
C
GH
IJ
O
80
(3,1)
65
(2,6)
B
A
Q
R
ST
DO
KLL
CN
P
M
N
FE
C
GH
IJ
FOR SL25C/CR
ONLY
All dimensions are in mm / (in)
Dimension A B C D E F G H I J K L M N O
07 / 09C / CR 600 475 245 418 177 35 93 81 83 55 398 101 97 17 22
(23,6) (18,7) (9,6) (16,4) (6,9) (1,3) (3,6) (3,1) (3,2) (2,2) (15,6) (3,9) (3,8) (0,6) (0,8)
10 / 15C / CR 700 521 250 485 175 36 95 93 86 68 441 130 111 15 18
(27,5) (20,5) (9,8) (19,1) (6,8) (1,4) (3,7) (3,6) (3,3) (2,6) (17,3) (5,1) (4,3) (0,5) (0,7)
iv
Dimension A B C D E F G H I J K L M N O
20C / CR 855 628 328 508 181 44 93 149 101 113 603 126 164 17 49
(33,7) (24,7) (12,9) (20,0) (7,1) (1,7) (3,7) (5,9) (4,0) (4,4) (23,7) (5,0) (6,4) (0,7) (1,9)
25C / CR 855 730 328 513 182 44 93 149 101 113 603 126 164 17 47
(33,7) (28,7) (12,9) (20,2) (7,2) (1,7) (3,7) (5,9) (4,0) (4,4) (23,7) (5,0) (6,4) (0,7) (1,9)
Dimension P Q R S T
20C / CR 32 3 23 73 75
(1,3) (0,1) (0,9) (2,9) (3,0)
25C / CR 32 3 23 73 75
(1,3) (0,1) (0,9) (2,9) (3,0)
This product is subjected to Waste of Electrical and Electronic Equipment Regulations (WEE
E
Regulations). The waste product shall be separately collected by specific collection and treatment centre
.
P
lease refer to local authorithy for these centres. This is only applicable to European Union countries
.
Ce produit est soumis
à
la r
à
é
r
é
é
é
lectriques e
t
é
é
é
ê
é
é
é
é
é
é
é
é
é
î
î
tre ces centres. Ceci
îî
est uniquement applicable aux pays de l'Union Euro
p
é
enne
.
Questo prodotto
è
soggetto alle disposizioni RAEE (Rifiuti di apparecchiature elettriche ed elettroniche)
.
à
à
locali. Questa disposizione
à
è
valida solamente i paes
i
d
el
l
U.
E
.
é
ctrico y Electr
ó
n
ico en materia d
e
ñ
ñ
á
í
fico
íí
de colecc
i
ó
solamente aplicable a los p
a
í
ses de la
U
n
i
ó
n
Europea
.
Dieses Produkt unterliegt den Bestimmungen zur Entsorgung von elektrischen und elektronische
n
G
er
ä
ä
ä
tes
ä
ä
ü
ü
ll bei Ihrer
ö
ü
ö
ä
ndiges Abfall-Amt. Dieser
ää
Hinweis gilt nur f
ü
f
f
rL
ä
ischen Union
.
П
р
оцес
с
у
тилизаци
и
д
анног
о
прод
у
кт
а
рег
у
лир
у
етс
я
п
р
авилам
и
п
о
у
тилизаци
и
отхо
д
о
в
и
(WEEE Re
g
ulations).
и
,
.
Э
т
и
п
р
авил
а
Ев
р
опейског
о
.
NOTICE
1-1
English
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
INSTALLATION MANUAL
WALL MOUNTED SPLIT TYPE AIR CONDITIONER
MODEL
Part No.:A08019020381 IM-WMG-0104(1)-McQuay
COOLING ONLY
R22 / R407C
WM07G / MWM007G
SL07C / MLC007C
WM09G / MWM009G
SL09C / MLC009C
WM10G / MWM010G
SL10C / MLC010C
WM15G / MWM015G
SL15C / MLC015C
WM20G / MWM020G
SL20C / MLC020C
WM25G / MWM025G
SL25C / MLC025C
R410A
5WM07G / M5WM007G
5SL07C / M5LC007C
5WM09G / M5WM009G
5SL09C / M5LC009C
5WM10G / M5WM010G
5SL10C / M5LC010C
5WM15G / M5WM015G
5SL15C / M5LC015C
5WM20G / M5WM020G
5SL20C / M5LC020C
5WM25G / M5WM025G
5SL25C / M5LC025C
HEAT PUMP
R22 / R407C
WM07GR / MWM007GR
SL07CR / MLC007CR
WM09GR / MWM009GR
SL09CR / MLC009CR
WM10GR / MWM010GR
SL10CR / MLC010CR
WM15GR / MWM015GR
SL15CR / MLC015CR
WM20GR / MWM020GR
SL20CR / MLC020CR
WM25GR / MWM025GR
SL25CR / MLC025CR
R410A
5WM07GR / M5WM007GR
5SL07CR / M5LC007CR
5WM09GR / M5WM009GR
5SL09CR / M5LC009CR
5WM10GR / M5WM010GR
5SL10CR / M5LC010CR
5WM15GR / M5WM015GR
5SL15CR / M5LC015CR
5WM20GR / M5WM020GR
5SL20CR / M5LC020CR
5WM25GR / M5WM025GR
5SL25CR / M5LC025CR
1-2
CONTENTS
Before installing the air conditioner unit, please read the following safety precautions carefully.
SAFETY PRECAUTIONS
- Outline And Dimensions page i-iv
- Safety Precautions page 2
- Installation Diagram page 3
- Installation Of The Outdoor Unit page 3
- Installation Of The Indoor Unit page 4
- Refrigerant Piping page 5
- Electrical Wiring Connection page 6
- Special Precautions When Dealing
with R410A Unit page 7
- Vacuuming and Charging page 7
- Indicator Lights page 8
- Air Conditioner Unit Operation page 9
- Operating Range page 9
- Electrostatic Filter page 10
- Installation of Unit with O
2
Therapy Feature page 10
- Auto Random Re-Start Function page 11
- Service And Maintenance page 11
- Troubleshooting page 12
! Caution
Please take note of the following important points when installing.
Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates around the unit, it may cause fire ignition.
Ensure that the drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
Ensure that the units panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from
being in contact with these places.
! Warning
Installation and maintenance shall be performed by qualified persons who are familiar with local code and
regulation, and experienced with this type of appliance.
All field wiring must be installed in accordance with the national wiring regulation.
Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work
according to the wiring diagram.
The unit must be GROUNDED to prevent possible hazards due to insulation failure.
All electrical wiring must not touch the refrigerant piping, compressor or any moving parts of the fan motors.
Confirm that the unit has been switched OFF before installing or servicing the unit.
1-3
English
INSTALLATION DIAGRAM
Indoor Unit
Refrigerant Piping
Air Discharge
Nozzle
Air Intake
Drain Hose
Signal Receiver
Indicator
Lights
Air Intake
Grille
Back Housing
ON/OFF Switch
Front Frame
Air Filter
Outdoor Unit
Dimension A B C D
Minimum Distance, 300 1000 300 500
mm (in) (11.8) (39.4) (11.8) (19.7)
INSTALLATION OF THE OUTDOOR UNIT
The outdoor unit must be installed in such a way, so as to
prevent short circuit of the hot discharged air or obstruc-
tion to the smooth air flow. Please follow the installation
clearances shown in the figure. Select the coolest possible
place where intake air temperature is not greater than the
outside air temperature (maximum 45°C).
Installation clearances
Note: If there is any obstacle higher than 2m, or if there is
any obstruction at the upper part of the unit, please allow
more space than the figure indicated in the above table.
Condensed Water Disposal of Outdoor Unit
(Heat Pump Unit Only)
There are 2 holes on the base of Outdoor Unit for
condensed water to flow out. Insert the drain elbow to
one of the holes.
To install the drain elbow, first insert one portion of the
hook to the base (portion A), then pull the drain elbow
in the direction shown by the arrow while inserting the
other portion to the base. After installation, check to
ensure that the drain elbow clings to base firmly.
If the unit is installed in a snowy and chilly area, con-
densed water may freeze in the base. In such case,
please remove plug at the bottom of unit to smooth the
drainage.
Obstacle
Return Air
Service Access
Obstacle
Obstacle
Return Air
Discharge Air
Obstacle
Please remove side
plate when connect-
ing the piping and
connecting cord
PUSH & PULL UP
BASE
A
DRAIN
ELBOW
DRAIN
ELBOW
PLUG
A
B
C
D
1-4
INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed in such a way so as to
prevent short circuit of the cool discharged air with the hot
return air. Please follow the installation clearance shown in
the figure. Do not place the indoor unit where there could
be direct sunlight shining on it. Also, this location must be
suitable for piping and drainage, and be away from doors
or windows.
Routing Of Piping
Remove the screw holding the front panel.
Maintenance &
Servicing Space
Air Flow
Direction
Higher Than
Eye Level
The refrigerant piping can be routed to the unit in a
number of ways (left or right from the back of the unit), by
using the cut-out holes on the casing of the unit (see figure).
Bend the pipes carefully to the required position in order to
align it with the holes. For the right hand and rear side out,
hold the bottom of the piping and then position it to the
required direction (see figure). The condensation drain hose
can be taped to the pipes.
Correct
1
2
3
4
5
Piping Routing
Right & Rear Side Routing
Drain hose
Fix with vinyl tape
Unit piping
50.0 mm
50.0 mm
50.0 mm
Hole With Cone Drill
Indoor Side
Outdoor Side
Mounting Installation Plate
Ensure that the wall is strong enough to withstand the weight
of the unit. Otherwise, it is necessary to reinforce the wall
with plates, beams or pillars.
Use the level gauge for horizontal mounting, and fix it with
4 suitable screws.
In case the rear piping draws out, drill a hole 65mm in di-
ameter with a cone drill, slightly lower on the outside wall
(see figure).
Mount The Unit Onto The Installation Plate
Hook the indoor unit onto the upper portion of the
installation plate (Engage the two hooks at the rear top of
the indoor unit with the upper edge of the installation plate).
Ensure that the hooks are properly seated on the
installation plate by moving it to the left and right.
Water Drainage Piping
The indoor drain pipe must be in a downward gradient for
smooth drainage. Avoid situations that are likely to cause
water to leak.
End
Dipped
Into
Water
Water
Leaking
Water
Leaking
Water
Leaking
Wrong
Wrong
Wrong
Drain
Water Drainage
Screw position in the wall
Ø 65.0 mm Hole in the wall
1. Hook the unit onto the installation plate.
Screw position in the wall
72.0
Centre Line
Ø 65.0 mm Hole in the wall
1-5
English
Piping Length & Elevation
If the pipe is too long, both the capacity and reliability of
the unit will drop. As the number of bends increases,
resistance to the flow of refrigerant system increases, thus
lowering cooling capacity. As a result, the compressor may
become defective. Always choose the shortest path and
follow the recommendations as tabulated below:
REFRIGERANT PIPING
Outdoor Unit
Indoor Unit
Piping Works
Do not use contaminated or damaged copper tubing. Do
not remove plastic, rubber plugs and brass nuts from the
valves, fittings, tubings and coils until you are ready to
connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that the nitrogen
gas is passed through coil and joints while the brazing
work is being done. This will eliminate soot formation on
the inside walls of the copper tubings.
Cut the connection pipe with a pipe cutter.
Remove burrs from cut edges of the pipes with remover.
Hold the end of the pipe downwards to prevent metal chips
from entering the pipe.
Insert the flare nuts, mounted on the connection parts of
both the indoor unit and outdoor unit onto the copper pipes.
Flare the pipe with extra length above the flaring tool as
shown in the table.
The flared edge must be even and not cracked or scratched.
Ø Tube, D A (mm)
Inch mm Imperial Rigid
1/4" 6.35 1.3 0.7
3/8" 9.52 1.6 1.0
1/2" 12.70 1.9 1.3
5/8" 15.88 2.2 1.7
3/4" 19.05 2.5 2.0
Piping Connection To The Units
Align the center of the piping and tighten the flare nut
sufficiently with fingers.
Finally, tighten the flare nut with the torque wrench until
the wrench clicks.
Pipe Size mm / (in) Torque Nm / (ft - lb)
6.35 (1/4) 18 (13.3)
9.53 (3/8) 42 (31.0)
12.7 (1/2) 55 (40.6)
15.88 (5/8) 65 (48.0)
19.05 (3/4) 78 (57.6)
Indoor Piping
Flare Nut
Flared Tube
Flare Joint
Spanar
Torque Wrench
Remark: The refrigerant pre-charged in the outdoor unit
is for piping length up to 7.62 m/25 ft.
Model
Maximum length, m (ft), L
Max. elevation, m (ft), H
Max. number of (90º) bends
Liquid pipe size
Gas pipe size
07 09 10 15 20 25
12 (39) 12 (39) 12 (39) 12 (39) 15 (49) 15 (49)
5 (16.4) 5 (16.4) 5 (16.4) 5 (16.4) 8 (26.2) 8 (26.2)
10 10 10 10 10 10
1/4" 1/4" 1/4" 1/4" 1/4" 3/8"
3/8" 3/8" 3/8" 1/2" 5/8" 5/8"
Cutting Copper Tube
1/4t
Remove Burr
Copper Tube
Swaging Block
1-6
ELECTRICAL WIRING CONNECTION
Cooling unit
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of
installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit. ETL listed is only applicable
to 60Hz power supply only.
Model 07 / 09 / 10 / 15 20 / 25
Voltage range**
220V-240V / 1Ph / 50Hz +
!
or 208V-230V / 1Ph / 60Hz+
!
Power supply cable size* mm
2
1.5 2.5
Number of wire 33
Interconnection cable size* mm
2
1.5 2.5
Number of wire 33
Recommended Fuse A 15 20
Model 07 / 09 / 10 / 15 20 / 25
Voltage range**
220V-240V / 1Ph / 50Hz +
!
or 208V-230V / 1Ph / 60Hz+
!
Power supply cable size* mm
2
1.5 2.5
Number of wire 33
Interconnection cable size* mm
2
1.5 2.5
Number of wire 55
Recommended Fuse A 15 20
!
There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended in
the fixed installation circuit.
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
Power Supply Cable
Outdoor coil sensor connection wire
(8m long) attached in the indoor unit
COMP
N2
OF
4WV
N1
L
COMP
OF
4WV
N
Heat pump unit (single phase)
COMP
N2
COMP
N
N1
L
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended
in the fixed installation circuit.
!
Power Supply Cable
Cooling unit (single phase)
All wires must be firmly connected.
All wires must not touch the refrigerant piping, compressor
or any moving parts of the fan motor.
The connecting wires between the indoor unit and the
outdoor unit must be clamped on the wire clamps as shown
in the figure.
The power supply cord must be equivalent to H05RN-F
(245IEC57) which is the minimum requirement.
Wire Clamp
Interconnection
Cable
Power Supply
Cable
1-7
English
SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT
R410A is a new HFC refrigerant which does not damage the
ozone layer. The working pressure of this new refrigerant is
1.6 times higher than conventional refrigerant (R22), thus
proper installation / servicing is essential.
Never use refrigerant other than R410A in an air condi-
tioner which designed to operate with R410A.
POE oil is used as lubricant for R410A compressor, which
is different from the mineral oil used for R22 compres-
sor. During installation or servicing, extra precaution must
be taken not to expose the R410A system too long to moist
air. Residual POE oil in the piping and components can
absorb moisture from the air.
To prevent mischarging, the diameter of the service port
on the flare valve is different from that of R22.
Use tools and materials exclusively for refrigerant R410A.
Tools exclusively for R410A are manifold valve, charg-
ing hose, pressure gauge, gas leak detector, flare tools,
torque wrench, vacuum pump and refrigerant cylinder.
As an R410A air conditioner incurs higher pressure than
R22 units, it is essential to choose the copper pipes cor-
rectly. Never use copper pipes thinner than 0.8mm even
though they are available in the market.
If the refrigerant gas leakage occurs during installation /
servicing, be sure to ventilate fully. If the refrigerant gas
comes into contact with fire, a poisonous gas may occur.
When installing or removing an air conditioner, do not
allow air or moisture to remain in the refrigerant cycle.
VACUUMING AND CHARGING
Purging the piping and the indoor unit
Except for the outdoor unit which is pre-charged with
refrigerant, the indoor unit and the refrigerant
connection pipes must be air-purged because the air
containing moisture that remains in the refrigerant cycle may
cause malfunction of the compressor.
Remove the caps from the valve and the service port.
Connect the center of the charging gauge to the vacuum
pump.
Connect the charging gauge to the service port of the
3-way valve.
Start the vacuum pump. Evacuate for approximately
30 minutes. The evacuation time varies with different
vacuum pump capacity. Confirm that the charging gauge
needle has moved towards -760mmHg.
Caution
If the gauge needle does not move to -760mmHg, be sure
to check for gas leaks (using the refrigerant
detector) at flare type connection of the indoor and outdoor
unit and repair the leak before proceeding to the next step.
Close the valve of the charging gauge and stop the vacuum
pump.
On the outdoor unit, open the suction valve (3 way) and
liquid valve (2 way) (in anti-clockwise direction) with 4mm
key for hexagon sacked screw.
Service Port
Outdoor Unit 3 ways valve
Flare nut
Refrigerant Piping
Allen key
Suction
valve
Discharge
Valve
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Vacuum
pump
Open
Close
Close
Close
Hi
Low
Model
07 / 09 / 10 / 15G
07 / 09 / 10 / 15GR
20G
20GR
25G
25GR
10m/32.8ft 12m/39.4ft 15m/49.2ft
35 65
50 90
35 65 110
60 110 185
90 165 280
120 220 370
Additional charge in gram (For R22 models)
Model
07 / 09 / 10 / 15G
07 / 09 / 10 / 15GR
20G
20GR
25G
25GR
10m/32.8ft 12m/39.4ft 15m/49.2ft
35 60
45 80
35 60 100
55 100 165
80 150 255
110 200 335
Additional charge in gram (For R410A models)
Additional charge
The refrigerant is pre-charged in the outdoor unit. If the
piping length is less than 7.62m (25ft), then additional charge
after vacuuming is not necessary. If the piping length is more
than 7.62m (25ft), then use the additional charge valve as indi-
cated in the table.
Open
Open
Suction
Valve
Discharge Valve
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Check
Valve
Close
Hi
Low
Charge operation
This operation must be done by using a gas cylinder and a
precise weighing machine. The additional charge is topped-up
into the outdoor unit using the suction valve via the service
port.
Remove the service port cap.
Connect the low pressure side of the charging gauge to the
suction service port center of the cylinder tank and close
the high pressure side of the gauge. Purge the air from the
service hose.
Start the air conditioner unit.
Open the gas cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into the
unit, close the low pressure side and the gas cylinder valve.
Disconnect the service hose from service port. Put back the
service port cap.
1-8
IR signal receiver
When an infrared remote control operating signal has
been transmitted, the signal receiver on the indoor unit
will make a <beep> sound to confirm acceptance of the
signal transmission.
Cooling unit / Heat Pump unit
The table shows the LED indicator lights for the air condi-
tioner unit under normal operation and fault conditions.
The LED indicator lights are located at the middle of the air
conditioner unit.
The heat pump units are equipped with an “auto” mode
sensor whereby it will provide reasonable room temperature
by switching automatically to either “cool” or “heat”
mode according to the temperature set by the user.
INDICATOR LIGHTS
LED indicator lights
IR Receiver
LED Indicator Lights for Cooling Unit / Heat Pump
Unit
LED Indicator Lights : Normal Operation And Fault Conditions For Cooling / Heat Pump Unit
Normal Operation / Fault Indication Action
Cool mode
Heat mode
Auto mode in Heating operation
Auto mode in Cooling operation
Timer on
Sleep mode on
Ionizer on
Fan mode on
Dry mode on
Room air sensor contact
Loose / Short
Call your dealer
Outdoor coil sensor open Call your dealer
Indoor coil sensor open Call your dealer
Compressor overload /
Indoor coil sensor short / Call your dealer
outdoor coil sensor short
Defrost operation
Gas leak Call your dealer
Outdoor coil sensor exist (MS Model) Call your dealer
Hardware error (tact switch pin short) Call your dealer
6 times
1 time
COOL/HEAT
(GREEN/RED)
Red
Green
Red
Green
Red
ON
ON or OFF Blinking
1 time
3 times
3 times
Sleep Mode Cool Timer Ionizer
5 times
1-9
English
OPERATING RANGE
Heat Pump Unit
Cooling unit
Temperature Ts °C / °F Th °C / °F
Minimum indoor
19.0 / 66.2 14.0 / 57.2
temperature
Maximum indoor
32.0 / 89.6 23.0 / 73.4
temperature
Minimum outdoor
19.4 / 66.9
temperature
Maximum outdoor
46.0 / 114.8
temperature
AIR CONDITIONER UNIT OPERATION
Dry mode
When the air humidity is high, the unit can operate in
dry mode. Press <MODE> button and choose <DRY>.
If the room temperature is 2°C/3.6°F higher than the set
temperature, the air conditioner will operate under
cooling mode until it reaches within the 2°C/3.6°F range
of difference compared to the set temperature before it
converts to dry mode.
If the room temperature is within the 2°C/3.6°F range
of difference compared to the set temperature, it will
directly operate under dry mode.
The unit will operate at LOW speed under dry mode.
Heat mode (for heat pump unit only)
When the unit is switched on from cold start or
defrosting cycle, the indoor fan will start to operate only
after the coil reaches the desired temperature.
When the set temperature is achieved, the indoor fan
will operate until the coil cannot provide anymore
additional heat.
Horizontal Air Flow Control
For more effective air circulation, you can manually
adjust the air discharge grille to the left or right.
During cool mode operation and dry mode operation,
do not direct the air discharge louver downwards for too
long. If operating continues in this way, condensation
may occur on the louver, thus resulting in drippings.
Hot Keep (for heat pump only)
During compressor cut off, the indoor fan can be
switched to
(i) ON (default) or
(ii) OFF or
(iii) Interval on and off
by setting the slide switch shown in the diagram.
The switch is located at the front frame cover (next to
the ON/OFF switch).
NOTE : When the option is selected, the power supply of
the unit needs to be reset in order to activate the
function.
Multi-Split (for heat pump only)
The unit can be switched to multi split (MS) by setting
the slide switch shown in the diagram.
For hot keep, during compressor cut off, the indoor fan
motor will switch to OFF by default.
NOTE : When the option is selected, the power supply of
the unit needs to be reset in order to activate the
function.
Temperature Ts °C / °F Th °C / °F
Minimum indoor
16.0 / 60.8
temperature
Maximum indoor
30.0 / 86.0
temperature
Minimum outdoor
-8.0 / 17.6 -9.0 / 15.8
temperature
Maximum outdoor
24.0 / 75.2 18.0 / 64.4
temperature
Overheating protection (for heat pump unit only)
In case the internal and/or the external temperature is
too high, or that the filter is dirty and clogged up, the
refrigerant may be overheated. The compressor will cut
out when the condensing temperature reaches 62°C/
143.6°F.
Frost prevention
When the air filter is dirty, the evaporating temperature
will decrease and eventually cause frosting.
The LED light will blink to indicate that the filter is
dirty. If the evaporating temperature reaches -1°C/33.8°F,
the unit will trip and defrost.
Fan speed and rated cooling capacity
The rated cooling capacity is provided at the maximum
fan speed.
The cooling capacity is lower when the unit is operating
at MEDIUM and LOW fan speed.
Ts: Dry bulb temperature. Th: Wet bulb temperature.
Horizontal
Cooling
25˚C / 77˚F
HOT KEEP
OFF
ON
MS
ON/OFF
ON/OFF switch
1-10
DUAL ACTION ELECTROSTATIC AIR PURIFYING
AND DEODORIZING FILTER MEDIA AND FILTER FRAME
ACTION 1-
ELECTROSTATIC AIR PURIFYING FILTER
Removes microscopic dust, smoke and small invisible
particles to keep the room air clean with pre-charged
electrostatic polypropylene filter.
ELECTROSTATIC FILTER
ACTION 2-
DEODORIZING FILTER
Removes unwanted smells and odors in the air and keeps
the room air fresh with activated carbon filter.
! Caution
1. The electrostatic air purifying and deodorizing filter
should be replaced once every 6 months or when the
filter changes color to brownish, whichever is sooner.
2. Used dusty filters should be disposed and shouldn't be
reused, even if it has been cleaned and washed.
3. The filter is a consumable part which you can purchase
from your air conditioner dealer.
4. Use the new filter immediately once it has been taken
out from its sealed packing. Do not unpack the new
filter too early before it is actually used as this may
decrease its deodorizing effect.
HOW TO INSTALL
Open the
front frame
grille.
Slide out the original
filters.
Slide back the original
filter.
Insert the dual action
electrostatic and
deodorizing filters
into the slot.
3. Insert the end hose to the connector (indoor)
Refrigerant piping
2. Insert the end hose to the connector (outdoor)
1. Open valve cover to connecting the O
2
hose
O
2
Hose
INSTALLATION OF UNIT WITH O
2
THERAPY FEATURE
1-11
English
SERVICE AND MAINTENANCE
Maintenance Procedures
1. Remove any dust adhering to the filter by using a vacuum cleaner or wash in
lukewarm water (below 40°C/104°F) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto the unit.
3. Do not use gasoline, volatile substances or chemicals to clean the filter.
1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth
soaked in lukewarm water (below 40°C/104°F) and a neutral detergent
solution.
2. Do not use gasoline, volatile substances or chemicals to clean the
indoor unit.
Period
At least once
every 2 weeks.
More frequently if
necessary.
At least once
every 2 weeks.
More frequently if
necessary.
Service Parts
Indoor air filter
Indoor unit
1 Off the unit.
2 Unscrew the air discharge housing.
3 Flip open the air discharge housing.
4 Clean the blower.
5 Close the air discharge housing and tighten it with screw.
! Warning
Disconnect from the main power supply before servicing the air conditioner unit.
DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result
in fire hazards.
AUTO RANDOM RE-START FUNCTION
If there is a power cut when the unit is operating, it will automatically resume the same operating mode when the power is
restored.
! Caution
Before turning off the power supply, set the remote controllers ON/OFF switch to the “OFF” position to prevent the
nuisance tripping of the unit.
If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service
personnel or the user.
1-12
! Caution
Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic
panel to melt or deform as a result of the excessive heat.
When The Unit Is Not To Be Used For An Extended Long Period Of Time
Operate the unit for 2 hours
with the following setting.
Operating mode : cool
Temperature : 30°C/86°F
Remove the power plug.
If you are using an independent
electric circuit for your unit,
cut off the circuit.
Remove the batteries in the
remote control.
If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit.
Check the following fault conditions and causes for some simple troubleshooting tips.
TROUBLESHOOTING
Causes / Action
- Protection against frequent starting. Wait for 3 to 4 minutes for
the compressor to start operating.
- Power failure, or the fuse needs to be replaced.
- The power plug is disconnected.
- It is possible that your delay timer has been set incorrectly.
- If the fault persist after all these verifications, please
contact the air conditioner unit installer.
- The air filter is dirty.
- The doors or windows are open.
- The air suction and discharge are clogged.
- The regulated temperature is not high enough.
- Odours may be caused by cigarettes, smoke particles, perfume
etc. which might have adhered onto the coil.
- This is caused by air humidity after an extended long period of
operation.
- The set temperature is too low, increase the temperature setting
and operate the unit at high fan speed.
- Switch off unit and call dealer.
- Refrigerant fluid flowing into the evaporator coil.
Fault
1. The compressor does not operate 3 minutes after the air
conditioner unit is started.
2. The air conditioner unit does not operate.
3. The air flow is too low.
4. Discharge air flow has bad odour.
5. Condensation on the front air grille of the indoor unit.
6. Water flowing out from the air conditioner unit.
7. Hissing air flow sound from the air conditioner unit during
operation.
If the fault persists, please call your local dealer / serviceman.
Français
2-1
Ce manuel fournit les procédures d’installation pour assurer le bon fonctionnement et la sécurité de cet appareil.
Des ajustements peuvent être nécéssaires pour suivre les réglementations locales.
Avant d’installer et de faire fonctionner le climatiseur, lisez attentivement ce manuel et conservez le.
MANUEL D’INSTALLATION
CLIMATISEURS SPLIT SYSTEM MONTAGE MURAL
MODÈLE
Part No.:A08019020381 IM-WMG-0104(1)-McQuay
FROID SEUL
R22 / R407C
WM07G / MWM007G
SL07C / MLC007C
WM09G / MWM009G
SL09C / MLC009C
WM10G / MWM010G
SL10C / MLC010C
WM15G / MWM015G
SL15C / MLC015C
WM20G / MWM020G
SL20C / MLC020C
WM25G / MWM025G
SL25C / MLC025C
R410A
5WM07G / M5WM007G
5SL07C / M5LC007C
5WM09G / M5WM009G
5SL09C / M5LC009C
5WM10G / M5WM010G
5SL10C / M5LC010C
5WM15G / M5WM015G
5SL15C / M5LC015C
5WM20G / M5WM020G
5SL20C / M5LC020C
5WM25G / M5WM025G
5SL25C / M5LC025C
POMPE À CHALEUR
R22 / R407C
WM07GR / MWM007GR
SL07CR / MLC007CR
WM09GR / MWM009GR
SL09CR / MLC009CR
WM10GR / MWM010GR
SL10CR / MLC010CR
WM15GR / MWM015GR
SL15CR / MLC015CR
WM20GR / MWM020GR
SL20CR / MLC020CR
WM25GR / MWM025GR
SL25CR / MLC025CR
R410A
5WM07GR / M5WM007GR
5SL07CR / M5LC007CR
5WM09GR / M5WM009GR
5SL09CR / M5LC009CR
5WM10GR / M5WM010GR
5SL10CR / M5LC010CR
5WM15GR / M5WM015GR
5SL15CR / M5LC015CR
5WM20GR / M5WM020GR
5SL20CR / M5LC020CR
5WM25GR / M5WM025GR
5SL25CR / M5LC025CR
2-2
SOMMAIRE
PRÉCAUTIONS DE SÉCURITÉ
- Disposition et Dimensions page i-iv
- Précautions de Sécurité page 2
- Diagramme D’Installation page 3
- Installation de L’Unité Extérieure page 3
- Installation de L’Unité Intérieure page 4
- Raccordement des Tuyauteries page 5
- Raccordement Électrique page 6
- Précautions Spéciales en Traitant L’Unité de
R410A page 7
- Aspiration et Chargement page 7
- L’indicateur S’Allume page 8
- Opération du Climatiseur page 9
- Plage d’exploitation page 9
- Filtre Électrostatique page 10
-
Installation de l’unité à fonction de thérapie à l’O
2
page 10
- Fonction de Redemarrage au Hasard Automatique page 11
- Entretien ét Maintenance page 11
- Analyse des Causes de Dysfonctionnement du
Climatiseur page 12
! Avertissement
Vérifier les points suivants au cours de l’installation.
Ne pas installer l’appareil où il peut se produire des fuites de gaz inflammable.
En cas de fuite et accumulation de gaz autour de l’appareil, il y a risque d’incendie.
S’assurer que le tuyau d’évacuation du condensat est correctement branché.
Si le tuyau d’évacuation est mal raccordé, il peut y avoir des fuites d’eau.
Ne pas surcharger l’unité (en fluide frigorigène).
Cet appareil est préchargé en usine. Une charge trop importante risque de provoquer une surcharge
électrique ou d’endommager le compresseur.
S’assurer que le panneau supérieur de l’appareil est remis en place après l’installation ou l’entretien.
Avec un panneau mal fixé l’appareil va fonctionner bruyamment.
Les bords coupants et les surfaces du refroidisseur tuulaire présentent un risque de blessure. Mieux
vaut éviter le contact avec ces endroits.
Avant de faire fonctionner l’appreil, veuillez bien lire les précautions de sécurité suivantes.
! Attention
L’installation et la maintenance doivent être exécutées par une personne qualifiée qui est familiarisée avec les lois
et réglementations en vigueur, et aussi expérimentée dans ce type d’équipements.
Tous les câblages doivent répondre aux réglementations électriques nationales.
Avant de commencer le raccordement suivant le schéma électrique, s’assurer que la tension nominale de l’appareil
corresponde bien à celle indiquée sur la plaque signalétique.
L unité doit être raccordée à la TERRE pour prévenir tous les risques possibles dûes à un défaut d’isolation.
Aucun câble électrique ne doit toucher la tuyauterie du réfrigérant, le compresseur ou les pièces mobiles des moteurs
de ventilation.
Avant l’installation ou l’entretien du climatiseur, s’assurer que l’appareil est éteint (OFF).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100

McQuay 5SL07C Инструкция по установке

Категория
Сплит-системы кондиционирования
Тип
Инструкция по установке

Задайте вопрос, и я найду ответ в документе

Поиск информации в документе стал проще с помощью ИИ