Generac 80kW QT08046GVSN Инструкция по применению

Категория
Двигатель
Тип
Инструкция по применению
H-100 Control Panel
Operations Manual
ii H-100 Control Panel Operations Manual
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
Table of Contents
H-100 Control Panel Operations Manual iii
Section 1Safety
1.1 Introduction ..........................................................................................................................1
1.2 Safety Rules ..........................................................................................................................1
1.3 General Hazards ...................................................................................................................2
1.4 Electrical Hazards ................................................................................................................3
1.5 Fire Hazards ..........................................................................................................................3
1.6 Explosion Hazards ...............................................................................................................3
Section 2 General Information
2.1 Introduction ..........................................................................................................................5
2.2 Features ................................................................................................................................ 5
2.3 Panel Setup ...........................................................................................................................5
2.3.1 Changing the Controller Configuration .........................................................................................5
2.3.2 Customization ...............................................................................................................................6
2.4 The Measurement “Engine” ................................................................................................6
2.4.1 Analog Channels ..........................................................................................................................6
2.4.2 Analog Maths ................................................................................................................................7
2.4.3 Analog Alarms ..............................................................................................................................8
2.4.3.1 Types.................................................................................................................................... 8
2.4.3.2 Setpoints............................................................................................................................... 8
2.4.3.3 Delay Time............................................................................................................................ 8
2.4.3.4 Hysteresis............................................................................................................................. 8
2.4.3.5 Shutdown.............................................................................................................................. 8
2.4.3.6 Dialout................................................................................................................................... 8
2.4.3.7 Active When.......................................................................................................................... 8
2.4.3.8 Sensor Failure Check ........................................................................................................... 8
2.4.3.9 Shutdown on Sensor Failure................................................................................................. 8
2.4.4 Other Analog Options ...................................................................................................................9
2.4.4.1 Event Log.............................................................................................................................. 9
2.4.4.2 Analog Outputs..................................................................................................................... 9
2.4.5 Analog Sensor Ratings .................................................................................................................9
2.5 Output Functions .................................................................................................................9
2.5.1 Spare Analog Channels ................................................................................................................9
2.6 Engine Management ............................................................................................................9
2.6.1 Generator Parameters ................................................................................................................10
2.6.2 Engine Settings ...........................................................................................................................10
2.7 Voltage Regulator (Option) ...............................................................................................11
2.8 Governor (Speed Regulator) ............................................................................................. 12
2.9 Starting and Stopping Sequence Diagrams ....................................................................14
Table of Contents
Table of Contents
iv H-100 Control Panel Operations Manual
2.10 Trending ............................................................................................................................14
2.10.1 Remote Trending ......................................................................................................................14
2.10.2 Local Trending ..........................................................................................................................15
2.10.3 Genlink Local Trending Setup ..................................................................................................15
2.10.3.1 No Trigger......................................................................................................................... 15
2.10.3.2 Pre-Trigger........................................................................................................................ 15
2.10.3.3 Post-Trigger...................................................................................................................... 15
2.10.3.4 Pre- and Post-Trigger ....................................................................................................... 15
2.11 The ILC ..............................................................................................................................15
2.12 The Front Panel Display ...................................................................................................16
2.12.1 Left Display ...............................................................................................................................16
2.12.2 Right Display Pages .................................................................................................................16
2.12.3 Left Display Pages ....................................................................................................................17
2.12.4 Right Display Pages .................................................................................................................20
2.12.5 Alarms ......................................................................................................................................20
2.13 Engine ................................................................................................................................22
2.14 Status .................................................................................................................................24
2.15 Service ...............................................................................................................................26
2.16 Generator ..........................................................................................................................27
2.17 Diagnostics .......................................................................................................................29
2.18 Exercise/HTS .....................................................................................................................31
2.19 Home ..................................................................................................................................34
2.20 The Control Panel .............................................................................................................34
2.21 The Alarm Log ..................................................................................................................34
2.22 The Event Log ...................................................................................................................35
2.23 Maintenance Settings .......................................................................................................35
2.24 Air/Fuel Ratio Control (Option) .......................................................................................35
2.25 I2T Current Monitoring (Option) ......................................................................................35
2.26 Internal Exercise Function ...............................................................................................36
2.27 QuietTest® Setup Using Genlink ....................................................................................36
2.28 Normal Exercise Setup Using Genlink ...........................................................................38
2.29 QuietTest® Setup Using Front Panel ..............................................................................40
2.30 Normal Exercise Setup Using Front Panel .....................................................................44
2.31 Set Date and Time ............................................................................................................49
2.31.1 Date and Time Setup Using Genlink ........................................................................................49
2.31.2 Date and Time Setup Using Front Panel ..................................................................................50
2.32 Adjust Display Contrast ...................................................................................................50
Table of Contents
H-100 Control Panel Operations Manual v
2.33 Enable HTS Commercial Transfer Switch ...................................................................... 52
2.33.1 HTS Setup Using Genlink .........................................................................................................52
2.33.2 HTS Setup Using Front Panel ..................................................................................................52
2.34 Communications ..............................................................................................................54
2.35 Remote Annunciator Connection (Option) .................................................................... 55
2.36 GenLink-DCP ....................................................................................................................55
2.36.1 GenLink Relay Control ..............................................................................................................55
2.36.2 Set Engine Hours ......................................................................................................................55
2.36.3 Absolute Maximum Ratings ......................................................................................................55
2.36.4 Environmental Ratings ..............................................................................................................55
2.37 2A and 10A Battery Chargers ......................................................................................... 55
2.37.1 2A, 12VDC Battery Charger .....................................................................................................57
2.37.2 10A, 12VDC Battery Charger ...................................................................................................57
Section 3 Analog Functions
3.1 User Configurable Analog Inputs ..................................................................................... 59
Section 4 I/O and Connector Information
4.1 Analog Inputs .....................................................................................................................63
4.2 Digital Outputs ...................................................................................................................64
4.3 Digital Inputs ......................................................................................................................64
4.4 Digital Output Functions ...................................................................................................65
4.5 Connector Pin Descriptions ..............................................................................................69
Section 5 Internal Alarms/Warnings
5.1 Alarm Displays and Descriptions .....................................................................................71
Section 6 Emissions Interface and Operation
6.1 OBD and Modbus Register Numbers ...............................................................................73
Section 7 Ground Fault Indication
7.1 Introduction ........................................................................................................................75
7.2 Definitions ...........................................................................................................................75
7.3 Requirements .....................................................................................................................75
7.4 Associated Documents .....................................................................................................75
7.5 Functional Description ......................................................................................................75
7.5.1 Enabling Ground Fault Indication Feature ..................................................................................75
7.5.2 Initial Parameter Values ..............................................................................................................76
Table of Contents
vi H-100 Control Panel Operations Manual
7.5.3 Data Sampling and Logic Execution Rates ................................................................................76
7.5.4 DOF Control if Enabled ..............................................................................................................76
7.5.5 AI Control if Enabled ...................................................................................................................76
7.6 GENLINK GFI Configuration Screen .................................................................................76
7.6.1 GFI enable ..................................................................................................................................77
7.6.2 GFI Screen's System Generated Fields .....................................................................................77
7.6.2.1 Generator Rated Current (RMS Amps)............................................................................... 77
7.6.2.2 Generator Average Current (RMS Amps)........................................................................... 77
7.6.2.3 Generator Gnd + Neutral Current (RMS Amps).................................................................. 77
7.6.3 GFI Field Editable Parameters ...................................................................................................77
7.6.3.1 Gnd + Neutral Current Threshold (RMS Amps).................................................................. 77
7.6.3.2 Gnd + Neutral Current Hysteresis (RMS Amps)................................................................. 77
7.6.3.3 Gnd + Neutral Fault Delay(s).............................................................................................. 77
7.6.3.4 Analog Input Channel Assignment (chan_ID)..................................................................... 77
7.6.3.5 Digital Output Function Assignment (chan_ID)................................................................... 77
7.6.4 Apply Button ...............................................................................................................................78
7.6.5 Print Button .................................................................................................................................78
7.6.6 Close Button ...............................................................................................................................78
7.6.7 GENLINK GFI Configuration Help Screen Information ...............................................................78
7.7 Basic Setup Instructions ...................................................................................................79
7.7.1 GFI Configuration Default Setup ................................................................................................79
7.7.2 GFI DOF Default Setup ..............................................................................................................79
H-100 Control Panel Operations Manual 1
Section 1Safety
1.1 — Introduction
Read this manual thoroughly. If any portion is not understood, contact the nearest Authorized Service Dealer for
clarification. The manufacturer also requires having an Authorized Service Dealer oversee the installation of any
standby generator set. Trained/qualified service technicians familiar with the control systems and available options
have full access to drawings, publications, and other information required for a successful installation.
1.2 — Safety Rules
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION, and
NOTE boxes are used to alert personnel to special instructions about a particular operation that may be hazardous if
performed incorrectly or carelessly. Observe them carefully. They indicate:
Indicates a hazardous situation or action that, if not avoided, will result in death or serious
injury.
Indicates a hazardous situation or action that, if not avoided, could result in death or seri-
ous injury.
Indicates a hazardous situation or action that, if not avoided, could result in minor or mod-
erate injury.
NOTE: Notes provide additional information important to a procedure or component.
These safety warnings cannot eliminate the hazards they indicate. Observing safety precautions and strict compliance
with the special instructions while performing the action or service are essential to preventing accidents.
Four commonly used safety symbols accompany DANGER, WARNING, and CAUTION boxes and the type of informa-
tion each indicates:
This symbol points out important safety information that, if not followed, could
endanger personnel and/or property.
This symbol represents the potential for an Explosion Hazard.
This symbol represents the potential for a Fire Hazard.
This symbol represents the potential for an Electrical Shock Hazard.
SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be
followed during installation of the generator set and batteries. The manufacturer suggests
that these safety rules be copied and posted in potential hazard areas. Safety should
be stressed to all installers, operators, potential operators, and service and repair
technicians for this equipment.
$
!
+
Safety
2H-100 Control Panel Operations Manual
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this
manual, and on tags and decals affixed to the unit, are not all-inclusive. If using a procedure, work method, or operating
technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the pro-
cedure, work method, or operating technique used does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance, or
being careless can cause possible injury or death. Permit only responsible and capable persons to install, oper-
ate, and maintain this equipment.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
If this generator is used to power electrical load circuits normally powered by a utility power source, install a
transfer switch. The transfer switch must effectively isolate the electrical system from the utility distribution sys-
tem when the generator is operating. Failure to isolate an electrical system by such means will result in damage
to the generator and also may result in injury or death to utility power workers due to backfeed of electrical
energy.
Generators produce potentially lethal voltages. Ensure all steps are taken to make the genera-
tor safe before operation or service.
1.3 — General Hazards
For safety reasons, the manufacturer recommends that this equipment be installed, serviced, and repaired by an
Authorized Service Dealer or other competent, qualified electrician or installation technician who is familiar with
all applicable codes, standards, and regulations.
Ensure that the generator is installed, operated, and serviced in accordance with the manufacturer’s instructions
and recommendations. Following installation, do nothing that might render the unit unsafe or in noncompliance.
The engine exhaust fumes contain carbon monoxide, which can be DEADLY. If breathed in sufficient concentra-
tions, carbon monoxide can cause unconsciousness or even death. For this reason, adequate ventilation must
be provided. Exhaust gases must be piped safely away from any building or enclosure that houses the generator
to an area where people, animals, etc. will not be harmed.
Keep hands, feet, clothing, etc. away from drive belts, fans, and other moving or hot parts. Never remove any
drive belt or fan guard while the unit is operating. Ensure that all guards, covers, and protective devices removed
during maintenance or service are reinstalled.
Adequate, unobstructed flow of cooling and ventilating air is critical to prevent buildup of explosive gases and to
ensure correct generator operation. Do not alter the installation or permit even partial blockage of ventilation pro-
visions, as this can affect safe operation of the generator.
Keep the area around the generator clean and uncluttered. Remove any materials that could become hazardous.
When working on this equipment, remain alert at all times. Never work on the equipment when physically or men-
tally fatigued.
Inspect the generator regularly, and promptly repair or replace any worn or damaged components using only fac-
tory approved parts and procedures.
Before performing any maintenance on the generator, always disconnect the battery cables to prevent accidental
startup. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG, or (–) first, then remove the
POSITIVE, POS, or (+) cable. When reconnecting the cables, connect the POSITIVE cable first, the NEGATIVE
cable last.
Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may
result in exhaust, fuel, oil or coolant leaks.
+
Safety
H-100 Control Panel Operations Manual 3
1.4 — Electrical Hazards
All generators produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers
extremely high and dangerous voltages to the transfer switch as well as the generator when it is in operation.
Avoid contact with bare wires, terminals and other connections. Ensure all covers, guards, and barriers are in
place, and that they are properly secured and/or locked before operation. If work must be done around an oper-
ating unit, stand on an insulated, dry surface to reduce potential shock hazard.
Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
If it is necessary to stand on metal or concrete while installing, operating, servicing, or repairing this equipment,
lay down a dry wooden platform and cover with insulated mats before beginning.
Verify that the generator is properly grounded.
Wire gauge sizes of electrical wiring, cables, and cord sets must be adequate to handle the maximum electrical
current (ampacity) to which it will be subjected.
Before installing or servicing equipment, verify that all power voltage supplies are positively turned off at their
sources. Failure to do so can result in hazardous and possibly fatal electrical shock.
Connecting this unit to an electrical system normally supplied by an electric utility is by means of a transfer switch
so as to isolate the generator electric system from the electric utility distribution system when the generator is
operating. Failure to isolate the two electric system power sources from each other by such means will result in
damage to the generator and may also result in injury or death to utility power workers due to backfeed of electri-
cal energy.
Generators installed with an automatic transfer switch will crank and start automatically when NORMAL (UTIL-
ITY) source voltage is removed or is below an acceptable preset level. To prevent automatic startup and possible
injury, disable the automatic start circuit (battery cables, etc.) before working on or around the unit. Place a “DO
NOT OPERATE” tag on the generator control panel and on the transfer switch.
In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not
possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use
a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is
unconscious, apply first aid and get immediate medical help.
Do not wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock,
or may get caught in moving parts resulting in injury.
1.5 — Fire Hazards
Keep a fire extinguisher near the generator at all times. Keep the extinguisher properly charged and be familiar
with its use. Direct any questions to the local fire department.
NOTE: DO NOT use any carbon tetra-chloride type fire extinguishers. These fire extinguishers emit toxic fumes
and the liquid can damage wiring insulation.
1.6 — Explosion Hazards
Properly ventilate the room or building housing the generator to prevent buildup of explosive gas.
Do not smoke around the generator. Immediately wipe up any fuel or oil spills. Ensure that no combustible mate-
rials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result.
Keep the area surrounding the generator clean and free of debris.
All types of fuels are potentially FLAMMABLE and/or EXPLOSIVE and must be handled with care. Inspect the
fuel system frequently and correct any leaks immediately. Be sure fuel supply lines are properly installed, purged,
and leak tested before placing the generator set into service.
Safety
4H-100 Control Panel Operations Manual
This page intentionally left blank.
H-100 Control Panel Operations Manual 5
Section 2 General Information
2.1 — Introduction
The H-100 Control Panel is an electronic control box that functions as an advanced standby generator controller. Its
technology is based on the flagship PM-DCP system with all its flexibility included. A familiar user interface in the form
of GenLink®-DCP is used to program, monitor and change the parameters in the unit. The interface appears the same
as it does for the PM-DCP.
Specialized programs are built into the H-100 Control Panel to allow customers to configure spare I/O to their own
needs. For example, built in Integrated Logic Controller (ILC) logic can eliminate the need for ancillary external control-
lers. Everything can be user customized from measurements to alarms to special functionality.
Why do we do this? Having one set of control firmware buys us the economy of scale which can be passed on to the
customer. It also has great technical advantages. The H-100 Control Panel and all PM-DCP products are built around a
common “core” of firmware. This provides EVERY product with the same technical tools. For example, both the H-100
Control Panel and PM-DCP products can call out for assistance via a modem, every product can provide trending data
for its measured parameters, any measured value can be setup to create alarms or warnings, each product has a built
in ILC, etc. H-100 Control Panel is very flexible.
2.2 — Features
Local/remote connection to a PC for GenLink®-DCP communication.
Interface with up to four HTS Commercial Transfer Switches.
Interface with up to two Remote Annunciator Panels.
New Generation GenLink.
Built-in Frequency and Voltage controller.
External modem option with dialout capability upon alarm.
Communication via standard CAN bus and Modbus protocols.
Programmable I/O channel properties.
Programmable alarm/warnings.
Alarm and event logging with time stamping.
Parameter logging and trending both to file and graphical.
Built-in diagnostics.
Internal ILC for combinatorial logic functions including analog inputs.
Spare customer programmable Analog input capacity.
Spare customer programmable Digital I/O capacity.
Firmware can be updated via Telephone line.
2.3 — Panel Setup
2.3.1— Changing the Controller Configuration
The H-100 Control Panel controller is setup in the factory to match the product it is shipped with and generally no
changes are required. For spares purposes the controller can be re-configured in the field using the GenLink software
tool and a PC.
If you need to change the function of the panel, the best way to get a basic setup for a product is to use GenLink to
download a “product file”. This will setup all the basic parameters and just leave customization and calibration to be
done. Product files are available on the web site for downloading cross referenced to product serial numbers/generic
product types. The manufacturer does not recommend changing the settings individually for a product as this is labori-
ous and prone to human error. Some of the settings require detailed knowledge of things like governor settings which
are not easily discernable.
General Information
6H-100 Control Panel Operations Manual
Some configurations are changeable from the H-100 Control Panel touch pad and displays. These configurations will
be described later and include:
Setting Display Contrast
Setting System Time and Date
Setting Up/Enabling Internal Exercise
Enabling Interface with HTS Commercial Transfer Switch
2.3.2— Customization
The controller is designed to be very flexible and allow great levels of customization via the GenLink tool. Once you
have customized your controller, you should save the settings for backup. This can be done during the customization
process, or at any time subsequent to customization by uploading the settings from the controller to GenLink and then
saving them. The digital outputs can be set to turn on from any one of a list of functions or they can be used as part of
the built-in ILC. The digital inputs can be moved, inverted, renamed, made alarms, used in the ILC, logged/not logged,
etc. Refer to the section “MEASUREMENT ENGINE” for details. Analog inputs are dealt with in the same section.
There are some parameters which are specific to the product, such as an engine controller or transfer switch. These
are all customizable via GenLink. Refer to the relevant section for details.
2.4 — The Measurement “Engine”
The measurement “engine” is the key feature of the system. All the inputs to the controller are processed by this mod-
ule. Each physical input is measured and the result processed by an individual set of rules that are set via a PC and
GenLink. Normally, a product is delivered with the inputs and outputs pre-configured and nothing needs to be done,
however the manufacturer has provided complete flexibility to each measurement (except where product safety is con-
cerned). The inputs are divided into analog and digital channels.
2.4.1— Analog Channels
There are 23 analog channels of which 14 have fixed functions. The remaining 9 channels are split between product
specific inputs (such as oil temperature), and customer spares. The exact split depends on the product. Table 1 shows
the channel allocation.
Some of the 14 fixed channels are “derived” readings in that they are calculated from the other readings. For example,
power is calculated from both voltage and current. These are not real hardware channels, but they result in an analog
reading that can be treated as a “fixed channel” just like any other.
CPU
Channel No. Channel Title Update Rate Derived
Value
7 User Configurable #1 (Usually Oil Temp) 3.84 ms No
8 User Configurable #2 (Usually Coolant Temp) 3.84 ms No
9 User Configurable #3 (Usually Oil Pressure) 3.84 ms No
10 User Configurable #4 (Usually Coolant Level) 3.84 ms No
11 User Configurable #5 (Usually Fuel level) 3.84 ms No
12 User Configurable #6 (Usually Spare) 3.84 ms No
13 User Configurable #7 (Usually Throttle Position) 3.84 ms No
14 Special Oxygen Sensor 192 µs No
15 Special Battery charge Sensor 3.84 ms No
16 Battery Voltage/PSU Voltages 3.84 ms No
1 Generator Phase A RMS Current Phase A ZERO CROSSING No
2 Generator Phase B RMS Current Phase B ZERO CROSSING No
3 Generator Phase C RMS Current Phase C ZERO CROSSING No
General Information
H-100 Control Panel Operations Manual 7
2.4.2— Analog Maths
Each of the 23 channels is processed by a set of measuring rules using constants that are set via GenLink. Usually
these constants can be changed by the customer. In the following illustration, the measurement is represented by M
and the GenLink constants are in italics. The measurement is processed in the following order and the result is then
stored for customer display or use.
M = M * Calibration Factor
This is used to calibrate out any reading inaccuracies where calibration factor is a number such that 1024 is equivalent
to 1, so it’s really M * calibration factor/ 1024. GenLink will hide this computation so you can enter floating point num-
bers such as 1.1 or 0.987 etc.
THEN
M = M processed by function “x”
Where the function “x” can be:
The function “x” may use any of the coefficients 1, 2, or 3, and in some cases will use calibration factor as a 4th coeffi-
cient (in that case use scaling factor for calibration). The coefficients are used to allow adjustment of the basic functions
to cater to future or alternate sensors. They perform different tasks in different functions, see Section 3 Analog Func-
tions for further details. Note that if calibration factor is used as a coefficient, it will be shown (and entered) by GenLink
as (actual coefficient/1024).
For example, if the coefficient is -378, it will be displayed as
-0.36914.
THEN
M =M * Scaling Factor:
Where scaling factor is a number such that 1024 is equivalent to 1, so it’s really M * scaling factor/1024. GenLink will
hide this computation so you can enter floating point numbers such as 2.1 or 0.987 etc.
- Generator Average Current Every Phase ZERO CROSSING Yes
4 Generator Phase A RMS Voltage Phase A ZERO CROSSING No
5 Generator Phase B RMS Voltage Phase B ZERO CROSSING No
6 Generator Phase C RMS Voltage Phase C ZERO CROSSING No
- Generator average voltage Every Phase ZERO CROSSING Yes
- Total Generator Power KW Every Phase ZERO CROSSING Yes
- Total Generator Power Factor Every Phase ZERO CROSSING Yes
- Generator Frequency Every Phase ZERO CROSSING Yes
- RPM #1 4-8 ms Variable No
- Air/Fuel Ratio Control % Duty Cycle 100ms No
1. THERMISTOR 5. UNALTERED 9. POLY_1ST_N1
2. CURRENT 6. POLY_3RD 10. POLY_1ST_N2
3. LINEAR 7. POLY_2ND 11. CAL_SCALE
4. PRESSURE 8. POLY_1ST 12. CFM_SENSOR
CPU
Channel No. Channel Title Update Rate Derived
Value
General Information
8H-100 Control Panel Operations Manual
2.4.3— Analog Alarms
Each of the 23 channels is processed by a set of alarm rules using constants that are set via GenLink. Usually these
constants can be changed by the customer. Note that all alarms and warnings will be entered into the alarm log and will
operate the audible alarm. The following list shows the alarm properties.
2.4.3.1— Types
This section is used to turn alarms and warnings on or off and define if the input must be greater than a value (GT) or
less than a value (LT). There can be up to 2 alarms and 2 warnings, of which there can be a maximum of 2 GT or 2 LT
types.
2.4.3.2— Setpoints
There can be up to 4 setpoints to support 2 alarms and 2 warnings, of which there can be a maximum of 2 GT or 2 LT
setpoints. The setpoints are in the same units that the measurement is displayed in on the Analog Channels Diagnostic
screen.
2.4.3.3— Delay Time
There are 2 delay fields that can be set with different times in each. Any or none of these times can be applied to any of
the alarms or warnings via GenLink radio buttons.
For example, a measurement may have to be greater than the setpoint for 1 second to cause an alarm, or less than
another setpoint for 2 seconds to cause a warning. The resolution of this time interval is 0.1 seconds.
2.4.3.4— Hysteresis
Applied hysteresis in display or final units (for example battery voltage is displayed in units of 1/100ths of a volt). When
an alarm/warning has gone active, the hysteresis is subtracted from the GT setpoint or added to the LT setpoint to cal-
culate the modified setpoint needed to make the alarm go inactive.
2.4.3.5— Shutdown
When set, this alarm condition (alarms only, not warnings) has been selected to shutdown the engine.
2.4.3.6— Dialout
When this field is set, the dialout feature is selected. If an alarm or warning occurs for this channel the controller will
automatically call for assistance via telephone (if the external modem option is fitted). Dialout can be selected either for
warnings, alarms, neither, or both. There is a predefined and prioritized list of 10 phone numbers that will be tried. The
controller expects GenLink to answer the call and log the fault. It is possible for the customer to program any Modbus
device with a modem to respond to the call.
2.4.3.7— Active When
You can select other criteria to determine when alarms and warnings become enabled. This is further divided in that
you can define these criteria independently for LT and GT alarm types.
ALWAYS ENABLED = This alarm or warning is always enabled under every circumstance.
HOLD OFF = Alarms/Warnings with this qualification only become enabled after a programmable hold off time has
been met. The hold off timer starts after the engine has started. Stopping the engine cancels the hold off timer.
IMMEDIATE = Alarms/Warnings with this qualification only become enabled immediately after the engine has
started.
2.4.3.8— Sensor Failure Check
When this field is set, the input sensor is checked for short circuit or open circuit failure.Normally each of the inputs are
conditioned externally to be 4-20mA current loops. Any currents outside this range indicate a sensor failure.This will
cause an alarm to occur. The alarm can be selected to shutdown the engine if so desired via the next field. The alarm
will be entered in the alarm log.
2.4.3.9— Shutdown on Sensor Failure
When this field is set, the engine will shut down if there is a sensor failure. If the field is unchecked, the failure will just
cause an alarm message to appear and the audible alarm to sound. The alarm will be entered in the alarm log.
General Information
H-100 Control Panel Operations Manual 9
2.4.4— Other Analog Options
2.4.4.1— Event Log
When set, the channel measurement is compared to the setpoint with one of the GT or LT family of options. Once the
condition is met (eg. measurement GT setpoint) the event is logged along with a date/time stamp into the volatile mem-
ory based event log. Six other parameters, that can be chosen by the customer, will also be logged. Volatile means that
when power is removed from the controller, the event log will be lost.
2.4.4.2— Analog Outputs
There are no analog outputs available for customization on an H-100 controller.
2.4.5— Analog Sensor Ratings
Typically the sensors used by the manufacturer have the following ratings:
2.5 — Output Functions
Output functions are flags that are set/reset by the internal program to indicate a certain status, for example “Engine
Running”. The Measurement Engine allows these flags to be treated as “channels” that can be made into alarms/warn-
ings, display messages, operate real outputs and also be fed as inputs to the ILC. For example, use the “Ready To
Start” output function to operate a relay by mapping it to a physical output via GenLink, or you could feed it into the ILC
to do combinatorial logic.
See TABLE OF OUTPUT FUNCTIONS in Section 4 I/O and Connector Information.
2.5.1— Spare Analog Channels
Depending upon the particular configuration of your product, the following input channels may be available for custom
measurements:
2.6 — Engine Management
The engine management module is very similar to that used in the manufacturer's other products. It controls engine
cranking, engine starting, engine running and engine stopping. These functions are performed to a set of “rules” that
can be customized via parameters from GenLink. In turn, the module needs to know certain things about the engine
which it expects to be programmed in from GenLink.
Temperature 35 - 300° F
Pressure 0 - 150 psi
Channel # Normal Function
4 Coolant Level
5 Fuel Level
6 Ignition Module Alarm
7 Throttle Position
8 Oxygen Sensor 0-1 VDC
9 Battery Charge Current 0-5 VDC
General Information
10 H-100 Control Panel Operations Manual
2.6.1— Generator Parameters
Engine Flywheel Teeth— Number of flywheel teeth or pulses per revolution for RPM input. RPM 1 is used for the
engine speed.
CT Ratio/Generator—Current Transformer ratio for the generator. This value is the result from reducing the CT
ratio. E.G. If the CT ratio is 100 amps to 5 amps, the resulting value is 20. Normally, the CT ratio will be x amps to
1 amp on H-100 Control Panels.
Generator Phase Configuration— Select either single-phase or three-phase configuration depending on how the
unit is supplied.
60 Hertz RPM— The engine RPM needed to supply 60 Hertz power.
NOTE: 60 Hertz RPM value is used for both 50Hz and 60Hz - Do Not Change!
QuietTest® RPM— The engine RPM used when running QuietTest®.
2.6.2— Engine Settings
All of the following times are in seconds:
Preheat Time— The time preheat is applied for before cranking if enabled.
Start Detection RPM— The Engine must reach this RPM before disengaging the starter.
Crank Time— The maximum time in seconds that each crank will last
Alarm Hold-off Time— The time after starting at which the hold-off alarms become enabled.
Engine Warm up Time— The engine will run for at least this time before issuing the “Accept load” signal.
Target Frequency— The target generator frequency (Hz).
Target Voltage— The target generator voltage (RMS).
Preheat Enable—The following four options are selectable (only for Diesel):
- Preheat disabled.
- Preheat before cranking.
- Preheat during cranking.
- Preheat before and during cranking.
The Preheat output pin shares its function with the Air/Fuel Solenoid output.You must choose one of the two
functions as follows:
- To select Air/Fuel- set the “Diesel” parameter on the governor settings page to “No”. Set Preheat to “Dis-
abled”
- To select Preheat- set the “Diesel” parameter on the governor settings page to “Yes”. Set Preheat to one of
the enable selections.
Engine Cool down Time— The generator will run for at least this time after remote start becomes inactive.
Pause Between Cranks Time— The time between each successive crank operation.
Number of Start Attempts— The maximum number of times the engine will attempt to start (crank) before faulting
out with overcrank.
Load Accept Frequency— The generator must reach this frequency before issuing the “Accept load” signal.
Load Accept Voltage—The generator must reach this voltage before issuing the “Accept load” signal.
Number Parameter Units
1 Engine Flywheel Teeth Teeth
2 CT Ratio - Generator -
3 Generator Phase Configuration 1 or 3
460 Hertz RPM RPM
5 QuietTest® RPM RPM
General Information
H-100 Control Panel Operations Manual 11
2.7 — Voltage Regulator (Option)
All panels include automatic voltage regulation as standard. There are various settings that can be made to the voltage
regulator via GenLink. The settings are normally factory preset and are shown here for completeness.
Voltage KP/KI/KD— Voltage regulation stability constants.
PMG— YES indicates a Permanent Magnet Excited alternator.
VF Corner— Used for v/f control to reduce the output voltage when a large load is applied that slows down the
generator. If the frequency drops below this setpoint, the voltage is reduced proportionally as the frequency
drops according to the Volts per Hertz ratio.
Panel Type— Indicates the panel type that the H-100 Control Panel has been programmed to be. It will normally
be H-100.
Volts per Hertz— Number of volts to reduce the generator voltage for each hertz below VF Corner frequency.
AVR Dump Improve— Makes the regulator module increase the gain temporarily on a load dump to improve the
transient voltage response.
Unit Rated Power— This is the generator’s rated power in kW.
Number Parameter Units
1 Preheat Time (S)econds
2 Start Detection RPM RPM
3 Crank Time S
4 Alarm Hold-Off Time S
5 Engine Warm Up Time S
6 Target Frequency Hz
7 Target Voltage Vrms
8 Preheat Enable -
9 Engine Cool Down Time S
10 Pause Between Cranks Time S
11 Number of Start Attempts -
12 Load Accept Frequency HZ
13 Load Accept Voltage Vrms
Voltage Regulator (Option) Chart
Number Parameter Units
1Voltage KP -
2Voltage KI -
3Voltage KD -
4 Excitation Type DPE/PMG
5 VF Corner Hertz
6 Panel Type H-100
7 Volts per Hertz V/Hertz
8 AVR Load Dump Improve None/Enabled/8-Cycle
9 Unit Rated Power kW
General Information
12 H-100 Control Panel Operations Manual
2.8 — Governor (Speed Regulator)
All panels include automatic frequency (speed) regulation as standard. There are various settings that can be adjusted
for the governor via GenLink, these include the target frequency. The settings are normally factory preset and are
shown here for completeness, they do not apply to all governor types.
Standby KP,KI,KD— Frequency regulation stability constants used for normal mode operation.
QuietTest® KP,KI,KD— Frequency regulation stability constants used for QuietTest® mode operation.
Actuator Type— Indicates the type of governor actuator. The following types are available:
- POWERFLOW— Barber Coleman Powerflow, voltage driven without position feedback
- BOSCH GAS— Bosch Butterfly, current driven with position feedback
- LINEAR CURRENT— Linear, Current Driven without position feedback
- DETROIT DIESEL— Detroit diesel PWM Driven
- HORIZONTAL DIESEL—Diesel Rack Arm with Horizontal Connecting Rod and current driven with position feed-
back
- VERTICAL DIESEL— Diesel Rack Arm with Vertical Connecting Rod and current driven with position feedback
- JOHN DEERE J1939 CAN— Controls speed by J1939 CAN bus commands using John Deere protocol
- VOLVO J1939 CAN— Controls speed by J1939 CAN bus commands using Volvo protocol
- HINO (do not use)— Not implemented; DO NOT USE.
- FPT NEF J1939 CAN— Controls speed by J1939 CAN bus commands using Fiat NEF protocol
- FPT CURSOR J1939 CAN— Controls speed by J1939 CAN bus commands using Fiat Cursor protocol
- PERKINS J1939 CAN— Controls speed by J1939 CAN bus commands using Perkins protocol
- HORIZONTAL GAS— Gas Butterfly Throttle Arm with Horizontal Connecting Rod and current driven with position
feedback
Actuator Offset— Number corresponding to lowest actuator position (Close Throttle).
Actuator Fullscale— Number corresponding to highest actuator position (Open Throttle).
Actuator Normal Start Position— The position the actuator will be parked at from start up until the “Start detection
RPM” is reached. If “soft start” is enabled, this is also the maximum position of the throttle until the Target Frequency
minus 3 Hz is reached. Therefore, if “soft start” is enabled, the actuator start position MUST be high enough to reach
Target Frequency minus 3 Hz.
Actuator QuietTest® Start Position— The position the actuator will be parked at from start up until the “Start detection
RPM” is reached. If “soft start” is enabled, this is also the maximum position of the throttle until the QuietTest® Target
Frequency minus 3Hz is reached. Therefore, if “soft start” is enabled, the actuator start position MUST be high
enough to reach, QuietTest® Target Frequency minus 3 Hz.
Soft Start Time— The time to stay at each soft start step before moving onto the next step. (Only applies if soft start
is enabled).
Soft Start Frequency— An entry of 0 Hz disables soft start. Any other value enables soft start which ramps up the
generator frequency at a rate determined by “Soft Start Time” to minimize smoke. This value selects the first fre-
quency to target after start up. Once this frequency is attained, the generator will hold this frequency for the “Soft
Start Time” and then move to the next step. Each step is 3 Hz higher with the final step being “Target Frequency”
minus 3 Hz. Each step is held for the “Soft Start Time”. During soft start, the throttle will not be allowed to exceed the
“Actuator Start Position”. Therefore, choose a start position that will allow the generator to attain full operating speed.
Diesel— Indicates if this is a diesel powered generator. This modifies such features as frequency control, and others.
Dump Enable—Indicates if extra load dump governor compensation is desired to reduce increase in frequency
caused by drop in load. The following three selections are available:
-No Dump— No additional compensation.
-Dump— Reset governor algorithm when load dump detected.
-Dump & Hold— Same as Dump, but also hold throttle closed until frequency back in range.
NOTE: This option will likely produce undesired frequency dips on load dumps.
General Information
H-100 Control Panel Operations Manual 13
Engine Linearization— Selects engine torque to actuator position translation curve for Bosch Actuators.
0 = No conversion— torque = position
1 = Butterfly Actuator with minimum position same as unpowered actuator
2 = Diesel arm with Horizontal rod
3 = Diesel arm with Vertical rod
4 = Same as 1, but minimum position at actuator mechanical stop
5 = Same as 4, but with limited position resolution of 1
6 = Same as 4, but with added energy to accommodate throttles that normally operate in the nearly closed posi-
tion at no load
7 = Same as 6, but with limited position resolution of 1
8 = Same as 4, but with a graduated energy profile based on position to increase stability at all loads
Governor Limit Type— Choose whether to use an integral limit or an anti-windup strategy.
Anti-Windup = an anti integral windup strategy is applied to the integral based on the “Governor Limit Value”
below.
Integral Limit = the Governor Integral is limited to the “Governor Limit Value” below.
Governor Limit Value— If “Integral Limit” is selected, this is the maximum value the integral is allowed. If “Anti-
Windup” is selected, this is the integral value above which the anti-windup algorithm becomes active.
PWM Counts per Ampx10—Number of PWM counts required to drive one tenth of an amp into a linear current driven
actuator. This only applies to the “Linear Current” actuator type.
Desynch. Offset— Offset of –0.9 to +0.9 Hertz to be applied to the target frequency to improve passive synchroniz-
ing by Automatic Transfer Switches. If an in-phase or synchronized transfer is required, use this setting to adjust the
generator frequency to 0.1 Hz above nominal Utility frequency.
Sensor Source— Indicates whether to use Engine Speed or Generator Frequency to govern speed. This should only
be “Flywheel” when severe electrical noise distorts the alternator frequency signal.
Governor (Speed Regulator) Option Chart
Number Parameter Units
1 Standby KP -
2 Standby KI -
3 Standby KD -
4 QuietTest® KP -
5 QuietTest® KI -
6 QuietTest® KD -
7 Actuator Type -
8 Actuator Offset -
9 Actuator Fullscale -
10 Actuator Normal Start Position -
11 Actuator QuietTest® Start Position -
12 Soft Start Time Seconds
13 Soft Start Frequency Hz
14 Diesel YES/NO
15 Dump Enable -
16 Engine Linearzation -
17 Governor Limit Type Anti-Windup/Integral Limit
18 Governor Limit Value -
19 WM Counts per Ampx10 -
20 Desynch. Offset Hz
21 Sensor Source Alternator/Flywheel
General Information
14 H-100 Control Panel Operations Manual
2.9 — Starting and Stopping Sequence Diagrams
2.10 — Trending
Just like in the PM-DCP, there are two types of trending available- Remote and Local.
2.10.1— Remote Trending
GenLink performs remote trending by polling the controller for the selected data at the desired rate. Up to 16 analog
channels can be visually monitored at a 0.3 second rate. If a faster rate is desired, reducing the number of analog
channels monitored will allow for a 0.1 second rate. The polling rate can be varied from 0.1 seconds to several hours.
GenLink can save the time stamped data to a file and/or display it as a near real-time graph. The file is MS Excel com-
patible (CSV format). Examples of things you can trend are the generator frequency response (in 0.1 second steps) to
a block load or Generated power over a day. When saving to a file in normal mode, all 23 analog channels are saved.
When saving to a file in fast mode, only the displayed analog channels are saved.
NO
NO
Remote start
contacts
CLOSED?
Start the
Engine
At load
accept limits?
Warm up
timer expired?
Issue load
accept signal
Remote start
contacts OPEN?
Cool down
timer expired?
Stop the
Engine
NO
NO
NO
NOTE: Shutdown Alarms will cause
the engine to turn off or not start.
2-wire Remote Starting and Stopping
Sequence Key switch in Auto Position
Time to
exercise?
Start the
Engine
Exercise time
expired?
Stop the
Engine
NO
NO
HTS indicates
loss of
Utility?
Start the
Engine
At load
accept limits?
Warm up
timer expired?
Command HTS
to transfer to
Generator Power
HTS indicates
return of Utility?
Cool down
timer expired?
Stop the
Engine
NO
NO
NO
NO
NO
NOTE: Shutdown Alarms will cause
the engine to turn off or not start.
Exercise without transfer starting and
stopping sequence key switch in auto
position.
NOTE: A Remote Start signal will ter-
minate exercise and proceed to nor-
mal running mode.
Loss of utility with HTS starting and
stopping sequence key switch in auto
position.
NOTE: Shutdown Alarms will cause
the engine to turn off or not start.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176

Generac 80kW QT08046GVSN Инструкция по применению

Категория
Двигатель
Тип
Инструкция по применению

Задайте вопрос, и я найду ответ в документе

Поиск информации в документе стал проще с помощью ИИ

на других языках