Generac 8 kVA 0059141 Руководство пользователя

Категория
Генераторы
Тип
Руководство пользователя
Owner's Manual
8, 10 & 13 KVA Air-cooled, 50 Hertz
Automatic Standby Generators
NOT INTENDED FOR USE IN CRITICAL LIFE
SUPPORT APPLICATIONS.

ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION!

DEADLY EXHAUST FUMES! OUTDOOR
INSTALLATION ONLY!
Introduction ................................................. 1
Read This Manual Thoroughly ................................................1
Safety Rules ................................................. 1
Contents ...............................................................................1
Operation and Maintenance....................................................1
How to Obtain Service ...........................................................1
Standards Index .....................................................................3
General Information .................................... 4
1.1 Unpacking/Inspection .....................................................4
1.2 Protection Systems ........................................................4
1.3 Emission Information......................................................4
1.4 The Generator ................................................................4
1.5 Specifications ................................................................5
1.6 Ready to Run .................................................................5
1.7 Fuel Requirements and Recommendations ......................5
1.8 Fuel Consumption ..........................................................6
1.9 Reconfiguring the Fuel System ........................................6
1.10 Location .........................................................................7
1.11 Battery Requirements .....................................................8
1.12 Battery Installation ..........................................................8
1.13 The Battery ..................................................................10
1.14 Battery Charger ............................................................10
Post Installation Start-up and
Adjustments ............................................... 10
2.1 Before Initial Startup .....................................................10
2.2 Check Transfer Switch Operation ..................................11
2.3 Electrical Checks ..........................................................11
2.4 Generator Tests Under Load ..........................................11
2.5 Checking Automatic Operation ......................................12
Operation ................................................... 12
3.1 Control Panel Interface .................................................12
3.2 Automatic Transfer Operation ........................................13
3.3 Sequence of Automatic Operation .................................13
3.4 Manual Transfer Operation ............................................14
3.5 Side Compartment .......................................................15
3.6 Protection Systems ......................................................16
3.7 Shutting Down the Generator While Under Load ............17
Maintenance .............................................. 18
4.1 Fuse .............................................................................18
4.2 Checking the Engine Oil Level .......................................18
4.3 Changing the Engine Oil ................................................18
4.4 Changing the Engine Air Cleaner ...................................19
4.5 Spark Plug(s) ...............................................................20
4.6 Battery Maintenance .....................................................20
4.7 Adjusting GT-530/990 Valve Clearance ..........................21
4.8 Cooling System ............................................................21
4.9 Attention After Submersion ...........................................22
4.10 Corrosion Protection.....................................................22
4.11 Out of Service Procedure ..............................................22
4.12 Service Schedule .........................................................23
Troubleshooting ........................................ 24
5.1 Troubleshooting Guide ..................................................24
Appendix .................................................... 25
6.1 Menu System Navigation ..............................................25
Installation Diagrams ................................ 27
Warranty ..................................................... 30
MANUAL DEL USUARIO .................31
 

............................ 61
Table of Contents
1
INTRODUCTION
Thank you for purchasing this compact, high performance, air-cooled,
engine-driven generator. It is designed to automatically supply electrical
power to operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal enclosure and is
intended exclusively for outdoor installation. This generator will operate
using either vapor withdrawn liquid propane (LP) or natural gas (NG).
NOTE:
This generator is suitable for supplying typical residential loads such
as Induction Motors (sump pumps, refrigerators, air conditioners,
furnaces, etc.), Electronic Components (computer, monitor, TV, etc.),
Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest Dealer
for starting, operating and servicing procedures.
SAFETY RULES
Throughout this publication, and on tags and decals affixed to the genera-
tor, DANGER, WARNING, CAUTION and NOTE blocks are used to alert
personnel to special instructions about a particular operation that may be
hazardous if performed incorrectly or carelessly. Observe them carefully.
Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if not
avoided, could result in death or serious injury.
Indicates a hazardous situation or action which, if not
avoided, could result in minor or moderate injury.
NOTE:
Notes contain additional information important to a procedure
and will be found within the regular text body of this manual.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the action or service are essential to
preventing accidents.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates is as follows:
This symbol points out important safety information that,
if not followed, could endanger personal safety and/or
property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. The
manufacturer strongly recommends that the operator read this Owner's
Manual and thoroughly understand all instructions before using this
equipment. The manufacturer also strongly recommends instructing other
users to properly start and operate the unit. This prepares them if they
need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information for these models:
8 KVA, V-twin GT-530 Engine
10 KVA, V-twin GT-990 Engine
13 KVA, V-twin GT-990 Engine
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure
that all maintenance for safe operation is performed promptly, and to have
the equipment checked periodically by a Dealer. Normal maintenance ser-
vice and replacement of parts are the responsibility of the owner/operator
and, as such, are not considered defects in materials or workmanship
within the terms of the warranty. Individual operating habits and usage
contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures a minimum number
of problems and keep operating expenses at a minimum. See a Dealer for
service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, contact a Dealer for
assistance. Service technicians are factory-trained and are capable of
handling all service needs.
When contacting a Dealer about parts and service, always supply the
complete model number and serial number of the unit as given on its data
decal, which is located on the generator. See section "The Generator" for
decal location.
Model No. _________________ Serial No. ______________
Data Label Sample
Safety Rules
2
Study these SAFETY RULES carefully before installing, operating
or servicing this equipment. Become familiar with this Owner’s
Manual and with the unit. The generator can operate safely, effi-
ciently and reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to follow simple
and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all-inclusive. If
using a procedure, work method or operating technique the manu-
facturer does not specifically recommend, ensure that it is safe for
others. Also make sure the procedure, work method or operating
technique utilized does not render the generator unsafe.
Despite the safe design of this generator,
operating this equipment imprudently, neglect-
ing its maintenance or being careless can
cause possible injury or death. Permit only
responsible and capable persons to install,
operate and maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or
hot during operation. Exercise care near run-
ning generators.
Installation must always comply with appli-
cable codes, standards, laws and regula-
tions.
A running generator gives off carbon mon-
oxide, an odorless, colorless poison gas.
Breathing in carbon monoxide can cause
headaches, fatigue, diziness, nausea, vomit-
ting, confusion, fainting, siezures or death.
GENERAL HAZARDS
For safety reasons, the manufacturer recommends that this equip-
ment be installed, serviced and repaired by a Service Dealer or
other competent, qualified electrician or installation technician who
is familiar with applicable codes, standards and regulations. The
operator also must comply with all such codes, standards and
regulations.
The engine exhaust fumes contain carbon monoxide, which
can be DEADLY. This dangerous gas, if breathed in sufficient
concentrations, can cause unconsciousness or even death.
Do NOT alter or add to the exhaust system or do anything that
might render the system unsafe or in noncompliance with appli-
cable codes and standards.
Install a battery operated carbon monoxide alarm indoors,
according to manufacturer's instructions/recommendations.
Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation. Do not alter the instal-
lation or permit even partial blockage of ventilation provisions,
as this can seriously affect safe operation of the generator. The
generator MUST be installed and operated outdoors only.
Keep hands, feet, clothing, etc., away from drive belts, fans,
and other moving or hot parts. Never remove any drive belt or
fan guard while the unit is operating.
When working on this equipment, remain alert at all times.
Never work on the equipment when physically or mentally
fatigued.
Inspect the generator regularly, and contact the nearest Dealer
for parts needing repair or replacement.
Before performing any maintenance on the generator, discon-
nect its battery cables to prevent accidental start up. Disconnect
the cable from the battery post indicated by a NEGATIVE, NEG
or (–) first, then remove the POSITIVE, POS or (+) cable. When
reconnecting the cables, connect the POSITIVE cable first, the
NEGATIVE cable last.
Never use the generator or any of its parts as a step. Stepping
on the unit can stress and break parts, and may result in dan-
gerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
EXHAUST HAZARDS
• Generator engine exhaust contains DEADLY carbon monox-
ide, an odorless, colorless poisonous gas. Breathing carbon
monoxide can cause: dizziness, throbbing temples, nausea,
muscular twitching, headache, vomiting, weakness and sleepi-
ness, inability to think clearly, fainting, unconsciousness or
even death. If you experience any carbon monoxide poisoning
symptoms, move into fresh air and immediately seek medical
attention.
Never operate the generator set inside any garage or other
enclosed area EVEN IF the doors and windows are open.
ELECTRICAL HAZARDS
All generators covered by this manual produce dangerous
electrical voltages and can cause fatal electrical shock. Utility
power delivers extremely high and dangerous voltages to the
transfer switch as does the standby generator when it is in
operation. Avoid contact with bare wires, terminals, connec-
tions, etc., while the unit is running. Ensure all appropriate
covers, guards and barriers are in place, secured and/or locked
before operating the generator. If work must be done around
an operating unit, stand on an insulated, dry surface to reduce
shock hazard.
Do not handle any kind of electrical device while stand-
ing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s
installation site. Safety should be stressed to all operators and potential operators of this equipment.
Safety Rules
3
The National Electrical Code (NEC) requires the frame and external
electrically conductive parts of the generator to be connected to
an approved earth ground. Local electrical codes also may require
proper grounding of the generator electrical system.
After installing this home standby electrical system, the genera-
tor may crank and start at any time without warning. When this
occurs, load circuits are transferred to the STANDBY (genera-
tor) power source. To prevent possible injury if such a start and
transfer occur, always set the generator’s AUTO/OFF/MANUAL
switch to its OFF position before working on equipment and
remove the 7.5A fuse from the generator control panel.
In case of accident caused by electric shock, immediately shut
down the source of electrical power. If this is not possible,
attempt to free the victim from the live conductor. AVOID DIRECT
CONTACT WITH THE VICTIM. Use a nonconducting implement,
such as a dry rope or board, to free the victim from the live
conductor. If the victim is unconscious, apply first aid and get
immediate medical help.
Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get
caught in moving components causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and maintained
properly. Installation must always comply with applicable
codes, standards, laws and regulations. Adhere strictly
to local, state and national electrical and building codes.
Comply with regulations the Occupational Safety and Health
Administration (OSHA) has established. Also, ensure that the
generator is installed in accordance with the manufacturer’s
instructions and recommendations. Following proper installa-
tion, do nothing that might alter a safe installation and render
the unit in noncompliance with the aforementioned codes,
standards, laws and regulations.
Keep a fire extinguisher near the generator at all times.
Extinguishers rated “ABC” by the National Fire Protection
Association are appropriate for use on the standby electric
system. Keep the extinguisher properly charged and be familiar
with its use. Consult the local fire department with any ques-
tions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any fuel or oil
spills immediately. Ensure that no combustible materials are left
in the generator compartment, or on or near the generator, as
FIRE or EXPLOSION may result. Keep the area surrounding the
generator clean and free from debris.
Gaseous fluids such as natural gas and liquid propane (LP)
gas are extremely EXPLOSIVE. Install the fuel supply system
according to applicable fuel-gas codes. Before placing the
home standby electric system into service, fuel system lines
must be properly purged and leak tested according to applica-
ble code. After installation, inspect the fuel system periodically
for leaks. No leakage is permitted.
STANDARDS INDEX
Applicable national, state, or local laws, codes, and regulations
pertaining to the installation of engine-generator power systems
must be strictly complied with. Always use the current accept-
able version or edition of the applicable code or standard which
applies to your jurisdiction. In the absence of pertinent local laws
and standards, the following published booklets may be used as
a guide (these apply to localities which recognize NFPA and IBC):
1. National Fire Protection Association (NFPA) 70: The NATIONAL
ELECTRIC CODE (NEC) *
2. NFPA 10: Standard for Portable Fire Extinguishers *
3. NFPA 30: Flammable And Combustible Liquids Code *
4. NFPA 37: Standard for Stationary Combustion Engines And
Gas Turbines *
5. NFPA 54: National Fuel Gas Code *
6. NFPA 58: Standard for Storage And Handling Of Liquefied
Petroleum Gases *
7. NFPA 70E: Standard For Electrical Safety In The Workplace *
8. NFPA 5000: Building Code *
9. ASAE EP-364.2 Installation and Maintenance of Farm Standby
Electric Power ****
10. Agricultural Wiring Handbook ***
11. International Building Code **
This list is not all inclusive. Check with the Authority Having Local
Jurisdiction (AHJ) for any local codes or standards which may
be applicable to your jurisdiction. The above listed standards are
available from the following internet sources:
* www.nfpa.org
** www.iccsafe.org
*** www.rerc.org Rural Electricity Resource Council, P.O. Box
309 Wilmington, OH 45177-0309
**** www.asabe.org American Society of Agricultural & Biological
Engineers, 2950 Niles Road, St. Joseph, MI 49085
Safety Rules
Only qualified electricians or contractors
should attempt such installations, which must
comply strictly with applicable codes, stan-
dards and regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
This standby generator set is ready for installation with a factory
supplied and pre-mounted base pad and has a weather protec-
tive enclosure that is intended for outdoor installation only.
If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a trans-
fer switch. The transfer switch must effectively
isolate the electrical system from the utility
distribution system when the generator is oper-
ating (NEC 700, 701 & 702). Failure to isolate an
electrical system by such means will result in
damage to the generator and also may result in
injury or death to utility power workers due to
backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the
person(s) making the delivery note all damage on the freight bill
or affix their signature under the consignor's memo of loss or
damage.
If a loss or damage is noted after delivery, separate the damaged
materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the con-
tents of a package that is not in evidence at the time of delivery,
but is discovered later.
To properly open the roof, press down on the center top lip and
turn the keylocks. If pressure is not applied from the top, the roof
may appear stuck. Always verify that the side locks are unlocked
before attempting to lift the roof.
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for
long periods of time with no operator present to monitor engine
conditions. For that reason, the engine is equipped with the fol-
lowing systems that protect it against potentially damaging condi-
tions:
1. Low Oil Pressure Sensor 6. Low Battery
2. High Temperature Sensor 7. Under-frequency
3. Overcrank 8. Undervoltage
4. Overspeed 9. Overvoltage
5. RPM Sensor 10. Internal Failure
There are readouts on the control panel to notify personnel that
one of these failures has occurred. There is a Status message on
the display that displays when all of the conditions described in the
"Ready to Run" section are true.
1.3 EMISSION INFORMATION
The engine used in this generator is not certified to United States
EPA emission standards, or any other emission standards. Sale or
use of this generator is not legal in the U.S. or any country which
has emission standards that are applicable to this product.
1.4 THE GENERATOR
Figure 1.1 – 8 KVA, V-twin, GT-530 Engine
(door removed)
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air
Filter
Circuit
Breaker
Control
Panel
Figure 1.2 – 10 and 13 KVA, V-twin,
GT-990/GT-999 Engine (door removed)
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air Filter
Circuit
Breakers
Control
Panel
4
General Information
5
1.5 SPECIFICATIONS
1.5.1 GENERATOR
Model (NG/LP) 7/8 KVA 10/10 KVA 13/13 KVA
Rated Voltage 220
Rated Maximum Load Current
(Amps) at 220 Volts (NG/LP)
31.8/36.4 45.5/45.5 59.0/59.0
Main Circuit Breaker 40 Amp 50 Amp 60 Amp
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 50 Hz
Battery Requirement Group 26R, 12 Volts and 525 CCA Minimum
Weight (unit only in lbs.) 387 439 455
Enclosure Steel Steel Steel
Normal Operating Range
This unit is tested in accordance to UL 2200 standards
with an operating temperature of -20 °F (-29 °C) to 122
°F. (50 °C). For areas where temperatures fall below 32
°F (0 °C), a cold weather kit is highly recommended.
When operated above 77º F (25º C) there may be a
decrease in engine power. (Please reference the engine
specifications section).
These generators are rated in accordance with UL2200, Safety Standard for Stationary
Engine Generator Assemblies; and CSA-C22.2 No. 100-04 Standard for Motors and
Generators.
** Circuits to be moved must be protected by same size breaker. For example, a 15 amp
circuit in the main panel must be a 15 amp circuit in the transfer switch.
1.5.2 ENGINE
Model 8 KVA 10/13 KVA
Type of Engine GT-530 GT-990
Number of Cylinders 2 2
Displacement 530cc 992cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valves
Ignition System Solid-state w/Magneto
Recommended Spark Plug BPR6HS RC14YC
Spark Plug Gap 0.76 mm (0.030 inch) 1.02 mm (0.040 inch)
Compression Ratio 9.5:1 9.5:1
Starter 12 VDC
Oil Capacity Including Filter Approx. 1.7 Qts
(1.609 L)
Approx. 1.9 Qts
(1.798 L)
Recommended Oil Filter Part # 070185F
Recommended Air Filter Part # 0E9581 Part # 0C8127
Operating RPM 3,000
* Engine power is subject to and limited by such factors as fuel Btu content, ambient
temperature and altitude. Engine power decreases about 3.5 percent for each 1,000
feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above
16 C (60 F) ambient temperature.
1.6 READY TO RUN
The "Ready to Run" on the display is ready when all of the following
conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO position.
2. The utility voltage being supplied to the unit is being sensed
by the PCB. If the utility sense voltage is not connected to the
unit or if it is below approximately 150-160 volts AC, then
the system will display the message "No Utility Present". This
indicates that if the AUTO/OFF/MANUAL switch is placed in
the Auto position, the generator will start.
3. No alarms are present, for example, low oil pressure, high
temperature, etc.
1.7 FUEL REQUIREMENTS AND
RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This type of
system uses the vapors formed above the liquid fuel in the storage
tank.
The engine has been fitted with a fuel carburetion system that meets
the specifications of the 1997 California Air Resources Board for
tamper-proof dual fuel systems. The unit will run on natural gas or
LP gas, but it has been factory set to run on natural gas. Should the
primary fuel need to be changed to LP gas, the fuel system needs
to be reconfigured. See the reconfiguring the Fuel System section
for instructions on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at least 1,000
Btus per cubic foot for natural gas; or at least 2,520 Btus per
cubic foot for LP gas. Ask the fuel supplier for the Btu content of
the fuel.
Required fuel pressure for natural gas is five (5) inches to seven
(7) inches water column (0.18 to 0.25 psi); and for liquid pro-
pane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
The primary regulator for the propane supply is NOT INCLUDED
with the generator.
NOTE:
All pipe sizing, construction and layout must comply with NFPA
54 for natural gas applications and NFPA 58 for liquid propane
applications. Once the generator is installed, verify that the fuel
pressure NEVER drops below four (4) inches water column for
natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer should consult
local fuel suppliers or the fire marshal to check codes and regula-
tions for proper installation. Local codes will mandate correct rout-
ing of gaseous fuel line piping around gardens, shrubs and other
landscaping to prevent any damage.
Special considerations should be given when installing the unit
where local conditions include flooding, tornados, hurricanes,
earthquakes and unstable ground for the flexibility and strength of
piping and their connections.
Use an approved pipe sealant or joint compound on all threaded
fitting.
All installed gaseous fuel piping must be purged and leak tested
prior to initial start-up in accordance with local codes, standards
and regulations.
General Information
1.8 FUEL CONSUMPTION
Unit
(NG/LP)
Nat. Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
7/8 KVA 77 140 0.94/34 1.68/62
10/10 KVA 152 215 1.53/56 2.08/76
13/13 KVA 156 220 1.55/57 2.18/80
* Natural gas is in cubic feet per hour.
** LP is in gallons per hour/cubic feet per hour.
*** Values given are approximate.
Verify that gas meter is capable of providing enough fuel flow to
include household appliances.
1.9.1 BTU FLOW REQUIREMENTS - NATURAL GAS
BTU flow required for each unit based on 1000 BTU per cubic
foot.
7 KVA — 140,000 BTU/Hour
10 KVA — 215,000 BTU/Hour
13 KVA — 220,000 BTU/Hour
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even
the slightest spark can ignite such fuels and
cause an explosion. No leakage of fuel is
permitted. Natural gas, which is lighter than
air, tends to collect in high areas. LP gas is
heavier than air and tends to settle in low
areas.
NOTE:
A minimum of one approved manual shut-off valve must be
installed in the gaseous fuel supply line. The valve must be eas-
ily accessible. Local codes determine the proper location.
1.9 RECONFIGURING THE FUEL
SYSTEM
To reconfigure the fuel system from NG to LP, follow these steps:
NOTE:
The primary regulator for the propane supply is NOT INCLUDED
with the generator. A fuel pressure of 10 to 12 inches of water
column (0.36 to 0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Open the roof.
2. For 8 KVA units: Loosen clamp and slide back the air inlet
hose.
Slide fuel selector on carburetor out towards the back of the
enclosure (Figures 1.3 and 1.4).
Return the inlet hose and tighten clamp securely.
For 10 and 13 KVA units: remove the air cleaner cover.
Slide the selector lever out towards the back of the enclosure
(Figures 1.5 and 1.6).
Return the air cleaner cover and tighten the two thumb
screws.
3. Close the roof.
4. Reverse the procedure to convert back to natural gas.
Figure 1.3 - 8 KVA, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
Figure 1.4 - 8 KVA, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Figure 1.5 - 10 & 13 KVA,
GT-990 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
6
General Information
7
Figure 1.6 - 10 & 13 KVA,
GT-990 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.10 LOCATION
The engine exhaust fumes contain carbon
monoxide, which can be DEADLY. This dan-
gerous gas, if breathed in sufficient con-
centrations, can cause unconsciousness or
even death. This generator must be installed
properly, in strict compliance with applicable
codes and standards. Following installation,
do nothing that might render the system
unsafe or in noncompliance with such codes
and standards.
Operate the generator outdoors ONLY.
Keep exhaust gases from entering a confined
area through windows, doors, ventilation, crawl
spaces or other openings (Figure 1.7).
It is highly recommended that carbon monox-
ide detector(s) be installed indoors according
to the manufacturer's instructions/recommen-
dations.
The generator must be mounted safely per
applicable codes and the manufacturer's speci-
fications. Do NOT alter or add to the exhaust
system, or do anything that might render the
exhaust system unsafe or in noncompliance
with applicable codes and standards.
1.10.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors,
where adequate cooling and ventilating air is always available
(Figure 1.7). Consider these factors:
• The installation of the generator must comply strictly with
NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards.
• Install the unit where air inlet and outlet openings will not
become obstructed by leaves, grass, snow, etc.. If prevailing
winds will cause blowing or drifting, consider using a wind-
break to protect the unit.
Install the generator on high ground where water levels will not
rise and endanger it.
Allow sufficient room on all sides of the generator for mainte-
nance and servicing. This unit must be installed in accordance
with current applicable NFPA 37 and NFPA 70 standards; as
well as any other federal, state and local codes for minimum
distances from other structures. DO NOT install under wooden
decks or structures unless there is at least five (5) feet of clear-
ance above the generator, three (3) feet of clearance on sides
and front, and 18 inches of clearance at back of unit.
Install the unit where rain gutter down spouts, roof run-off,
landscape irrigation, water sprinklers or sump pump discharge
does not flood the unit or spray the enclosure, including any air
inlet or outlet openings.
Install the unit where services will not be affected or obstructed,
including concealed, underground or covered services such as
electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one direction, face the
generator air inlet openings to the prevailing winds.
Install the generator as close as possible to the fuel supply, to
reduce the length of piping.
• Install the generator as close as possible to the transfer switch.
REMEMBER THAT LAWS OR CODES MAY REGULATE THE
DISTANCE AND LOCATION.
The genset must be installed on a level surface. The base frame
must be level within two (2) inches all around.
The generator is typically placed on pea gravel or crushed
stone. Check local codes if a concrete slab is required. If a
concrete base slab is required, all federal, state and local codes
should be followed. Special attention should be given to the
concrete base slab which should exceed the length and width
of the generator by a minimum of six (6) inches (0.152 meters)
on all sides.
Figure 1.7 – Generator Clearances
General Information
8
1.10.2 INSTALLATION GUIDELINES FOR STATIONARY
STATIONARY AIR-COOLED 8, 10 AND 13 KVA
GENERATORS
The National Fire Protection Association has a standard for the
installation and use of stationary combustion engines. That
standard is NFPA 37 and its requirements limit the spacing of an
enclosed generator set from a structure or wall (Figure 1.8).
NFPA 37, Section 4.1.4, Engines Located Outdoors. Engines, and
their weatherproof housings if provided, that are installed outdoors
shall be located at least 5 ft. from openings in walls and at least 5
ft. from structures having combustible walls. A minimum separa-
tion shall not be required where the following conditions exist:
1. The adjacent wall of the structure has a fire resistance rating
of at least 1 hour.
2. The weatherproof enclosure is constructed of noncombus-
tible materials and it has been demonstrated that a fire within
the enclosure will not ignite combustible materials outside the
enclosure.
Annex A — Explanatory Material
A4.1.4 (2) Means of demonstrating compliance are by means
of full scale fire test or by calculation procedures.
Because of the limited spaces that are frequently available for
installation, it has become apparent that exception (2) would be
beneficial for many residential and commercial installations. With
that in mind, the manufacturer contracted with an independent
testing laboratory to run full scale fire tests to assure that the
enclosure will not ignite combustible materials outside the enclo-
sure.
The criteria was to determine the worst case fire scenario within
the generator and to determine the ignitability of items outside the
engine enclosure at various distances. The enclosure is construct-
ed of non-combustible materials and the results and conclusions
from the independent testing lab indicated that any fire within the
generator enclosure would not pose any ignition risk to nearby
combustibles or structures, with or without fire service personnel
response.
Based on this testing and the requirements of NFPA 37, Sec 4.1.4,
the guidelines for installation of the generators listed above are
changed to 18 inches (457mm) from the back side of the genera-
tor to a stationary wall or building. For adequate maintenance and
airflow clearance, the area above the generator should be at least
4 feet with a minimum of 3 feet at the front and ends of the enclo-
sure. This would include trees, shrubs and vegetation that could
obstruct airflow. See the diagram on the reverse of this page and
the installation drawing within the owner’s manual for details.
Generator exhaust contains DEADLY carbon monoxide gas. This
dangerous gas can cause unconsciousness or death. Do not place
the unit near windows, doors, fresh air intakes (furnaces, etc.) or
any openings in the building or structure, including windows and
doors of an attached garage.
If the AUTO/OFF/MANUAL switch is not set
to its OFF position, the generator can crank
and start as soon as the battery cables are
connected. If the utility power supply is not
turned off, sparking can occur at the battery
posts and cause an explosion.
1.11 BATTERY REQUIREMENTS
See the Specifications section for correct battery size and rating.
1.12 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if necessary and
have the battery fully charged before installing it.
Before installing and connecting the battery, complete the follow-
ing steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 7.5A fuse from the generator control panel.
Battery cables were factory connected at the generator (Figure
1.9). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter contactor) to the
battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame ground) to the
battery post indicated by a negative, NEG or (—).
6. Install the battery post covers (included).
NOTE:
Dielectric grease should be used on battery posts to aid in the
prevention of corrosion.
NOTE:
Damage will result if battery connections are made in reverse.
NOTE:
In areas where temperatures regularly fall below 32° F (0° C) it
is recommended that a pad type battery heater be installed to
aid in cold climate starting.
Figure 1.9 – Battery Cable Connections
General Information
9
General Information
Figure 1.8 – Installation Guidelines
18 inches
Minimum Distance
36 inches
36 inches
36 inches
60 inches 60 inches
Existing Wall
No operable windows or openings in the wall permitted
within 5 feet from any point of the generator.
Top of Generator
60” Minimum
60” Recommended
Minimum From Ends
18 inches
Minimum
Generator
Clearance from operable
windows, doors, any
openings in the wall,
shrubs or vegetation over
12” in height
Clearance from the ends and front of the
generator must be 36 inches. This would
include shrubs, trees and any kind of
vegetation. Clearance at the top should
be a minimum of 60 inches from any
structure, overhang or projections from
the wall. The generator should not be
placed under a deck or other structure
that is closed in and would limit or
constrain air flow.
These guidelines are based upon fire
testing of the generator enclosure and
the manufacturer’s requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
This drawing supersedes installation instructions in all air-cooled installation and owner’s manuals dated previous
to May 26, 2007.
10
Post Installation Start-up and Adjustments
1.13 THE BATTERY
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following
precautions are to be observed when work-
ing on batteries:
Remove the 7.5A fuse from the generator con-
trol panel.
• Remove watches, rings or other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots;
Do not lay tools or metal parts on top of the
battery.
Disconnect charging source prior to connecting
or disconnecting battery terminals.
Do not open or mutilate the battery.
Released electrolyte has been known to
be harmful to the skin and eyes, and to be
toxic.
The electrolyte is a dilute sulfuric acid that
is harmful to the skin and eyes. It is electri-
cally conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing.
Where electrolyte contacts the skin, wash it off
immediately with water.
Where electrolyte contacts the eyes, flush thor-
oughly and immediately with water and seek
medical attention.
Spilled electrolyte is to be washed down with
an acid neutralizing agent. A common practice
is to use a solution of 1 pound (500 grams)
bicarbonate of soda to 1 gallon (4 liters) of
water. The bicarbonate of soda solution is to
be added until the evidence of reaction (foam-
ing) has ceased. The resulting liquid is to be
flushed with water and the area dried.
Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The fol-
lowing procedures are to be followed:
• DO NOT SMOKE when near the battery.
DO NOT cause flame or spark in battery area.
Discharge static electricity from body before
touching the battery by first touching a ground-
ed metal surface.
Be sure the AUTO/OFF/MANUAL switch is
set to the OFF position before connecting
the battery cables. If the switch is set to
AUTO or MANUAL, the generator can crank
and start as soon as the battery cables are
connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the gener-
ator control panel, or sparking may occur at
the battery posts as the cables are attached
and cause an explosion.
Servicing of the battery is to be performed or supervised by per-
sonnel knowledgeable of batteries and the required precautions.
Keep unauthorized personnel away from batteries.
See the Specifications section for the correct size and rating when
replacing the battery. Have these procedures performed at the
intervals specified in the “Service Schedule.” A negative ground
system is used. Battery connections are shown on the wiring dia-
grams. Make sure the battery is correctly connected and terminals
are tight. Observe battery polarity when connecting the battery to
the generator set.
1.14 BATTERY CHARGER
NOTE:
The battery charger is integrated into the control module in all
models.
It operates as a "Smart Charger" which ensures output is continu-
ally optimized to promote maximum battery life and charging levels
are at safe conditions. The user can monitor both battery voltage
and current charge in both "Boost" and "Float" modes on the LCD
display on the controller.
NOTE:
There is a warning on the LCD display when the battery needs
service.
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the factory prior to
being shipped and do not require any type of break-in.
NOTE:
This unit comes filled with oil from the factory. Check the oil
level and add the appropriate amount if necessary.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its OFF (or OPEN)
position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF
position.
3. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
4. Turn OFF all loads connected to the transfer switch terminals
T1 and T2.
5. Check the engine crankcase oil level and, if necessary, fill to
the dipstick FULL mark with the recommended oil. Do not fill
above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must have been
properly purged and leak tested in accordance with applicable
fuel-gas codes. All fuel shutoff valves in the fuel supply lines
must be open.
11
During initial start up only, the generator may exceed the normal
number of start attempts and experience an “over crank” fault (See
the "Overcrank" section). This is due to accumulated air in the fuel
system during installation. Reset the control board and restart up
to two more times, if necessary. If unit fails to start, contact the
local dealer for assistance.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
2.2 CHECK TRANSFER SWITCH
OPERATION
Refer to the "Manual Transfer Operation" section, of the owner’s
manual for procedures.
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned
off. Failure to turn off all power voltage sup-
plies will result in extremely hazardous and
possibly fatal electrical shock.
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its OFF (or OPEN)
position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF
position.
3. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
4. Turn on the utility power supply to the transfer switch using
the means provided (such as a utility main line circuit break-
er).
The transfer switch is now electrically
“hot.” Contact with “hot” parts will result in
extremely hazardous and possibly fatal
electrical shock. Proceed with caution.
5. Use an accurate AC voltmeter to check utility power source
voltage across transfer switch terminals N1 and N2. Nominal
line-to-line voltage should be 220 volts AC.
6. When certain that utility supply voltage is compatible with
transfer switch and load circuit ratings, turn OFF the utility
power supply to the transfer switch.
7. On the generator panel, set the Auto/Off/ Manual switch to
MANUAL. The engine should crank and start.
8. Let the engine warm up for about five minutes to allow inter-
nal temperatures to stabilize. Then, set the generator’s main
circuit breaker to its ON (or closed) position.
Proceed with caution! Generator power volt-
age is now supplied to the transfer switch.
Contact with live transfer switch parts will
result in dangerous and possibly fatal electri-
cal shock.
9. Connect an accurate AC voltmeter and a frequency meter
across transfer switch terminal lugs E1 and E2. Voltage
should be 220-230 at a frequency of 49.5-50.5 Hertz.
10. Set the generator’s main circuit breaker to its OFF (or OPEN)
position. Let the engine run at no-load for a few minutes to
stabilize internal engine generator temperatures.
11. Set the generator's AUTO/OFF/MANUAL switch to OFF. The
engine should shut down.
NOTE:
It is important not to proceed until certain that generator AC
voltage and frequency are correct and within the stated limits.
2.4 GENERATOR TESTS UNDER
LOAD
To test the generator set with electrical loads applied, proceed as
follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) posi-
tion.
2. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to OFF.
4. Turn OFF the utility power supply to the transfer switch,
using the means provided (such as a utility main line circuit
breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned
off. Failure to turn off all power voltage sup-
plies will result in extremely hazardous and
possibly fatal electrical shock.
5. Manually set the transfer switch to the STANDBY position, i.e.,
load terminals connected to the generator's E1/E2 terminals.
The transfer switch operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch to MANUAL.
The engine should crank and start immediately.
7. Let the engine stabilize and warm up for a few minutes.
8. Set the generator’s main circuit breaker to its ON (or CLOSED)
position. Loads are now powered by the standby generator.
9. Turn ON the load center of the transfer switch (T1 and T2).
10. Connect an accurate AC voltmeter and a frequency meter
across terminal lugs E1 and E2.
Voltage should be greater than 220 volts and frequency
should be 50 Hz.
11. Let the generator run at full rated load for 20-30 minutes.
Listen for unusual noises, vibration or other indications of
abnormal operation. Check for oil leaks, evidence of overheat-
ing, etc.
Post Installation Start-up and Adjustments
12
Operation
12. When testing under load is complete, turn OFF electrical loads.
13. Set the generator's main circuit breaker to its OFF (or OPEN)
position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The engine should
shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation, proceed as
follows:
1. Set generator’s main circuit breaker to its OFF (or open) posi-
tion.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn OFF the utility power supply to the transfer switch, using
means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the UTILITY position, i.e.,
load terminals connected to the utility power source side.
5. Turn ON the utility power supply to the transfer switch, using the
means provided (such as a utility main line circuit breaker).
6. Set the generator's main circuit breaker to its ON (or CLOSED)
position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The system is
now ready for automatic operation.
8. Turn OFF the utility power supply to the transfer switch.
With the AUTO/OFF/MANUAL switch at AUTO, the engine should
crank and start when the utility source power is turned OFF after a
10 second delay. After starting, the transfer switch should connect
load circuits to the standby side after a five (5) second delay. Let
the system go through its entire automatic sequence of operation.
With the generator running and loads powered by generator AC
output, turn ON the utility power supply to the transfer switch. The
following should occur:
After about 15 seconds, the switch should transfer loads back
to the utility power source.
About one minute after re-transfer, the engine should shut down.
3.1 CONTROL PANEL INTERFACE
3.1.1 USING THE AUTO/OFF/MANUAL SWITCH
(FIGURE 3.1)
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting occurs when utility
power source voltage droops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch
to OFF and remove the fuses before work-
ing on or around the generator or transfer
switch. Then, place a “DO NOT OPERATE”
tag on the generator panel and on the trans-
fer switch.
1. AUTO” Position – Selecting this switch activates fully auto-
matic system operation. It also allows the unit to automatically
start and exercise the engine every seven days with the setting
of the exercise timer (see the Setting the Exercise Timer sec-
tion).
2. “OFF” Position – This switch position shuts down the engine.
This position also prevents automatic operation.
3. “MANUAL” Position – Set the switch to MANUAL to crank
and start the engine. Transfer to standby power will not occur
unless there is a utility failure.
3.1.2 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. Once it is set,
the generator will start and exercise every seven days, on the day
of the week and at the time of day specified. During this exercise
period, the unit runs for approximately 12 minutes and then shuts
down. Transfer of loads to the generator output does not occur
during the exercise cycle unless utility power is lost.
Figure 3.1 – 8/10/13 KVA Generator Control Panel
Escape
MAIN FUSE
AUTO OFF MANUAL
7.5 AMP
Enter
INSTALLATION ASSISTANT
Interconnect System Self Test Feature (follow the on-screen
prompts)
Upon power up, this controller will go through a system self test
which will check for the presence of utility voltage on the DC
circuits. This is done to prevent damage if the installer mistakenly
connects AC utility power sense wires into the DC terminal block. If
utility voltage is detected, the controller will display a warning mes-
sage and lock out the generator, preventing damage to the control-
ler. Power to the controller must be removed to clear this warning.
Utility voltage must be turned on and present at the N1 and N2
terminals inside the generator control panel for this test to be
performed and pass.
NOTE:
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT
WIRES IS NOT WARRANTABLE!
13
This test will be performed each time the controller is powered up.
Upon first power up of the generator, the display interface will
begin an installation assistant. The assistant will prompt the user
to set the minimum settings to operate. These settings are sim-
ply: Current Date/Time and Exercise Day/Time. The maintenance
intervals will be initialized when the exercise time is entered (Figure
3.1).
The exercise settings can be changed at any time via the "EDIT"
menu (see Appendix, "Menu System").
If the 12 volt battery is disconnected or the fuse removed, the
Installation Assistant will operate upon power restoration. The
only difference is the display will only prompt the customer for the
current Time and Date.
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO
INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING
UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN
THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE
PROMPTED TO ENTER AN EXERCISE TIME.
NOTE:
The exerciser will only work in the AUTO mode and will not work
unless this procedure is performed. The current date/time will
need to be reset every time the 12 volt battery is disconnected
and then reconnected, and/or when the fuse is removed.
Display Interface Menus
The LCD display is organized as detailed below:
The “Home” page, this page is the default page which will be
displayed if no keys are pressed for 30 seconds. This page
normally shows the current Status message and the current
date and time. The highest priority active Alarm and/or Warning
will be automatically posted on this page as well as flashing
the backlight when such an event is detected. In the case of
multiple Alarms or Warnings, only the first message will be
displayed. To clear an Alarm or Warning, see the Protection
Systems section - Clear Alarm.
The display backlight is normally off. If the user presses any
key, the backlight will come on automatically and remain on for
30 seconds after the last key was pressed.
The “Main Menu” page will allow the user to navigate to all other
pages or sub-menus by using the Left/Right and Enter keys.
This page can be accessed at any time with several presses of
the dedicated Escape key. Each press of the Escape key takes
you back to the previous menu until the main menu is reached.
This page displays the following options: HISTORY; STATUS;
EDIT; AND DEBUG. (See the Appendix - "Menu System".)
3.2 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their
UTILITY position, i.e., loads connected to the utility power
source.
2. Be sure that normal UTILITY power source voltage is avail-
able to transfer switch terminal lugs N1 and N2 (Refer to the
Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or CLOSED)
position.
With the preceding steps complete, the generator will start auto-
matically when utility source voltage drops below a preset level.
After the unit starts, loads are transferred to the standby power
source. Refer to the Sequence of Automatic Operation section.
3.3 SEQUENCE OF AUTOMATIC
OPERATION
3.3.1 UTILITY FAILURE
Initial Conditions: Generator in Auto, ready to run, load being sup-
plied by utility source. When utility fails (below 60% of nominal),
a 10 second line interrupt delay time is started. If the utility is still
gone when the timer expires, the engine will crank and start. Once
started, a five (5) second engine warm-up timer will be initiated.
When the warm-up timer expires, the control will transfer the load
to the generator. If the utility power is restored (above 80% of
nominal) at any time from the initiation of the engine start until the
generator is ready to accept load (5 second warm-up time has not
elapsed), the controller will complete the start cycle and run the
generator through its normal cool down cycle; however, the load
will remain on the utility source.
3.3.2 CRANKING
The system will control the cyclic cranking as follows: 16 second
crank, seven (7) second rest, 16 second crank, seven (7) second
rest followed by three (3) additional cycles of seven (7) second
cranks followed by seven (7) second rests.
Choke Operation
1. The 990cc engines have an electric choke in the air box that
is automatically controlled by the electronic control board.
2. The 530cc engines have an electric choke on the divider panel
air inlet hose that is automatically controlled by the electronic
control board.
Failure to Start
This is defined as any of the following occurrences during crank-
ing:
1. Not reaching starter dropout within the specified crank cycle.
Starter dropout is defined as four (4) cycles at 1,000 RPM.
2. Reaching starter dropout, but then not reaching 2200 RPM
within 15 seconds. In this case the control board will go into
a rest cycle for seven (7) seconds, then continue the rest of
the crank cycle.
During a rest cycle the start and fuel outputs are de-energized and
the magneto output is shorted to ground.
Cranking Conditions
The following notes apply during cranking cycle.
1. Starter motor will not engage within five (5) seconds of the
engine shutting down.
2. The fuel output will not be energized with the starter.
3. The starter and magneto outputs will be energized together.
Operation
14
4. Once the starter is energized the control board will begin look-
ing for engine rotation. If it does not see an RPM signal within
three (3) seconds it will shut down and latch out on RPM
sensor loss.
5. Once the control board sees an RPM signal it will energize the
fuel solenoid, drive the throttle open and continue the crank
sequence.
6. Starter motor will disengage when speed reaches starter
dropout.
7. If the generator does not reach 2200 RPM within 15 seconds,
re-crank cycle will occur.
8. If engine stops turning between starter dropout and 2200
RPM, the board will go into a rest cycle for seven (7) seconds
then re-crank (if additional crank cycles exist).
9. Once started, the generator will wait for a hold-off period
before starting to monitor oil pressure and oil temperature
(refer to the Alarm Messages section for hold-off times).
10. During Manual start cranking, if the Mode switch is moved
from the Manual position, the cranking stops immediately.
11. During Auto mode cranking, if the Utility returns, the cranking
cycle does NOT abort but continues until complete. Once the
engine starts, it will run for one (1) minute, then shut down.
3.3.3 LOAD TRANSFER
The transfer of load when the generator is running is dependent
upon the operating mode as follows:
1. Manual
Will not transfer to generator if utility is present.
Will transfer to generator if utility fails (below 65% of nominal
for 10 consecutive seconds.
Will transfer back when utility returns for 15 consecutive
seconds. The engine will continue to run until removed from
the Manual mode.
2. Auto
Will start and run if Utility fails for 10 consecutive seconds.
Will start a five (5) second engine warm-up timer.
Will not transfer if utility subsequently returns.
Will transfer to generator if utility is still not present.
Will transfer back to utility once utility returns (above 75% of
nominal) for 15 seconds.
• Will transfer back to utility if the generator is shut down for
any reason (such as the switch is in the OFF position or a
shutdown alarm.
After transfer, will shut down engine after one (1) minute
cool-down time.
3. Exercise
Will not exercise if generator is already running in either Auto
or Manual mode.
During exercise, the controller will only transfer if utility fails
during exercise for 10 seconds, and will switch to Auto
mode.
3.3.4 UTILITY RESTORED
Initial Condition: Generator supplying power to customer load.
When the utility returns (above 80% of nominal), a 15 second
return to utility timer will start. At the completion of this timer, if
the utility supply is still present and acceptable, the control will
transfer the load back to the utility and run the engine through a
one (1) minute cool down period and then shut down. If utility fails
for three (3) seconds during this cool down period, the control
will transfer load back to the generator and continue to run while
monitoring for utility to return.
3.4 MANUAL TRANSFER
OPERATION
3.4.1 TRANSFER TO GENERATOR POWER SOURCE
To start the generator and activate the transfer switch manually,
proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch to OFF.
2. Set the generator’s main circuit breaker to its OFF (or OPEN)
position.
3. Turn OFF the utility power supply to the transfer switch
using the means provided (such as a utility main line circuit
breaker).
Do not attempt to activate the transfer switch
manually until all power voltage supplies to
the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and pos-
sibly fatal electrical shock.
4. Use the manual transfer handle inside the transfer switch to
move the main contacts to their STANDBY position, i.e., loads
connected to the standby power source (Figure 3.2).
5. To crank and start the engine, set the AUTO/OFF/MANUAL
switch to MANUAL.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON (or CLOSED)
position. The standby power source now powers the loads.
Figure 3.2 – Manual Transfer Switch Operation
Operation
15
3.4.2 TRANSFER BACK TO UTILITY POWER SOURCE
When utility power has been restored, transfer back to that source
and shut down the generator. This can be accomplished as fol-
lows:
1. Set the generator’s main circuit breaker to its OFF (or OPEN)
position.
2. Let the engine run for a minute or two at no-load to stabilize
the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch to its OFF (or
OPEN) position. The engine should shut down.
4. Check that utility power supply to the transfer switch is turned
OFF.
Do not attempt to activate the transfer switch
manually until all power voltage supplies to
the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and pos-
sibly fatal electrical shock.
5. Use the manual transfer handle inside the transfer switch to
move the main contacts back to their UTILITY position, i.e.,
loads connected to the utility power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer switch using
the means provided.
7. Set the system to automatic operation as outlined in Automatic
Transfer Operation section.
3.5 SIDE COMPARTMENT
(FIGURES 3.3 & 3.4)
Local codes may require this compartment to be locked. A hasp is
provided so the owner can secure the compartment with their own
padlock. Check local codes in the area.
3.5.1 MAIN CIRCUIT BREAKER
This is a 2-pole breaker rated according to the Specifications sec-
tion.
Figure 3.3 – Side Compartment
3.5.2 EXTERIOR READY LIGHTS
• Green LED ‘Ready’ light is on when utility is present and switch
is in AUTO indicating the generator is ready and when the gen-
erator is running.
• Red LED ‘Alarm’ light is on when the generator is OFF or a fault
is detected. (See the Protections Systems section.)
Yellow LED ‘Maintenance’ light (See the Protections Systems
section.)
Figure 3.4 – Open Side Compartment
LED Indicator Lights Main Circuit Breaker
3.6 PROTECTION SYSTEMS
3.6.1 ALARMS
Highest Priority (Latching) Displayed on the control panel and the
external red LED. They must be cleared before the alarm message
goes away. The alarm log records each occurrence (see Appendix
- "Menu System").
Low Oil Pressure (Shutdown Alarm)
A five (5) second delay on start-up and seven (7) second delay
once the engine is running.
This switch (Figure 3.5) has normally closed contacts that are
held open by engine oil pressure during operation. Should the oil
pressure drop below the five (5) PSI range, switch contacts close
and the engine shuts down. The unit should not be restarted until
oil level is verified.
High Engine Temperature (Shutdown Alarm – Auto Reset)
A 10 second delay on start-up and one (1) second delay before
shutdown. Auto reset when the condition clears and restart the
engine if a valid start signal is still present.
This switch’s contacts (Figure 3.5) close if the temperature should
exceed approximately 144° C (293° F), initiating an engine shut-
down. Once the oil temperature drops to a safe level the switch’s
contacts open again.
Operation
16
Over Crank (Shutdown Alarm)
This occurs if the engine has not started within the specified crank
cycle. (See "Cranking" section.)
NOTE:
The oil drain hose may be routed in the opposite direction as
shown in figure.
Figure 3.5 – Low Oil Pressure and
High Temperature Switches
Oil Filter
Oil
Drain
Hose
Low Oil Switch
High Temp Switch
L
o
o
s
e
n
Over Speed (Shutdown Alarm)
4320 RPM for three (3) seconds or 4500 RPM immediately. This
feature protects the generator from damage by shutting it down
if it happens to run faster than the preset limit. This protection
also prevents the generator from supplying an output that could
potentially damage appliances connected to the generator circuit.
Contact the nearest Dealer if this failure occurs.
RPM Sense Loss (Shutdown Alarm)
During cranking, if the Control Board does not see a valid RPM
signal within three (3) seconds, it will shut down and lock out on
RPM sense loss. While engine is running, if RPM signal is lost for
one (1) second the Control Board will shut the engine down, wait
15 seconds, then re-crank the engine. If no RPM signal is detected
within the first three (3) seconds of cranking, the Control Board
will shut the engine down and latch out on RPM sensor loss. If the
RPM signal is detected, the engine will start and run normally. If
the RPM signal is subsequently lost again, the Control Board will
try one more re-crank attempt before latching out and displaying
the RPM sensor failure message.
Under-frequency (Shutdown Alarm)
After starting, if the generator stays under frequency for more than
30 seconds it will shut down. The under-frequency setting is 45
Hz.
Internal Fault (Shutdown Alarm)
This alarm cannot be cleared, call service dealer.
Undervoltage (Shutdown Alarm)
If the generator voltage falls below 60% of nominal for more than
five (5) seconds, it shuts down.
Overvoltage (Shutdown Alarm)
If the generator voltage rises above 110% of rating for greater than
three (3) seconds, an alarm will be issued and the unit will shut
down.
If the generator voltage rises above 130% of rating for greater than
0.2 seconds, an alarm will be issued and the unit will shut down.
Clear Alarm
Clear the alarm by setting the AUTO/OFF/MANUAL switch to the
OFF position. Press the ENTER key to unlatch any active fault and
clear the corresponding alarm message.
3.6.2 COMMON ALARM RELAY
The common alarm relay will be activated if there is a shutdown
alarm. It will not activate on warnings or indicate that the AUTO/
OFF/MANUAL switch is in the OFF position. The OFF position will
clear the alarms and the relay. The relay will not be used to indicate
a generator is not activated.
The common alarm terminals are wired to a set of potential-free
(dry) contacts on the Nexus contoller board. These Normally Open
(N.O.) contacts close when an alarm condition occurs and are
used to activate a remote signaling device. The circuit is rated for
a maximum of 130mA at 24 VDC.
3.6.3 WARNINGS
Second Priority (Non-latching) Displayed on the control panel
and the external yellow LED (V-twins only). Warnings automati-
cally clear when the monitored condition goes away. Warnings are
recorded in the alarm log. Warnings cannot cause shutdowns.
Low Battery
The Control Board monitors battery voltage and displays a warn-
ing if the battery voltage falls below 11.9 volts for one (1) minute.
Warning is automatically cleared if the battery voltage rises above
12.4 volts. Battery voltage is not monitored during the crank cycle.
Exercise Set Error
If the exercise period becomes corrupted, a warning message
will be displayed. This message will only clear when the exercise
period is reset.
3.6.4 MAINTENANCE ALERTS
Third priority
Operation
17
Maintenance Message
When a maintenance period expires, a warning message will
be displayed. The alert can be reset by pressing the Enter key,
which will cause the user to be prompted to confirm the action.
Resetting will clear the alert and reset the maintenance counters
for all conditions annunciated. The history log will record the alert.
The maintenance counter will not accumulate without battery
power. Once battery power is restored, the set time prompt will be
displayed. The maintenance counters will be adjusted to the new
time and date.
NOTE:
Since most maintenance alerts will occur at the same time
(most have two (2) year intervals), only one will appear on the
display at any one time. Once the first alert is cleared, the next
active alert will be displayed.
3.7 SHUTTING THE GENERATOR
DOWN WHILE UNDER LOAD
To safely stop and start a loaded generator follow these steps.
3.7.1 ISOLATE THE MAIN SERVICE DISTRIBUTION
PANEL
1. At the main service distribution panel, open (turn off) the main
service entrance breaker.
3.7.2 STOPPING THE GENERATOR
1. Turn the Main Circuit Breaker off (Figure 3.6).
2. If generator has a GFCI Outlet and it is being used, turn off the
15 Amp Outlet Breaker (Figure 3.6).
3. Allow the generator to run for 1 minute without load to cool
down.
4. Turn the Auto/Off/Manual switch to the Off position (Figure
3.7).
5. If the generator will be left off for longer than 1 hour without
utility present remove the 7.5 Amp Main Fuse from the control
panel (Figure 3.7). This will prevent the control panel from
running down the battery.
Figure 3.6 – Open Side Compartment
120V GFCI Outlet 15 Amp Outlet Breaker
Main Circuit BreakerLED Indicator Lights
3.7.3 STARTING THE GENERATOR
1. If the Main Fuse was removed, replace the fuse. The startup
wizard will be displayed, allowing the correct time and date to
be entered. It will not be necessary to re-enter the activation
code.
2. Turn the Auto/Off/Manual switch to the Auto position. After a
short delay the generator will start.
3. Allow the generator to run for 15 seconds to allow the engine
to warm up.
4. Turn on the Main Circuit Breaker.
5. Turn on the Outlet Breaker if necessary.
Figure 3.7 – 8 - 20kW Generator Control Panel
Escape
MAIN FUSE
AUTO OFF MANUAL
7.5 AMP
Enter
3.7.4 REPOWER THE MAIN SERVICE DISTRIBUTION
PANEL
1. At the main service distribution panel, close (turn on) the main
service entrance breaker.
This method will ensure proper transfer between generator and
utility in the event that utility returns while the generator is shut
off.
Operation
18
4.1 FUSE
The 7.5 amp fuse on the control panel protects the DC control cir-
cuit against overload (Figure 3.1). This fuse is wired in series with
the battery output lead to the panel. If this fuse element has melted
open, the engine will not be able to crank or start. Replace this fuse
using only an identical 7.5 amp replacement fuse. Whenever the
fuse is removed or replaced, the exercise timer needs to be reset.
4.2 CHECKING THE ENGINE OIL
LEVEL
For oil capacities, see the Specifications section. For engine oil
recommendations, see the Engine Oil Recommendations section.
When power outages necessitate running the generator for extend-
ed periods of time, the oil level should be checked daily.
To check the engine oil level, proceed as follows (Figures 4.1 and
4.2):
1. If the generator is running during a utility outage, first turn OFF
all associated loads running in the residence. Second, turn the
generator's main circuit breaker to the OFF position.
2. Move the AUTO/OFF/MANUAL switch to the OFF position.
3. Remove the dipstick and wipe it dry with a clean cloth.
4. Completely insert the dipstick; then, remove it again. The oil
level should be at the dipstick “Full” mark. If necessary, add
oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL
MARK.
5. Install the dipstick.
6. Reset the AUTO/OFF/MANUAL switch to its original position.
7. If the generator was running during a utility outage, first turn
the generator's main circuit breaker back to the ON position.
Second, turn ON needed loads in the residence.
Figure 4.1 — Oil Dipstick, 8 KVA
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
Figure 4.2 — Oil Dipstick and Fill, 10 & 13 KVA
4.3 CHANGING THE ENGINE OIL
Hot oil may cause burns. Allow engine to
cool before draining oil. Avoid prolonged
or repeated skin exposure with used oil.
Thoroughly wash exposed areas with soap.
4.3.1 OIL CHANGE INTERVALS
See the "Service Schedule" section.
4.3.2 ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum Institute (API)
Service Class SJ, SL or better. Use no special additives. Select the
appropriate viscosity oil grade according to the expected operating
temperature.
• SAE 30 Above 32° F
• 10W-30 Between 40° F and -10° F
• Synthetic 5W-30 10° F and below
SAE 30
SAE 30
Synthetic 5W-30
Syn the tic 5W- 30
10W-30
10W -30
Maintenance
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

Generac 8 kVA 0059141 Руководство пользователя

Категория
Генераторы
Тип
Руководство пользователя

Задайте вопрос, и я найду ответ в документе

Поиск информации в документе стал проще с помощью ИИ

на других языках