Ingersoll-Rand X4i Quick Setup Manual

  • Здравствуйте! Я прочитал руководство по быстрой настройке системы автоматизации компрессоров Ingersoll Rand X4I. Я могу ответить на ваши вопросы о настройке параметров, таких как количество компрессоров, пределы давления, времени работы, и другие функции. Готов помочь!
  • Как изменить количество подключаемых компрессоров?
    Как настроить предельные значения давления?
    Что делать, если возникла ошибка?
    Как сбросить настройки до значений по умолчанию?
Ingersoll Rand
System Automation X4I
Quick Setup Manual
Before installing or starting this unit for the first
time, this manual should be studied carefully to
obtain a working knowledge of the unit and or the
duties to be performed while operating and
maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical
manual contains IMPORTANT SAFETY DATA and
should be kept with the unit at all times.
C.C.N. : 80443641
REV. : A
DATE : APRIL 2007
More Than Air. Answers.
Online answers: http://www.air.irco.com
2
SECTION 1 — TABLE OF CONTENTS
SECTION 1 — TABLE OF CONTENTS................................ 2
SECTION 2 — INTRODUCTION........................................ 3
SECTION 3 — SAFETY..................................................... 3
INSTALLATION ............................................................ 3
OPERATION................................................................. 3
MAINTENANCE AND REPAIR ........................................ 3
SECTION 4 — TYPICAL INSTALLATION............................ 4
SECTION 5 — BEFORE YOU START .................................. 5
CHECK LIST GUIDANCE ............................................... 5
ASSISTANCE................................................................ 5
SECTION 6 — MENU NAVIGATION .................................. 6
DISPLAY ITEM STRUCTURE .......................................... 8
MAIN STATUS SCREEN DISPLAY (MENU PAGE P00) ....... 8
INFORMATION DISPLAYS ............................................. 8
STATUS DISPLAY...................................................... 8
SEQUENCE ROTATION.............................................. 9
OPERATIONAL FUNCTIONS.......................................... 9
STOP ................................................................ 9
START ................................................................ 9
POWER FAILURE AUTO-RESTART ........................ 10
FAILURE MODE....................................................... 10
RESET .............................................................. 10
COMPRESSOR IDENTIFICATION .............................. 10
FAULT CODES ........................................................ 10
SECTION 7 — QUICK SETUP COMMISSIONING ............... 11
PHYSICAL CHECKS .....................................................11
PRESSURE DISPLAY.....................................................11
QUICK SET-UP CONFIGURATION.................................11
SECTION 8 — SYSTEM CONFIGURATION........................12
ACCESSING THE CONFIGURATION SCREENS ...............12
QUICK SET-UP CONFIGURATION.................................12
S02 TAB SETTINGS..................................................12
S02 TAB SCREEN.....................................................12
NUMBER OF COMPRESSORS SETTINGS.....................13
MAXIMUM PRESSURE ALARM SETTINGS ...................13
S01 TAB SETTINGS..................................................14
REAL TIME CLOCK SETTINGS...................................14
COMPRESSOR CONNECTION CONFIGURATION ...........15
C02 TAB SCREEN ....................................................15
COMPRESSOR CONNECTION METHOD.....................15
IR-PCB SETUP ..........................................................15
IRV-PCB SETUP ........................................................16
COMPRESSOR TABLES CONFIGURATION .....................17
T01 TAB SCREEN ....................................................17
HIGH PRESSURE SET POINT SETTINGS......................17
LOW PRESSURE SET POINT SETTINGS.......................17
MINIMUM PRESSURE ALARM SETTINGS ....................18
TOTAL UNIT RESET AND DEFAULT VALUES .............18
SECTION 9— X4I COMMISSIONING FORMS ....................22
SECTION 2 — INTRODUCTION
This manual is intended as a quick reference to establish
basic sequence control of the compressors with the X4I.
This document details the minimum required hardware
setup process for the product. Please refer to the
Operator’s Manual for complete setup and operating
instructions. If you have any questions regarding the X4I,
please contact your local authorized and trained Ingersoll
Rand Service Center or contact Technical Support
Services at 800-820-0308 to speak one of our Technical
Support Engineers.
SECTION 3 — SAFETY
!
!
WARNING :
Risk of Danger
WARNING :
Risk of Electric Shock
WARNING :
Risk of High Pressure
WARNING :
Consult Manual
3
Before installing or operating the X4I, take time
to carefully read all the instructions contained in
this manual, all compressor manuals, and all
manuals of any other peripheral devices that may
be installed or connected to the product.
Electricity and compressed air have the potential
to cause severe personal injury or property
damage.
The operator should use common sense and
good working practices while operating and
maintaining this system. All applicable codes
should be strictly adhered to.
Maintenance must be performed by adequately
qualified personnel that are equipped with the
proper tools.
INSTALLATION
Installation work must only be carried out by a
competent person under qualified supervision.
A fused isolation switch must be fitted between
the main power supply and the X4I.
The X4I should be mounted in such a location as
to allow operational and maintenance access
without obstruction or hazard and to allow clear
visibility of indicators at all times.
If raised platforms are required to provide access
to the X4I they must not interfere with normal
operation or obstruct access. Platforms and
stairs should be of grid or plate construction
with safety rails on all open sides.
OPERATION
The X4I must only be operated by competent
personnel under qualified supervision.
Never remove or tamper with safety devices,
guards or insulation materials fitted to the X4I.
The X4I must only be operated at the supply
voltage and frequency for which it is designed.
When main power is switched on, lethal voltages
are present in the electrical circuits and extreme
caution must be exercised whenever it is
necessary to carry out any work on the unit.
Do not open access panels or touch electrical
components while voltage is applied unless it is
necessary for measurements, tests or
adjustments. Such work should be carried out
only by a qualified electrician equipped with the
correct tools and wearing appropriate protection
against electrical hazards.
All air compressors and/or other equipment
connected to the unit should have a warning sign
attached stating ‘THIS UNIT MAY START
WITHOUT WARNING' next to the display panel.
If an air compressor and/or other equipment
connected to the unit is to be started remotely,
attach warning signs to the equipment stating
‘THIS UNIT CAN BE STARTED REMOTELY’ in a
prominent location, one on the outside of the
equipment, the other inside the equipment
control compartment.
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must only
be carried out by competent personnel under
qualified supervision.
If replacement parts are required use only
genuine parts from the original equipment
manufacturer, or an alternative approved source.
Carry out the following operations before
opening or removing any access panels or
carrying out any work on the X4I:
Isolate the X4I from the main electrical power
supply. Lock the isolator in the 'OFF' position
and remove the fuses.
Attach a label to the isolator switch and to the
unit stating ‘WORK IN PROGRESS - DO NOT APPLY
VOLTAGE'. Do not switch on electrical power or
attempt to start the X4I if such a warning label is
attached.
Make sure that all instructions concerning
operation and maintenance are strictly followed
and that the complete unit, with all accessories
and safety devices, is kept in good working
order.
The accuracy of sensor devices must be checked
on a regular basis. They must be calibrated when
acceptable tolerances are exceeded. Always
ensure any pressure within the compressed air
system is safely vented to atmosphere before
attempting to remove or install a sensor device.
The X4I must only be cleaned with a damp cloth,
using mild detergents if necessary. Avoid the use
of any substances containing corrosive acids or
alkalis.
Do not paint the control faceplate or obscure any
indicators, controls, instructions or warnings.
SECTION 4 — TYPICAL INSTALLATION
Refer to the X4I Operator’s Manual and the X4I Interconnect and Application Guide for installation details.
New Picture above
4
5
SECTION 5 — BEFORE YOU START
Prior to attempting installation and commissioning of the
X4I please review the following check list:
o Quick Set Up Manual is available and has been
reviewed
o Application Guide is available and the correct
diagrams have been identified
o If the specific diagrams are not in the Application
Guide the specific compressor control wiring
schematic will be required to define the correct
interconnection
o Operator’s Manual is available and has been
reviewed
o Compressors to be connected can accept remote
load / unload commands
o Compressors to be connected have automatic
Start / Stop capability
o Correct compressor controller EPROM is installed
or available to allow Remote Control and Auto
Start/Stop (SE Controller)
o The correct wire is available to connect the X4I
with the Compressor / IR-PCB interface
o The correct wire is available to connect the X4I
with the pressure sensor/transducer
o The X4I can be located within 330ft (100m) of
each compressor
o The Pressure sensor/transducer can be located
appropriately within 330ft (100m) for the X4I
Controller
CHECK LIST GUIDANCE
o Electrical Drawing For Each Compressor: It is
important to have the Electrical drawing for each
compressor so that the correct interconnect
drawing can be referenced from the Interconnect
and Application Guide
o Types of Compressors To Be Sequenced: Refer
to the Interconnect and Application Guide for
specific details on the types of compressors that
can be sequenced and their individual
requirements such as Auto Restart, Intellisys
Software, etc.
o IR-PCB Mounting: The IR-PCB module is
designed to be installed within the compressor
starter enclosure. The mounting location of the
IR-PCB should be away from any high voltage
connections, contactors, or transformers.
o IR-PCB and Compressor Interconnections: Refer
to the Interconnect and Application Guide for
specific drawings for various compressors and
the X4I. If there is not a specific drawing
available for the compressor being sequenced at
the site, please contact Technical Support
Services for assistance.
o IR-PCB and Compressor Interconnection Wire:
The X4I is supplied with 100 Ft (100m) of 18
gauge stranded wire (Orange) to use for the
connections between the IR-PCB and the
compressor. In most cases, this is sufficient for
most installations. If additional wire is required,
any 18 gauge stranded wire can be used in lieu
of the wire provided in the kit.
o X4I and Compressor Interconnect Wire: The X4I
and the compressor IR-PCB interconnection is
designed to use 7-conductor shielded cable or
individual wires run through earthed/grounded
metal conduit/tubing. (18 gauge wire)
o X4I and Pressure Transducer Wire: The X4I and
the pressure transducer interconnection is
designed to use 2-conductor shielded cable.
(18gauge)
o All external wiring to the X4I should be made
through the holes (grommets) provided in the
X4I enclosure (8 in total). Drilling or tapping
additional holes in the enclosure can result metal
shavings making contact with the circuit boards.
Damage due to metal shavings in the circuit
boards is not covered by warranty.
o Power / Local Disconnect (Breaker): Incoming
power (115VAC/230VAC, single phase) should
be fused (50VA) and a local disconnect provided.
The power source should be regulated and noise
free. The use of a power supply regulator might
be required in applications where unregulated
power is an issue
o Confirm that all electrical connections are made
properly and tightened and conform to local
standards.
o Common Receiver: The X4I must have its
pressure transducer located in a common
receiver for proper Wet Side or Dry Side System
pressure control.
o Pressure Transducer Installation: The pressure
transducer threads are BPT. It is the equivalent
of ¼” NPT.
ASSISTANCE
o Contacting Technical Support Services or Service
Bulletins listed on the IR ServiceNet can provide
further assistance if there are other questions or
concerns prior to Installation and Start-up.
o
SECTION 6 — MENU NAVIGATION
The keypad and navigation buttons on the X4I are depicted below and provide the following functionality:
6
1
2
3
Above Picture is new
7
DISPLAY ITEM STRUCTURE
All operational system status and values are accessible
from the normal user display. To view status or values
that are not normally visible on the default screen, press
UP or DOWN. All standard User display items are
viewable only and cannot be adjusted. The standard user
display items are shown on three different Menu Page
(P00) screens: “Main Status”, “Status Display” and
“Sequence Rotation Display”.
8
All adjustable value, parameter or option item displays
are grouped into “menu mode” lists. Items are assigned
to a list according to type and classification. Item lists
are identified by page number (or menu number). All
adjustable parameters and options are assigned to menu
mode pages “P01” or higher.
MAIN STATUS SCREEN DISPLAY (MENU
PAGE P00)
At controller initialization, all display elements and LED
indicators are switched on for three seconds and then
the normal operating display is shown. In normal
operational display mode, the main display will
continuously show the detected system pressure and the
item display will show the first item of the “Page 00”
menu. User menu “Items” can be selected using the UP or
DOWN buttons at any time. Pressing the ENTER button
will lock any selected Item display and inhibit return to
the default display. When an Item display is locked, the
lock key symbol will be shown. To unlock an item
display, press UP or DOWN to view an alternative Item
display or press RESET or ESCAPE. No item values,
options or parameters can be adjusted in page “P00”. If a
fault condition occurs, the fault code becomes the first
list item and the display will automatically jump to
display the fault code. More than one active fault code
item can exist at any one time and can be viewed by
pressing UP or DOWN. The most recent “active” fault will
be at the top of the list.
Main Status Screen
INFORMATION DISPLAYS
To view detailed information applicable to the selected
user menu display item press the enter
button:
STATUS DISPLAY
P00
#1
1
18:00 T02
102
98
80
psi
psi
psi
Status Display Screen
If the “Pressure Schedule” feature is active;
shows the day of the week (#1: Monday), the
time of day (18:00) and the table to be used
(T02) of the next scheduled instruction to be
executed.
1
The current active ‘Table’ (T01)
Upper, or unload, pressure set point
Lower, or load, pressure set point
Minimum pressure alarm (Warning)
Press the escape
button to return to the normal
operational display screen.
SEQUENCE ROTATION
9
P00
#4 18:00
18 / 05 / 2006
A B C D
Sequence Rotation Display Screen
Day of the week (#4: Thursday), the time of
day (18:00) and the date (18/05/2006) of
the next automated sequence rotation event.
The active ‘mode’ of operation.
ABCD The current active rotation sequence
assignment.
Press the escape
button to return to the normal
operational display screen.
NOTE: The sequence assignment can be manually rotated
at any time. When viewing the ‘Sequence Rotation’
information screen press the Enter button. The
manual rotation symbols will appear and
flash. Press the enter button to execute a manual
rotation or the escape button to abandon the
manual rotation.
Automated sequence rotation is not disrupted by a
manual rotation; the next scheduled automated
sequence rotation event will still occur.
OPERATIONAL FUNCTIONS
STOP
To stop the X4I, press STOP. Dependent on the setup
and configuration of the X4I, the compressors will
function as follows:
If parameter CF=X, then pressure regulation
control is automatically transferred back to each
compressor. The compressor(s) will continue to
operate using the pressure settings programmed
or set in the individual compressor controller(s).
If parameter CF=
, then the X4I will hold each
compressor in an offload state. If the
compressor is equipped with a main motor run-
on-time function the compressor will run offload
for a period of time and then stop in to a
“standby” or “auto restart” state.
The design of some air compressor control systems may
inhibit automatic transfer of pressure regulation control
to local operation mode. In this instance, the compressor
will not continue production of compressed air. Consult
the air compressor manual or your air compressor
supplier or specialist for details before installing the X4I.
START
To start the X4I press START. If the Prefill function is
enabled, and system pressure is below the set prefill
pressure, the system will enter Prefill mode for the set
Prefill time.
NOTE: The Default setting for Prefill is OFF.
See the section on Prefill in the Operator’s Manual
for more information.
To manually skip the Prefill function, press and hold
START for several seconds. When Prefill is complete, if
applicable, the X4I will enter normal operating mode.
The X4I will operate in accordance with the parameters
and options set in the active “Table”.
See the section on Tables in the Operator’s Manual
for more information.
Each compressor in the system must be started (running
or in a standby or auto restart condition) before X4I
control of the compressor can be established. The X4I
will not start a compressor that is in a stopped condition.
POWER FAILURE AUTO-RESTART
If the power failure auto-restart function is enabled, the
X4I will automatically start when power is restored after a
disruption or failure, if the X4I was in a ‘started’ state
when the power disruption or failure occurred.
NOTE: The Default setting for Power Failure Auto Restart
is ON.
10
NOTE: The X4I will not automatically restart if it was in a
stopped state when the power disruption or failure
occurred.
FAILURE MODE
If the X4I experiences a disruption to normal control, or
an X4I shutdown fault occurs, pressure regulation control
is automatically transferred back to each compressor.
The compressor(s) will continue to operate using the
pressure settings programmed or set in the individual
compressor controller(s).
RESET
To reset an X4I Alarm (Warning) or Shutdown condition,
press RESET. Compressor Alarm (Warning) conditions are
automatically reset when the condition has been resolved
and reset on the compressor. “Compressor Not
Available” (Shutdown, Trip) conditions are automatically
reset when the condition has been resolved and reset on
the compressor; and the compressor has been restarted.
COMPRESSOR IDENTIFICATION
Each compressor connected to the X41 will have a unique
assigned compressor identification number; starting at
compressor 1 and increasing sequentially to the number
of compressors connected to the unit.
Ingersoll Rand
102
psi
1234
1234
FAULT CODES
In the event of a unit or systemFault”, the X4I will
display a fault code. The fault code becomes an item in
the user operational display menu. If more than one
“active” fault occurs, each will be displayed as a separate
item in the operational user menu. Press UP or DOWN to
view all active fault codes or to view the normal status
display.
See the section on Fault Codes in the Operator’s
Manual for more information.
11
SECTION 7 — QUICK SETUP COMMISSIONING
When commissioning the X4I, carry out the following
procedures before attempting to start. It is
recommended that an authorized and trained Service
Technician performs the commissioning.
The Quick Setup Manual allows the user to enter the
basic required parameters to quickly start sequencing
the compressors with the X4I. Once sequencing and
basic control is established, the user can refer to the
Operator’s Manual for more detailed information on
other features and functionality of the unit.
PHYSICAL CHECKS
1. Before applying power to the X4I, ensure that the
power supply connections are correct and secure
and that the operating voltage selector is set
correctly for the power supply voltage in use:
115Vac or 230Vac (+-10%), 50/60Hz.
2. Open the front panel of the X4I and check the
location of the link wire(s) connected to the
“Voltage Selection” terminals of the power supply
PCB. If necessary, change the link wire locations
to those illustrated for the voltage in use.
See the INSTALLATION section in the
Operator’s Manual for more information.
3. Switch on the power supply to the unit.
The control program identification will be displayed for a
short period followed by the normal operational user
display.
PRESSURE DISPLAY
Check the displayed system pressure. If the pressure is
incorrect, or inaccurate, check the type and range of the
sensor and carry out the pressure sensor commissioning
and calibration procedure. If the display shows an error,
the error will need to be corrected before continuing.
See the Operator’s Manual for troubleshooting and
correcting the fault or error condition.
QUICK SET-UP CONFIGURATION
Before successful basic operation can be established the
following items must be set (in the order show) to suit
installation requirements. The X4I can easily be
commissioned by simply setting the following
parameters.
NOTE: Leave all other parameters at factory defaults.
S02 – NC Number of Compressors
S02 – PM Maximum Pressure Alarm
S01 - Ct Real Time Clock Set
C02 –01 to 04 Compressor #1 to 4 Configuration
T01 – PH High Pressure Set Point
T01 – PL Low Pressure Set Point
T01 – Pm Minimum Pressure Alarm
NOTE: By default, the pressure unit of measurement is
PSI. If the unti of measurement is BAR or kPA, please
refer to the Operator’s Manual for information on
changing the S02 P> Units Setting parameter.
Once set, the X4I will sequence all compressor based on
load demand (First In / Last Out) and will rotate them
once per week on Monday at 00:00 hours.
SECTION 8 — SYSTEM CONFIGURATION
ACCESSING THE CONFIGURATION SCREENS
In order to change the configuration parameters, you will
first need to input the service access code. The service
access code is 0032. Enter this code as follows:
1. Press the menu
button. This will display
the Access Code Screen.
12
Access Code Screen
2. Adjust the first access code digit by using the
scroll up (+)
and scroll down (-)
buttons. When the correct number
shows press the enter
button. The cursor
should then move to the next digit to the right.
3. Adjust the remaining digits until the proper
access code is shown on the screen. If for any
reason you need to go back to a previous digit
press the escape
button. This will back
the cursor up one digit at a time.
4. When you’ve adjusted the final digit to the
correct number press the enter
button and
you should see an animation of a key opening a
lock. You are now able to access the
configuration screens.
5. When in menu mode, you must press the escape
button until you are returned to the Main
menu. If you do not, the X4I remains in the
menu mode.
6. After successfully entering the access code you
should see the screen shown below. The cursor
will flash on the name of the current page (P00).
You can scroll through the tabs by pressing the
scroll up (+)
and scroll down (-)
buttons.
Default Configuration Screen
QUICK SET-UP CONFIGURATION
S02 TAB SETTINGS
After you have successfully entered the password and
you are at the P00 screen, scroll up (+)
or scroll
down (-)
until the S02 page is highlighted.
S02 TAB SCREEN
Press the enter
button to confirm your selection.
The cursor should be flashing on 01 P>.
S02 Home Screen
NUMBER OF COMPRESSORS SETTINGS
1. From the S02 home screen, scroll up (+)
or scroll down (-)
to move the cursor to
highlight 02- NC (Number of Compressors).
13
Number of Compressors Settings
2. The default setting for this parameter is 4. The 4
indicates the number of compressors the X4I is
configured for and the number of compressors
that will be sequenced by the X4I. This value
must be set to match the system at
commissioning.
3. Press the enter
button to display the
Number of Compressor configuration screen.
The flashing cursor should be displayed
highlighting the Number of Compressor
parameter. The values for this parameter are “1”
to “4”.
4. Scroll up (+)
or scroll down (-)
until the value matches the number of
compressors that you have wired into the
controller. Press the enter
button to
confirm your selection.
5. You should be returned to the S02 home screen
and values just entered should appear next to
the NC parameter.
MAXIMUM PRESSURE ALARM SETTINGS
1. From the S02 home screen scroll up (+)
or scroll down (-)
to move the cursor to
highlight 03- PM (Maximum Pressure Alarm).
Maximum Pressure Alarm Settings
2. The default setting for this parameter is 145.
This number indicates the value used for the
High pressure ‘Fault’ level. This value remains
active at all times regardless of which ‘Table’ is
active. It should be set at a level just below the
system pressure relief value(s) and below the
maximum system pressure rating of all air
system components.
3. Press the enter
button to display the
Maximum Pressure Alarm configuration screen.
The flashing cursor should be displayed
highlighting the Maximum Pressure Alarm
parameter. The values for this parameter are:
o The highest value for the Maximum
Pressure Alarm setpoint = “The
maximum range of the pressure
transducer used”
o The lowest value for the Maximum
Pressure Alarm setpoint = “The highest
value from any Table “PH - Pressure
High” Setpoint plus 2 times the “To
Tolerance”
If PH in Table 1 (T01) is set for 100 PSI,
and PH in Table 2 (T02) is set for 110
and TO is set for 3.0 PSI, then the lowest
Maximum Pressure setpoint would be
116 PSI.
4. Scroll up (+)
or scroll down (-)
until the value is set to a pressure that is just
below your air system requirements. Press the
enter
button to confirm your selection.
5. You should be returned to the S02 home screen
and values just entered should appear next to
the PM parameter.
6. After you have completed adjusting the settings
on the S02 screen, press the escape
button
to return to the page selection screen.
S01 TAB SETTINGS
1. Scroll up (+)
or scroll down (-)
until the S01 page is highlighted.
Figure 1 – S01 Screen
2. Press the enter
button to confirm your
selection. The cursor should be flashing on line
01 Ct.
User Configuration Home Screen
REAL TIME CLOCK SETTINGS
1. From the S01 home screen scroll up (+)
or scroll down (-)
to move the cursor to
highlight 01- Ct (Real Time Clock).
14
Real Time Clock Setting
2. The default setting for this parameter is - --.--,
which indicates the Real Time Clock has not
been initialized. The format for the Real Time
Clock is as follows.
o The ‘Day of the Week’ (1= Monday to
7=Sunday) which is automatically
calculated and set in accordance with
the Day, Month and Year entered
o The Hours and Minutes (displayed in
Military Time)
o The Day, Month, and Year
3. Press the enter
button to display the Real
Time Clock setup screen. The flashing cursor
should be displayed highlighting the Hours dash.
This sets the Hour for the Real Time Clock. The
values for this parameter are “00” to “23”.
4. Scroll up (+)
or scroll down (-)
until the value is set for the correct Hour for the
Real Time Clock. Press the enter
button to
accept this parameter. The flashing cursor
should be displayed highlighting the Minutes
dash. This sets the Minutes for the Pressure
Schedule. The values for this parameter are “0”
to “59”.
5. Scroll up (+)
or scroll down (-)
until the value is set for the correct Minute for
the Real Time Clock. Press the enter
button
to accept this parameter. The flashing cursor
should be displayed highlighting the Day dash.
This sets the Day for the Real Time Clock. The
values for this parameter are “1” to “31”.
6. Scroll up (+)
or scroll down (-)
until the value is set for the correct Day for the
Real Time Clock. Press the enter
button to
accept this parameter. The flashing cursor
should be displayed highlighting the Month
dash. This sets the Month for the Real Time
Clock. The values for this parameter are “1” to
“12”
7. Scroll up (+)
or scroll down (-)
until the value is set for the correct Month for
the Real Time Clock. Press the enter
button
to accept this parameter. The flashing cursor
should be displayed highlighting the Year dash.
This sets the Year for the Real Time Clock. The
values for this parameter are “2005” to “2100”.
8. Scroll up (+)
or scroll down (-)
until the value is set for the correct Year for the
Real Time Clock. Press the enter
button to
accept this parameter. You should be returned to
the S01 home screen and values just entered
should appear next to the Ct parameter.
9. After you have completed adjusting the settings
on the S01 screen press the escape
button
to return to the page selection screen.
COMPRESSOR CONNECTION
CONFIGURATION
15
C02 TAB SCREEN
1. After you have returned to the page selection
screen, scroll up (+)
or scroll down (-)
until the C02 page is highlighted.
C02 Tab Screen
2. Press the enter
button to confirm your
selection. The cursor should be flashing on line
01 01.
C02 Home Screen
COMPRESSOR CONNECTION METHOD
1. From the C02 home screen scroll up (+)
or scroll down (-)
to move the cursor to
highlight 01- 01 (Compressor 1 Connection
Settings).
Compressor Connection Settings
2. The default setting for this parameter is I-PCB.
This setting is used for the type, method of
connection, and the control functionality, of each
compressor connected to the X4I. Each air
compressor in the system is integrated with the
X4I using an interface module.
3. Press the enter
button to display the
Compressor Connection setup screen for
compressor #1. The flashing cursor should be
displayed highlighting the I-PCB. The values for
this parameter are:
o “IR-PCB” for Fixed speed, load/unload;
connected to X4I using ‘ir-PCB’ module
using 6-wire method.
o “IRV-PCB” for Variable Speed; connected
to X4I using ‘ir-PCB’ module employing
the 7-wire ‘V’ terminal method.
o “I-485” for Fixed speed, load/unload;
connected to X4I on Multi485 network.
o “V-485” for Variable Capacity/Speed;
connected to X4I on Multi485 network.
NOTE: Quick Setup only requires the selection of Option
A or B. For information on Option C or D, please refer to
the Operator’s Manual.
IR-PCB SETUP
1. Scroll up (+)
or scroll down (-)
to change the value to IR-PCB. Press the enter
button to confirm your selection.
2. The flashing cursor should be displayed
highlighting the Compressor Start Sequence
Time. The Default setting for this parameter is
10 Sec. This is the time required to start the
motor and then load the compressor. The values
for this parameter are “0” to “60”.
3. Scroll up (+)
or scroll down (-)
to change the value to the time required. Press
the enter
button to confirm your selection.
4. The flashing cursor should be displayed
highlighting the ‘i-PCB’ Alarm (Warning) Input.
The Default setting for this parameter is +V=!. If
the ‘i-PCB’ Alarm input detects a voltage between
12-250VAC/DC, an alarm (Warning) condition is
generated. The values for this parameter are:
o +V=! for an Alarm (Warning) condition is
generated if the ‘ir-PCB’ Alarm input
detects a voltage between 12-250Vac/dc
(default)
o 0V=! for an Alarm (Warning) condition is
generated if the ‘ir-PCB’ Alarm input
detects no voltage.
5. Scroll up (+)
or scroll down (-)
to change the value for the Alarm condition
required for your application. Press the enter
button to confirm your selection. You
should be returned to the C02 home screen and
‘ir-PCB’ should appear next to the 01-01
parameter.
IRV-PCB SETUP
1. Scroll up (+)
or scroll down (-)
to change the value to IRV-PCB. Press the enter
button to confirm your selection.
2. The flashing cursor should be displayed
highlighting the Compressor Start Sequence
Time. The Default setting for this parameter is
10 Sec. This is the time required to start the
motor and then load the compressor. The values
for this parameter are “0” to “60”.
3. Scroll up (+)
or scroll down (-)
to change the value to the time required. Press
the enter
button to confirm your selection.
4. The flashing cursor should be displayed
highlighting the ‘i-PCB’ Alarm (Warning) Input.
The Default setting for this parameter is +V=!. If
the ‘i-PCB’ Alarm input detects a voltage between
12-250VAC/DC, an alarm (Warning) condition is
generated. The values for this parameter are:
o +V=! for an Alarm (Warning) condition is
generated if the ‘ir-PCB’ Alarm input
detects a voltage between 12-250Vac/dc
(default)
o 0V=! for an Alarm (Warning) condition is
generated if the ‘ir-PCB’ Alarm input
detects no voltage.
5. Scroll up (+)
or scroll down (-)
to change the value for the Alarm condition
required for your application. Press the enter
button to confirm your selection.
6. The flashing cursor should be displayed
highlighting the Compressor Run-On Stop Time.
The Default setting for this parameter is 0 Sec.
This is the time that the compressor main motor
will continue to run when the compressor is
unloaded. The time is from the moment the
compressor unloads until the main motor stops
and the compressor enters a ‘Standby’ or ‘Auto
Restart’ condition. This setting is only applicable
to ‘IRV-PCB’ connectivity and is not displayed for
other connectivity options. The values for this
parameter are “0” to “999”.
7. Scroll up (+)
or scroll down (-)
to change the value to the time required. Press
the enter
button to confirm your selection.
You should be returned to the C02 home screen
and ‘irv-PCB’ should appear next to the 01-01
parameter.
8. Repeat this by scrolling up (+)
or
scrolling down (-) to move the cursor
to highlight the remaining compressors and set
the Compressor Connection type and the
Compressor Connection parameters for each of
the other compressors.
9. You should be returned to the C02 home screen
each time after completing the Compressor
Connection Setting and values just entered
should appear next to the 01 to 04 parameters
Once all values have been entered for all
compressors, you should be returned to the C02
home screen and all ‘i-PCB’ values entered
should appear next each compressor parameter.
10. After you have completed adjusting the settings
on the C02 screen press the escape
button
to return to the page selection screen.
16
COMPRESSOR TABLES CONFIGURATION
T01 TAB SCREEN
1. After you have returned to the page selection
screen, scroll up (+)
or scroll down (-)
until the T01 page is highlighted.
T01 Tab Screen
2. Press the enter
button to confirm your
selection. The cursor should be flashing on line
01 PH.
17
T01 Home Page
HIGH PRESSURE SET POINT SETTINGS
1. From the T01 home screen scroll up (+)
or scroll down (-)
to move the cursor to
highlight 01- PH (High Pressure Set Point).
High Pressure Set Point Setting
2. The default setting for this parameter is 102 PSI.
This setting indicates the High Pressure Setpoint
that is used to unload the compressor when the
Table is active.
3. Press the enter
button to display the High
Pressure Set Point setup screen. The flashing
cursor should be displayed highlighting 102 PSI.
The values for this parameter are:
o The highest value for the High Pressure
setpoint = PM “Maximum Pressure
Alarm” minus 2 times TO “Tolerance”.
If PM is set for 145 PSI and TO is set for
3.0 PSI, then the highest value for the
High Pressure setpoint would be 139 PSI.
o The lowest value for the High Pressure
setpoint = PL “Low Pressure” setpoint
plus TO “Tolerance”
If PL is set for 98 PSI and TO is set for
3.0 PSI, then the lowest value for the
High Pressure setpoint would be 101 PSI.
4. Scroll up (+)
or scroll down (-)
until the number is set to the value required to
maintain control of for your air system. Press
the enter
button to confirm your selection.
You should be returned to the T01 home screen
and values just entered should appear next to
the PH parameter.
LOW PRESSURE SET POINT SETTINGS
1. From the T01 home screen scroll up (+)
or scroll down (-)
to move the cursor to
highlight 02- PL (Low Pressure Set Point).
Low Pressure Set Point Setting
2. The default setting for this parameter is 98 PSI.
The 98 PSI indicates the Low Pressure Setpoint
that used to load the compressor when the Table
is active.
3. Press the enter
button to display the Low
Pressure Set Point setup screen. The flashing
cursor should be displayed highlighting the 98
PSI. The values for this parameter are:
o The highest value for the Low Pressure
setpoint = PH “High Pressure” setpoint
minus TO “Tolerance”. If PH is set for
102 PSI and TO is set for 3.0 PSI, then
the highest value for the Low Pressure
setpoint would be 99 PSI.
o The lowest value for the Low Pressure
setpoint = Pm “Minimum Pressure Alarm”
setpoint plus 2 times TO “Tolerance” If
Pm is set for 80 PSI and TO is set for 3.0
PSI, then the lowest value for the Low
Pressure setpoint would be 86 PSI.
4. Scroll up (+)
or scroll down (-)
until the number is set to the value required to
maintain control of for your air system. Press
the enter
button to confirm your selection.
You should be returned to the T01 home screen
and values just entered should appear next to
the PL parameter.
MINIMUM PRESSURE ALARM SETTINGS
1. From the T01 home screen scroll up (+)
or scroll down (-)
to move the cursor to
highlight 03- Pm (Minimum Pressure Alarm).
18
Minimum Pressure Alarm Setting
2. The default setting for this parameter is 80 PSI.
The 80 PSI indicates the Minimum Low Pressure
Setpoint that is used to alarm if the pressure in
the air system is low when the Table is active.
3. Press the enter
button to display the
Minimum Low Pressure Setpoint setup screen.
The flashing cursor should be displayed
highlighting the 80 PSI. The values for this
parameter are:
o The lowest Minimum Pressure Alarm
setpoint = “The minimum range of the
pressure transducer used.
o The highest Minimum Pressure Alarm
setpoint = “The value from the Table PL
Low Pressure Setpoint” minus 2 times TO
“Tolerance””
If PL in Table 1 (T01) is set for
100 PSI and TO is set for 3.0
PSI, then the highest Minimum
Pressure setpoint would be 94
PSI
4. Scroll up (+)
or scroll down (-)
until the number is set to the value required to
maintain control of for your air system. Press
the enter
button to confirm your selection.
You should be returned to the T01 home screen
and values just entered should appear next to
the Pm parameter.
5. After you have completed adjusting the settings
on the T01 screen, press the escape
button to return to the page selection screen.
6. After you have returned to the page selection
screen press the escape
button to return
to the main screen.
TOTAL UNIT RESET AND DEFAULT VALUES
If at any time there is a requirement to reset all the
parameters and internal memory values to factory
default, this can be accomplished by using the following
procedure.
1. Press the menu
button. This will display
the Access Code Screen.
Access Code Screen
2. Enter the access code ‘9750’ but do not press
the enter
button when the last access code
character “0” is flashing.
3. When the flashing cursor is highlighting the last
“0”, press and hold the STOP
button
for 10 seconds. After 10 seconds, the controller
will reset and re-initialize.
4. All parameters, values and options will be reset
to default and the internal permanent memory
will be cleared and reset. The Default Parameters
for all X4I settings are shown in the following
lists.
TABLE #1
T01
PH High Pressure Set Point
Default Setting is: 102 PSI
PL Low Pressure Set Point
Default Setting is: 98 PSI
Pm Minimum Pressure Alarm
Default Setting is: 0 PSI
SQ Sequence Rotation Mode
Default Setting is: FILO
01 Compressor #1 Priority
Default Setting is: 1
02 Compressor #2 Priority
Default Setting is: 1
03 Compressor #3 Priority
Default Setting is: 1
04 Compressor #4 Priority
Default Setting is: 1
TABLE #2
T02
PH High Pressure Set Point
Default Setting is: 102 PSI
PL Low Pressure Set Point
Default Setting is: 98 PSI
Pm Minimum Pressure Alarm
Default Setting is: 0 PSI
SQ Sequence Rotation Mode
Default Setting is: FILO
01 Compressor #1 Priority
Default Setting is: 1
02 Compressor #2 Priority
Default Setting is: 1
03 Compressor #3 Priority
Default Setting is: 1
04 Compressor #4 Priority
Default Setting is: 1
TABLE #3
T03
PH High Pressure Set Point
Default Setting is: 102 PSI
PL Low Pressure Set Point
Default Setting is: 98 PSI
Pm Minimum Pressure Alarm
Default Setting is: 0 PSI
SQ Sequence Rotation Mode
Default Setting is: FILO
01 Compressor #1 Priority
Default Setting is: 1
02 Compressor #2 Priority
Default Setting is: 1
03 Compressor #3 Priority
Default Setting is: 1
04 Compressor #4 Priority
Default Setting is: 1
Pressure Schedule
P01
01 Schedule Setting #1
Default Setting is: -. - - : - - - - -
to
28 Schedule Setting #28
Default Setting is: -. - - : - - - - -
19
Prefill
P02
PF Prefill Function
Default Setting is: X
PT Prefill Time
Default Setting is: - MIN
PP Prefill Pressure
Default Setting is: 0 PSI
01 Compressor #1
Default Setting is: X
02 Compressor #2
Default Setting is: X
03 Compressor #3
Default Setting is: X
04 Compressor #4
Default Setting is: X
User Configuration
S01
Ct Real Time Clock Set
Default Setting is: -. - - : - -
PS Pressure Schedule Enable
Default Setting is: X
AR Auto Restart Enable
Default Setting is:
RP Rotation Interval
Default Setting is: 1. 00:00
TS Default Table Select
Default Setting is: T01
BL Display Backlit Adjust
Default Setting is: 5
Configuration
S02
P> Pressure Units
Default Setting is: PSI
NC Number Of Compressors
Default Setting is: 4
PM Maximum Pressure Alarm
Default Setting is: 145 PSI
CF Stop Control Function
Default Setting is: X
TO Tolerance
Default Setting is: 3.0 PSI
DA Damping
Default Setting is: 1.0
PC Pressure Change Time
Default Setting is: 4 MIN
AI Auxiliary Input Function
Default Setting is: 05:SS NO
AO Auxiliary Output Function
Default Setting is: 07 ON NO
ER Error Log Reset
Default Setting is: X
Sensor Calibration
S03
1O Pressure Offset
Default Setting is: 0 PSI
1R Pressure Range
Default Setting is: 232 PSI
20
/