SICK WS/WE190L Standard Инструкция по эксплуатации

Тип
Инструкция по эксплуатации
A
English
Photoelectric retro-reective sensor
with laser light
Operating instructions
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
Safety specifications
Read the operating instructions and the assembly instructions before
starting operation.
Connection, assembly and settings only by competent technicans.
Protect the device against moisture and soiling when operating.
No safety component in accordance with EU machine guidelines.
a Caution
Use of controls or adjustments or performance of pro-
cedures other than those specied herein may result in
hazardous radiation exposure.
Proper use
The WS / WE190L through-beam photoelectric switch is an optoelectronic
sensor, that operates using a transmission unit (WS) and reception unit
(WE). It is used for optical, noncontact detection of objects, animals, and
people.
Starting operation
1 The devices WS / WE190L have complementary switching outputs:
WE190L-P only:
Q: dark-switching, if light interrupted, output HIGH,
Q: light-switching, if light interrupted, output LOW.
WE190L-N only:
Q: dark-switching, if light received, output LOW,
Q: light-switching, if light received, output HIGH.
2 The following apply for connection in B: brn = brown, blu = blue,
blk = black, wht = white.
Connect cables.
3 Use mounting holes (supplied) to mount WS and WE opposite each
other and align roughly. Adjust for scanning range (see technical data
at end of these operating instructions and see diagram; x=scanning
range, y=operating reserve).
Connect WS and WE to operating voltage (see type label).
Adjustment of light reception:
Determine the on / o points of the LED signal strength indicator
(LED yellow) by swiveling the photoelectric reex switch horizontally
and vertically. Select the middle position, so that the red sender beam
hits the reector center. The yellow LED lights continuously.
Maintenance
SICK photoelectic sensors do not require any maintenance.
We recommend doing the following regularly:
- clean the external lens surfaces
- check the screw connections and plug-in connections
No modications may be made to devices.
Subject to change without notice. Specied product properties and technical
data are not written guarantees.
Deutsch
Reexions-Lichtschranke
mit Laserlicht
Betriebsanleitung
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximale Pulsleistung: 2 mW
Impulsdauer: 4 µs
Wellenlänge: 655 nm
Entspricht 21 CFR 1040.10
und 1040.11 mit Ausnahme von
Abweichungen nach
Laser-Hinweis 50, 24. Juni 2007
Laserstrahlung
NICHT IN STRAHL BLICKEN
KLASSE 2 LASERPRODUKT
Sicherheitshinweise
Kein Sicherheitsbauteil gemäß EU-Maschinenrichtlinie.
Vor der Inbetriebnahme die Betriebsanleitung lesen.
Anschluss, Montage und Einstellung nur durch Fachpersonal.
Gerät bei der Inbetriebnahme vor Feuchte und Verunreinigung schützen.
a Vorsicht
Die Verwendung anderer Steuerungen, Einstellungen
oder Vorgehensweisen als hier beschrieben kann zu
gefährlicher Strahlenexposition führen.
Bestimmungsgemäße Verwendung
Die Einweg-Lichtschranke WS / WE190L ist ein optoelektronischer Sensor,
der mit einer Sende- (WS) und Empfangseinheit (WE) arbeitet. Sie wird zum
optischen, berührungslosen Erfassen von Sachen, Tieren und Personen
eingesetzt.
Inbetriebnahme
1 Die Geräte WS / WE190L haben antivalente Schaltausgänge:
Nur WE190L-P:
Q: dunkelschaltend, bei Lichtunterbrechung Ausgang HIGH,
Q: hellschaltend, bei Lichtunterbrechung Ausgang LOW.
Nur WE190L-N:
Q: dunkelschaltend, bei Lichtempfang Ausgang LOW,
Q: hellschaltend, bei Lichtempfang Ausgang HIGH.
WS / WE190L
Sensing range max. Schaltabstand max. Portée max. Distância de comutação max. 50 m
Light spot diameter / distance Lichtfleckdurchmesser / Entfernung Diamètre de la tache lumineuse / distance Diâmetro do ponto de luz / distância 40 mm / 10 m
Supply voltage U
B
Versorgungsspannung U
B
Tension d‘alimentation U
B
Tensão de alimentação U
B
10 ... 30 V DC
1)
Output current I
max
Ausgangsstrom I
max
Courant de sortie I
maxi
Corrente de saída I
máx.
< 100 mA
Response time Ansprechzeit Temps de réponse Tempo de reação < 0.5 ms
Switching frequency Schaltfrequenz max. Fréquence max. Sequência max. de sinais 1000 / s
Enclosure rating Schutzart Type de protection Tipo de proteção IP 67
Protection class Schutzklasse Classe de protection Classe de proteção
Circuit protection Schutzschaltungen Circuits de protection Circuitos protetores A, B
2)
Ambient operating temperature Betriebsumgebungstemperatur Température ambiante Temperatura ambiente de operação –10 ... +40 °C
1)
Limit values:
Ripple max. 5 V
SS
2)
A = U
B
connections reverse-polarity protected
B = Output Q, short-circuit protected
1)
Grenzwerte:
Restwelligkeit max. 5 V
SS
2)
A = U
B
-Anschlüsse verpolsicher
B = Ausgang Q kurzschlussgeschützt
1)
Valeurs limites ;
Ondulation résiduelle max. 5 V
SS
2)
A = Raccordements U
B
protégés contre les inversions de polarité
B = Sortie Q protégée contre les courts-circuits
1)
Valores limite;
Ondulação residual max. 5 V
SS
2)
A = Conexões U
B
protegidas contra inversão de polos
B = Saída Q protegida contra curto-circuitos
WS / WE190L
Distanza di lavoro max. Distancia de conmutación max. 触发感应距离 max. 検出距離 max. Расстояние срабатывания max. 50 m
Diametro punto luminoso / distanza Diámetro / distancia de mancha de luz
光点直径 / 距离 スポット径 / 距離 Диаметр светового пятна / расстояние 40 mm / 10 m
Tensione di alimentazione U
B
Tensión de alimentación U
B
电源电压 U
B
供給電圧 U
B
Напряжение питания U
B
10 ... 30 V DC
1)
Corrente di uscita I
max.
Corriente de salida I
max.
输出电流I
max
最大出力電流 I
max.
Выходной ток I
max
< 100 mA
Tempo di risposta Tiempo de reacción
触发时间 応答時間
Частота переключения < 0.5 ms
Sequenza signali max. Secuencia de señales max.
信号流 max
最大スイッチング周波数
Время отклика 1000 / s
Tipo di protezione Tipo de protección
保护种类 保護等級
Класс защиты IP 67
Classe di protezione Protección clase
保护级别 保護クラス
Класс защиты
Commutazioni di protezione Circuitos de protección
保护电路 保護回路
Схемы защиты A, B
2)
Temperatura ambiente circostante Temperatura ambiente de servicio 工作环境-温度
動作周囲温度
Диапазон рабочих температур –10 ... +40 °C
1)
Valori limite:
Ondulazione residua max. 5 V
SS
2)
A = U
B
-collegamenti con protezione contro inversione di poli
B = Uscita Q con protezione anti-cortocircuito
1)
Valores límite:
Aondulación residual max. 5 V
SS
2)
A = conexiones U
B
con protección contra polarización inversa
B = Salida Q protegida contra cortocircuito
1)
极限值:
残余纹波最大为 5 V
SS
2)
A = U
B
极性反接保护
B = 具有短路保护的输出端 Q
1)
限界値:
リップル 最大 5 V
PP
2)
A = U
B
電源電圧逆接保護
B = 出力 Q 短絡保護
1)
Предельные значения
Oстаточная волнистость макс. 5 Вss
2)
A = U
B
-подключения с защитой от перепутывания полюсов
B = Выход Q с защитой от короткого замыкания
-------------------------------------------------------------------------------- 8024455.12HK 1219 COMAT ----------------------------------------------------------------------------
WS / WE190L
Standard
More representatives and agencies at www.sick.com ∙ Subject to change
without notice ∙ The specied product features and technical data do not
represent any guarantee.
Weitere Niederlassungen nden Sie unter www.sick.com ∙ Irrtümer
und Änderungen vorbehalten ∙ Angegebene Produkteigenschaften und
technische Daten stellen keine Garantieerklärung dar.
Plus de représentations et d’agences à l’adresse www.sick.com ∙ Sujet à
modication sans préavis ∙ Les caractéristiques de produit et techniques
indiquées ne constituent pas de déclaration de garantie.
Para mais representantes e agências, consulte www.sick.com ∙ Alterações
poderão ser feitas sem prévio aviso ∙ As características do produto e os
dados técnicos apresentados não constituem declaração de garantia.
Altri rappresentanti ed agenzie si trovano su www.sick.com ∙ Contenuti
soggetti a modiche senza preavviso ∙ Le caratteristiche del prodotto e i dati
tecnici non rappresentano una dichiarazione di garanzia.
Más representantes y agencias en www.sick.com ∙ Sujeto a cambio sin
previo aviso ∙ Las características y los datos técnicos especicados no
constituyen ninguna declaración de garantía.
欲了解更多代表机构和代理商信息,请登录 www.sick.com
如有更改, 不另行通知 对所给出的产品特性和技术参数
的正确性不予保证。
その他の営業所はwww.sick.com よりご覧ください ・ 予告なしに変更され
ることがあります ・ 記載されている製品機能および技術データは保証を明
示するものではありません。
------------------------------------------------------------------------------------------------------------------------- -------------------------------------------------------------------------------------------------------------------------
BZ int49
Detailed addresses and further locations at www.sick.com
Australia
Phone +61 (3) 9457 0600
1800 33 48 02 – tollfree
Austria
Phone +43 (0) 2236 62288-0
Belgium/Luxembourg
Phone +32 (0) 2 466 55 66
Brazil
Phone +55 11 3215-4900
Canada
Phone +1 905.771.1444
Czech Republic
Phone +420 234 719 500
Chile
Phone +56 (2) 2274 7430
China
Phone +86 20 2882 3600
Denmark
Phone +45 45 82 64 00
Finland
Phone +358-9-25 15 800
France
Phone +33 1 64 62 35 00
Germany
Phone +49 (0) 2 11 53 010
Greece
Phone +30 210 6825100
Hong Kong
Phone +852 2153 6300
Hungary
Phone +36 1 371 2680
India
Phone +91-22-6119 8900
Israel
Phone +972 97110 11
Italy
Phone +39 02 27 43 41
Japan
Phone +81 3 5309 2112
Malaysia
Phone +603-8080 7425
Mexico
Phone +52 (472) 748 9451
Netherlands
Phone +31 (0) 30 229 25 44
New Zealand
Phone +64 9 415 0459
0800 222 278 – tollfree
Norway
Phone +47 67 81 50 00
Poland
Phone +48 22 539 41 00
Romania
Phone +40 356-17 11 20
Russia
Phone +7 495 283 09 90
Singapore
Phone +65 6744 3732
Slovakia
Phone +421 482 901 201
Slovenia
Phone +386 591 78849
South Africa
Phone +27 10 060 0550
South Korea
Phone +82 2 786 6321/4
Spain
Phone +34 93 480 31 00
Sweden
Phone +46 10 110 10 00
Switzerland
Phone +41 41 619 29 39
Taiwan
Phone +886-2-2375-6288
Thailand
Phone +66 2 645 0009
Turkey
Phone +90 (216) 528 50 00
United Arab Emirates
Phone +971 (0) 4 88 65 878
United Kingdom
Phone +44 (0)17278 31121
USA
Phone +1 800.325.7425
Vietnam
Phone +65 6744 3732
SICK AG, Erwin-Sick-Strasse 1, D-79183 Waldkirch
2006/42/EG
NO
SAFETY
1 2
40,5
30
2,812,5
25
39,2
5
2,6
44,4
32,9
9,3
15
12,3
1,3
L
D
WS / WE190L
B 3 WS / WE190L-P132 WS / WE190L-P430
WS / WE190L-N132 WS / WE190L-N430
2 Leitungsdose spannungsfrei aufstecken und festschrauben.
Für Anschluss in B gilt: brn = braun, blu = blau, blk = schwarz,
wht = weiß.
Leitungen anschließen.
3 WS und WE mit Befestigungsbohrungen an Halter (beiliegend)
gegenüberliegend montieren und grob ausrichten. Dabei Reichweite
beachten (s. technische Daten am Ende dieser Betriebsanleitung und
s. Diagramm; x=Reichweite, y=Funktionsreserve).
WS und WE an Betriebsspannung legen (s. Typenaufdruck).
Justage Lichtempfang:
Ein-Ausschaltpunkte der Empfangsanzeige (gelbe LED) durch
horizontales und vertikales Schwenken der Lichtschranke ermitteln.
Mittelstellung so wählen, dass der rote Sendelichtstrahl in der Reek-
tormitte auftrit. Bei optimalem Lichtempfang leuchtet die gelbe LED
permanent.
Wartung
SICK-Lichtschranken sind wartungsfrei.
Wir empfehlen, in regelmäßigen Abständen
- die optischen Grenzächen zu reinigen
- Verschraubungen und Steckverbindungen zu überprüfen
Veränderungen an Geräten dürfen nicht vorgenommen werden.
Irrtümer und Änderungen vorbehalten. Angegebene Produkteigenschaften
und technische Daten stellen keine Garantieerklärung dar.
brn
blu
brn
blu
blk
brn
blu
blk
wht
brn
blu
blk
wht
MM
Q
1
L+
M
NC
3
4
NC
2
1
3
4
2
L+L+
L+
M
Q
NC
10
0
10
1
WS / WE 190L
x [m]
y
2010 30 40 50
Français
Barrières réexes
avec lumière laser
Manuel d’utilisations
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
Remarques relatives à la sécurité
Il ne s’agit pas d’un composant de sécurité conformément à la Directive
CE sur les machines.
Lire le manuel d’utilisation avant la mise en service.
Faire eectuer le raccordement, le montage et le réglage uniquement
par un personnel spécialisé.
Protéger l’appareil de l’humidité et des impuretés lors de la mise en
service.
a Attention
Tout usage de commandes, réglages ou toute appli-
cation de procédures autres que ceux décrits dans ce
document peut entraîner une exposition dangereuse
au rayonnement.
Utilisation conforme
La barrière lumineuse unidirectionnelle WS / WE190L est un capteur
optoélectronique fonctionnant au moyen d’un module émetteur (WS) et
d’un module récepteur (WE). Elle s’utilise pour la saisie optique de choses,
d’animaux et de personnes sans aucun contact.
Mise en service
1
Les appareils
WS / WE190L
présentent des sorties logiques exclusives:
WE190L-P uniquement:
Q: commutation sombre, sor tie HIGH (inactive) lorsque le trajet lumi-
neux est interrompu,
Q: commutation claire, sortie LOW (inactive) lorsque le trajet lumineux
est interrompu.
WE190L-N uniquement:
Q: commutation sombre, sortie LOW (active) à la réception de lumière,
Q: commutation claire, sortie HIGH (active) à la réception de lumière.
2 Pour le raccordement dans B on a : brn = brun, blu = bleu, blk = noir,
wht = blanc.
Raccorder les conducteurs.
3 Installer les modules WS und WE munis de trous de xation sur un
suppor t (joint) l’un en face de l’autre et les aligner de façon grossière.
Ce faisant, tenir compte de la portée (voir les caractéristiques
techniques à la n des présentes Instructions de Service ainsi que le
diagramme; x=portée, y=lumière susante).
Appliquer la tension de service aux modules WS et WE (voir inscription
indiquant le modèle).
Ajustement Réception de la lumière :
Déterminer les points d‘allumage et d‘extinction du témoin de récepti-
on (LED jaune) en faisant basculer la barrière opto-électronique hori-
zontalement et verticalement. Choisir une position intermédiaire telle
que le rayon de lumière rouge émise tombe au milieu du réecteur.
Lorsque la réception de la lumière est optimale, le LED jaune est
allumé en permanence.
Maintenance
Les capteurs SICK ne nécessitent aucune maintenance.
Nous vous recommandons de procéder régulièrement
- au nettoyage des surfaces optiques
- au contrôle des vissages et des connexions enchables
Ne procéder à aucune modication sur les appareils.
Sujet à modication sans préavis. Les caractéristiques du produit et tech-
niques fournies ne sont pas une déclaration de garantie.
Português
Barreira de luz de reexão
com luz laser
Instruções de operação
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
Notas de segurança
Os componentes de segurança não se encontram em conformidade
com a Diretiva Europeia de Máquinas.
Ler as instruções de operação antes da colocação em funcionamento.
A conexão, a montagem e o ajuste devem ser executados somente por
pessoal técnico qualicado.
Durante o funcionamento, manter o aparelho protegido contra impure-
zas e umidade.
a Atenção
O uso de controles ou ajustes ou a execução de pro-
cedimentos diferentes dos aqui especicados podem
resultar em exposição perigosa à radiação.
Especificações de uso
A barreira de luz de uma via WS / WE190L é um sensor optoeletrônico que
trabalha com uma unidade emissora (WS) e uma unidade receptora (WE).
Serve para a análise ótica, sem contato, de objetos, animais e pessoas.
Colocação em funcionamento
1
Os equipamentos WE190L possuem saídas antivalentes:
Italiano
Sensore fotoelettrico a riettore
a luce laser
Struzioni d’uso
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
Avvertenze sulla sicurezza
Nessun componente di sicurezza conformemente alla direttiva macchine UE.
Prima della messa in funzione leggere le istruzioni d’uso.
Allacciamento, montaggio e regolazione solo a cura di personale tecnico
specializzato.
Alla messa in funzione proteggere l’apparecchio dall’umidità e dalla
sporcizia.
a Attenzione
Usare controlli e regolazioni o eseguire procedure
diversamente da come specicato di seguito può
causare una esposizione a radiazioni pericolose.
Impiego conforme agli usi previsti
La barriera luminosa a senso unico WS / WE190L è un sensore optoelettro-
nico dotato di un’unità di trasmissione (WS) e di un’unità di ricezione (WE).
Viene impiegata per il rilevamento ottico a distanza di oggetti, animali e
persone.
Messa in funzione
1
Gli apparecchi
WS / WE190L
hanno uscite di commutazione antivalen-
ti:
Solo WE190L-P:
Q: commutazione a scuro, con interruzione della luce uscita HIGH,
Q: commutazione a chiaro, con interruzione della luce uscita LOW.
Solo WE190L-N:
Q: commutazione a scuro, con ricezione di luce uscita LOW,
Q: commutazione a chiaro, con ricezione di luce uscita HIGH.
2 Per collegamento B osservare: brn = marrone, blu = blu, blk = nero,
wht = bianco.
Collegare i cavi.
3 Montare WS e WE sul supporto (a corredo) usando i fori di ssaggio di
fronte al riettore e oreintare approssimativamente. Ternere conto del-
la portata di ricezione (cf. Scheda tecnica alla ne di queste Istruzioni
e il Diagramma; x=portata, y=riserva funzionale).
Allacciare WS e WE a tensione d’esercizio (cf. stampigliatura).
Aggiustare la ricezione luce:
Individuare i punti di inserimento e disinserimento dell‘indicatore
di ricezione (LED giallo) orientando la barriera luminosa in senso
verticale e orizzontale. Scegliere la posizione mediana, in modo che il
raggio di luce rossa colpisca il centro del riettore. Quando la ricezione
è ottimale i LED verde si accendono permanentemente.
Manutenzione
I sensori SICK sono esenti da manutenzione.
A intervalli regolari si consiglia di
- pulire le superci limite ottiche
- Vericare i collegamenti a vite e gli innesti a spina
Non è consentito eettuare modiche agli apparecchi.
Contenuti soggetti a modiche senza preavviso. Le proprietà del prodotto e
le schede tecniche indicate non costituiscono una dichiarazione di garanzia.
Español
Barrera fotoeléctrica de reexión
con luz láser
Instrucciones de servicio
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
Indicaciones de seguridad
No se trata de un componente de seguridad según la Directiva de
máquinas de la UE.
Lea las instrucciones de servicio antes de efectuar la puesta en funcio-
namiento.
La conexión, el montaje y el ajuste deben ser efectuados exclusivamente
por técnicos especialistas.
Proteja el equipo contra la humedad y la suciedad durante la puesta en
funcionamiento.
a Atención
El uso de controles, ajustes o procedimientos distintos
a los especicados aquí podría dar lugar a una exposi-
ción a radiación peligrosa.
Uso conforme a lo previsto
La barrera fotoelectrica unidirecciona WS / WE190L es un sensor opto-
electrónico que trabaja con una unidad de transmisión (WS) y una unidad
de recepción (WE). Se emplea para la detección óptica y sin contacto de
objetos, animales y personas.
Puesta en funcionamiento
1 Los aparatos WS / WE190L tienen marchas de conexión antivalentes:
Solo WE190L-P
Q: de conexión oscura, con interrupción de luz salida HIGH,
Q: conexión luminosa, con interrupción de luz salida LOW.
Solo WE190L-N:
Q: de radiación oscura, con recepción de luz salida LOW,
Q: conexión luminosa, con recepción de salida HIGH.
2
Para conectar en B: brn = marrón, blu = azul, blk = negro,
wht = blanco.
Conectar los conductores.
3
Montar WS y WE mediante los taladros de jación a un soporte (adjun-
to) uno frente a otro y ajustarlos ligeramente. Para ello, tener en cuenta
el alcance (ver características técnicas al nal del presente Manual de
Servicio y el diagrama; x=alcance, y=reserva funcional).
Poner WS y WE en tensión de servicio (ver impresión tipográca).
Ajuste de la recepción de luz:
Determinar los puntos de conexión / desconexión de la indicación
de recepción (LED amarillo) mediante giro horizontal y vertical de la
barrera fotoeléctrica. Elegir la posición central de forma que el haz lu
-
minoso rojo emitido caiga en el centro del reector. Con una recepción
óptima de luz se enciende permanentemente el LED amarillo.
Mantenimiento
Los sensores SICK no precisan mantenimiento.
A intervalos regulares, recomendamos:
- limpiar las supercies ópticas externas
- comprobar las uniones roscadas y las conexiones.
No se permite realizar modicaciones en los aparatos.
Sujeto a cambio sin previo aviso. Las propiedades y los datos técnicos del
producto no suponen ninguna declaración de garantía.
中文
带激光的
反射式光电传感器
操作规程
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
安全须知
按照EU-机器规程无保护元件。
使用前阅读操作规程。
只允许专业人员进行接线,安装及调整。
使用时应防潮湿防污染。
a 小心
使用在此没有描述过的其他控制器、设置或操作方式,
可能会遭受危险的射线照射。
正确使用须知
对射式光电传感器
WS / WE190L 是一种利用发射单元 (WS) 和接收单元 (WE)
工作的光电传感器。用于物体、动物和人体的非接触式光学检测。
调试
1 设备 WS / WE190L 具有补偿量开关量输出:
WE190L-P
Q:暗通,光线中断时输出端为 HIGH
Q:亮通,光线中断时输出端为 LOW。
WE190L-N
Q:暗通,接收光线时输出端为 LOW
Q:亮通,接收光线时输出端为 HIGH
2 在不通电的情况下插上并拧紧电缆插口。
布置 PIN / 布线时请参照图 B (brn = 棕色、blu = 蓝色、blk = 黑色、
wht = 白色)。
连接电缆。
3 与光电传感器面对面安装合适的反射器并粗略对准。同时注意扫描范围
(参见本操作指南末尾的技术数据和图表;
x = 扫描范围,y = 运行备
用,
y
B
= 工作范围,y
G
= 极限扫描范围)。
接通传感器工作电压(参见型号铭牌标识)。
校准受光:
通过水平和竖直摆动光电传感器确定接收指示灯(黄色 LED)的接通/关
断点。调整中间位置,确保红色发射光束落在反射器中央。光线接收为
最佳状态时,黄色
LED 恒亮。
保养
SICK 传感器无需保养。
我们建议,定期:
- 清洁镜头检测面
- 检查螺栓连接和插头连接
不得对设备进行任何改装。
如有更改,不另行通知。所给出的产品特性和技术参数并非质保声明。
日本語
レーザ光を使用した
リフレクタ形光電センサ
取扱説明書
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
安全上の注意事項
本製品は EU 機械指令の要件を満たす安全コンポーネントではありません。
使用を開始する前に取扱説明書をお読みください。
接続、取付けおよび設定できるのは専門技術者に限ります。
装置を使用開始する際には、濡れたり汚れたりしないように保護してく
ださい。
a 注意
本書で指定されていない制御や調整を行ったり手順を
実行したりすると、危険な放射線暴露につながる可能
性があります。
使用目的
透過形光電スイッチ
WS / WE190Lは、投光ユニット (WS) および受光ユニッ
ト (
WE) を用いて動作する光電センサです。これは物体、動物および人物を
光学技術により非接触で検知するための装置です。
使用開始
1 機 器 WS / WE190Lは補完的スイッチング出力を備えています:
WE190L-Pのみ:
Q: ダークオン、受光していない時は出力HIGH
Q: ライトオン、受光していない時は出力LOW
WE190L-Nのみ:
Q: ダークオン、受光時は出力LOW
Q: ライトオン、受光時は出力HIGH
2 メスケーブルコネクタを無電圧で差し込み、ネジ止めします。
PIN 割り当て / 配線割り当ては、図 B を参照してください
(brn =
茶、blu = 青、blk = 黒、wht = )
ケーブルを接続します。
3 適切なリフレクタを光電センサと向かい合うように取り付け、大まか
に位置を合わせます。その際、検出距離にご注意ください (本取扱説明
書の終わりの技術仕様および図を参照;
x = 検出距離、y = 予備能、
y
B
= 動作範囲、y
G
= 検出距離限界)。
センサに動作電圧を供給します (型式ラベル参照)
受光調整:
光電センサを左右そして上下方向に振って、信号強度表示灯 (黄色の
LED) のオン/オフが切り替わるスイッチングポイントを検出します。赤
色の投光軸がリフレクタ中央にあたるように中央位置を選択します。
最適な受光状態では、黄色の
LEDが常時点灯します
メンテナンス
SICK センサはメンテナンスフリーです。
定期的に以下を行うことをお勧めしています:
- レンズ境界面の清掃
- ネジ締結と差込み締結の点検
機器を改造することは禁止されています。
記載内容につきましては予告なしに変更する場合がございますのであらか
じめご了承ください。指定された製品特性および技術データは保証書では
ありません。
Русский язык
Отражательный фотоэлектрический датчик
с лазерным лучом
Руководство по эксплуатации
EN/IEC 60825-1:2014
IEC60825-1:2007
Laser
2
Maximum pulse power 2 mW
Puls length: 4 µs
Wavelength: 655 nm
Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007
Laser Radiation
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
Указания по безопасности
Не является оборудованием для обеспечения безопасности
в соответствии с Директивой ЕС по работе с машинным
оборудованием.
Перед вводом в эксплуатацию изучите руководство по эксплуатации.
Подключение, монтаж и установку поручать только специалистам.
При вводе в эксплуатацию защищать устройство от попадания грязи
и влаги.
a ОСТОРОЖНО
Использование других элементов управления,
настроек или процедур, отличных от описанных
здесь, может привести к опасному облучению.
Использование по назначению
Однолучевой фотоэлектрический датчик WS / WE190L является
оптоэлектронным датчиком, работающим с передатчиком (WS)
и приёмником (WE). Устройство используется для оптической
бесконтактной регистрации предметов, животных и людей.
Ввод в эксплуатацию
1 Устройства WS / WE190L имеют дополнительные переключающие
выходы:
Только WE190L-P:
Q: активация при отсутствии отражённого света, при прерывании
светового луча выход ВЫСОКИЙ, Q: активация при наличии
отражённого света, при прерывании светового луча выход НИЗКИЙ.
Только WE190L-N:
Q: активация при отсутствии отражённого света, при приёме
светового луча выход НИЗКИЙ, Q: активация при наличии
отражённого света, при приёме светового луча выход ВЫСОКИЙ.
2 Вставить в обесточенном состоянии розетку кабеля и закрепить
винтами.
Для разъёма в B применяются следующие обозначения:
brn = коричневый, blu = синий, blk = черный, wht = белый.
Подключить кабели.
3 фотоэлектрического датчика подходящий отражатель. При этом
учесть дальность сканирования (см. технические характеристики
в конце данного руководства по эксплуатации и диаграмму, x =
дальность сканирования, y = функциональный резерв, yB = рабочий
диапазон, yG = предельный диапазон).
Подать на датчик рабочее напряжение (см. заводской штамп).
Юстировка приема света:
Определить точки включения и выключения индикатора приёма
(жёлтый светодиод) путём поворачивания фотоэлектрического
датчика в горизонтальной и вертикальной плоскостях. Выбрать
среднее положение, так чтобы красный луч передатчика попадал в
центр отражателя. При оптимальном приёме света жёлтый светодиод
горит непрерывно.
Техобслуживание
Датчики SICK не нуждаются в техобслуживании.
Рекомендуется регулярно
- очищать оптические ограничивающие поверхности
- проверять прочность резьбовых и штекерных соединений
Запрещается вносить изменения в устройства.
Право на ошибки и внесение изменений сохранено. Указанные
свойства изделия и технические характеристики не являются гарантией.
Somente WE 190L-P:
Q: ativado quando escuro signica que a saída está HIGH, quando o
raio de luz está interrompido.
Q: ativado com luz signica que a saída está LOW, quando o raio de luz
está interrompido.
Somente WE 190L-N:
Q: ativado quando escuro signica que, a saída está LOW quando
recebe luz.
Q: ativado quando há luz signica que, a saída está HIGH quando
recebe luz.
2
Para a ligação elétrica em B é: brn = marron, blu = azul, blk = preto,
wht = branco.
Fazer a cablagem elétrica.
3 Montar o WS e o WE um em frente do outro, mediante os furos de
xação no suporte (adjunto) e ajustá-los mais ou menos. Atender ao
alcance da luz (ver dados técnicos no nal destas instruções de ope-
ração e ver diagrama; x=alcance da luz, y=reserva de funcionamento).
Ligar o WS e o WE à tensão operacional (ver identicação de tipo).
Ajuste da recepção luminosa:
Determinar os pontos de ligação e de desligamento do indicador
de recepção (LED amarelo) basculando a barreira fotoelétrica na
horizontal e na vertical. Selecionar a posição central de modo que o
raio luminoso de emissão, vermelho, atinja o centro do reetor. No
caso de recepção luminosa otimizada, os LED amarelo acende em
permanência.
Manutenção
Os sensores SICK não requerem manutenção.
Recomendamos que se efetue em intervalos regulares
- uma limpeza das superfícies ópticas
- uma vericação das conexões roscadas e dos conectores
Não são permitidas modicações no aparelho.
Sujeito a alterações sem aviso prévio. As propriedades do produto e os dados
técnicos especicados não constituem nenhum certicado de garantia.
  • Page 1 1
  • Page 2 2

SICK WS/WE190L Standard Инструкция по эксплуатации

Тип
Инструкция по эксплуатации

Задайте вопрос, и я найду ответ в документе

Поиск информации в документе стал проще с помощью ИИ